Three-Phase Power Calculator

Updated

Three-Phase Power Calculator finds kW, kVA and kVAR from line voltage, current and power factor, or the line amps for a known kW or kVA load, with per-phase values in wye or delta.

Quick Setup

Know volts and amps to get kW, or know kW or kVA to get amps. A balanced load is assumed.

A
Voltage and ConnectionL-L, Wye

Line-to-line is measured between two phases. Connection only changes the per-phase card.

Three-Phase Real Power (P)
35.33 kW Real Power
P = √3 × V × I × PF = 1.732 × 480 V × 50 A × 0.85
41.57 kVA Apparent Power
Reactive Power (Q)21.9 kVAR
Phase Angle (φ)31.79°
Apparent power is what the supply must deliver, real power does the work, and reactive power only swings between source and load each cycle.
11.78 kW per Phase
Phase Voltage277.1 V
Phase CurrentSame as line
A balanced load splits power evenly across three phases. Each wye phase sees line-to-neutral voltage, and each delta phase sees line voltage at less current.
42.5 A at Unity Power Factor
Extra Current From Low PF7.5 A
Added Line Loss38.41%
At unity power factor the same kW needs the least current. A lower power factor adds current that does no work, and cable losses rise with its square.
1.415 A per kW
Real Power per Amp706.7 W
Same Load on Single-Phase86.6 A
Quick factors that hold at this voltage and power factor. Single-phase means a two-wire load at the same voltage, which draws 1.732 times the current.
Power TrianglePF 0.85
Real Power P = 35.33 kWReactive Power Q = 21.9 kVARApparent Power S = 41.57 kVAAngle φ = 31.79°, PF 0.85
Formulas With Your NumbersP = √3 × V × I × PF
FormulaYour NumbersResult
S = √3 × V × I1.732 × 480 V × 50 A41.57 kVA
P = S × PF41.57 kVA × 0.8535.33 kW
Q = S × sin φ41.57 kVA × 0.526821.9 kVAR
φ = arccos(PF)arccos(0.85)31.79°
Amps at Common Voltages35.33 kW at PF 0.85
Line-to-LineLine-to-NeutralAmps for 35.33 kW
208 V120.1 V115.4 A
240 V138.6 V100 A
400 V230.9 V60 A
415 V239.6 V57.83 A
480 V277.1 V50 A
600 V346.4 V40 A
Balanced Load Assumed
The formulas assume the same current in L1, L2 and L3. For unequal phases, work out each phase from its own current and line-to-neutral voltage, then add the three.

Three-Phase Power Calculator Formulas for kW, kVA and kVAR

Three-phase power is calculated from the line-to-line voltage, the line current and the power factor. The Three-Phase Power Calculator returns all three kinds of power from those entries. Apparent power comes first, since it needs only volts and amps.

S is in volt-amperes, and dividing by 1,000 gives kVA. That is the kVA formula for any balanced three-phase load. The square root of three is 1.732, and it appears because the line voltage is measured between two phases that are 120 degrees apart.

Real power in kW is the apparent power times the power factor. This is the 3 phase load calculation formula most people need, and it is how to calculate kW in 3-phase from a clamp meter reading. Reactive power is the third side of the triangle.

The tool opens on a 3-phase power calculation example of 480 V, 50 A and a power factor of 0.85. Apparent power is 1.732 × 480 × 50, or 41.57 kVA. Real power is 41.57 × 0.85, or 35.33 kW, and reactive power is 21.9 kVAR at a phase angle of 31.79 degrees.

Tony Kuphaldt's Lessons in Electric Circuits defines the three terms. True power is what the circuit actually uses, in watts. Reactive power is absorbed and returned by the load without being used, in VAR. Apparent power is voltage times current with no regard to phase angle, in VA.

The Power Triangle panel draws those three as a right triangle, with real power along the base, reactive power up the side and apparent power as the long edge. The Formulas With Your Numbers panel lists each line of working.

kW to Amps and kVA to Amps

The Known Values menu of the Three-Phase Power Calculator also runs the formulas backward. Voltage and kW finds the line current, which makes the tool a 3 phase power calculator for kW to amps. The button changes to Calculate Line Current.

A 30 kW load at 480 V and 0.85 power factor draws 42.45 A. The same entry reports 35.29 kVA of apparent power and 18.59 kVAR. Voltage and kVA skips the power factor for current, so a 75 kVA transformer at 480 V carries 90.21 A at full load.

Load at PF 0.85208 V240 V400 V480 V
1 kW3.266 A2.83 A1.698 A1.415 A
15 kW48.98 A42.45 A25.47 A21.23 A
20 kW65.31 A56.6 A33.96 A28.3 A
30 kW97.97 A84.9 A50.94 A42.45 A

So 20 kW on a 3 phase supply is 28.3 A at 480 V and 65.31 A at 208 V, both at 0.85 power factor. At unity power factor the 480 V figure falls to 24.06 A. The fourth result card gives the same ratio as amps per kW, which reads 1.415 A per kW for the default entry.

The Amps at Common Voltages panel repeats the load across 208, 240, 400, 415, 480 and 600 V. The default 35.33 kW needs 115.4 A at 208 V and 40 A at 600 V. The Current Calculator covers the same sum for DC and single-phase circuits.

Amps to kVA and kW: 16A, 32A, 100A and 400A

Going from amps to power always needs the voltage, which is why the Three-Phase Power Calculator asks for it first. One kVA is not equal to one ampere. At 480 V a single kVA is 1.203 A, and at 208 V it is 2.776 A. The table gives apparent power for common breaker and supply sizes.

Line current208 V240 V400 V480 V
12 A4.323 kVA4.988 kVA8.314 kVA9.977 kVA
16 A5.764 kVA6.651 kVA11.09 kVA13.3 kVA
32 A11.53 kVA13.3 kVA22.17 kVA26.6 kVA
100 A36.03 kVA41.57 kVA69.28 kVA83.14 kVA
200 A72.05 kVA83.14 kVA138.6 kVA166.3 kVA
400 A144.1 kVA166.3 kVA277.1 kVA332.6 kVA

Kilowatts are the kVA figure times the power factor. A 32 A 3-phase supply at 400 V is 22.17 kVA, which is 22.17 kW into a resistive load and 18.84 kW at 0.85. A 100 A supply at 480 V is 83.14 kVA and 70.67 kW at 0.85. A 200 A supply at 480 V is 166.3 kVA and 141.3 kW at 0.85, and a 400 A service at 480 V is 332.6 kVA.

The same rule answers the kVA and kW questions. One kVA equals one kW only at unity power factor. To convert kVA to kW, multiply by the power factor. To go from kW to kVA, divide by it, so 1 kW at 0.85 needs 1.176 kVA.

L1, L2, L3 and Line-to-Neutral Voltage

L1, L2 and L3 are the three line conductors of a three-phase supply. Each carries an AC voltage shifted 120 degrees from the next, so three-phase is always AC and never DC. The voltage between any two lines is the line-to-line voltage, and the voltage from one line to the neutral is the line-to-neutral voltage.

The Voltage and Connection panel accepts either one. Enter 277 V as line-to-neutral and the Three-Phase Power Calculator converts it to 479.8 V line-to-line before running the formulas. The result note states the conversion.

The Load Connection choice changes only the per-phase card. Kuphaldt's chapter on Y and delta configurations gives the rules. In a wye, line voltage is phase voltage times the square root of three and the currents are equal. In a delta, the voltages are equal and line current is phase current times the square root of three.

For the 480 V, 50 A default the Three-Phase Power Calculator shows 11.78 kW per phase. Set to wye, each phase sees 277.1 V and the full 50 A. Set to delta, each winding sees 480 V and carries 28.87 A. Total power is the same either way.

Continental Control Systems lists the common electrical service types and voltages. It calls 208Y/120 V the most common commercial building service in North America, with 480Y/277 V in larger facilities. A 240 V three-phase delta is used mainly in industrial plants, and its four-wire high-leg version has one phase at 208 V to neutral.

The same source lists 400Y/230 V for Europe and 600Y/347 V for Canada. A 220 V figure does not say whether a supply is single-phase or three-phase. The phase count comes from the number of line conductors, and US three-phase services are named 208, 240 or 480 V, with 600 V less common.

To check 3-phase voltage, measure between each pair of lines and compare the three readings. Fluke describes clamp meters that read L1, L2 and L3 in turn and then show the L1-L2, L2-L3 and L3-L1 voltages. Those readings and the clamp current go straight into the tool.

The formulas assume the same current in all three lines. For unequal phases on a wye, the result note says to work out each phase from its own current and line-to-neutral voltage and add the three. Currents of 50 A, 40 A and 30 A at 277.1 V and 0.85 give 28.26 kW in total.

Power Factor and Extra Current

Power factor is the share of apparent power that does work. The third card of the Three-Phase Power Calculator shows what a low figure costs. At 0.85 the default load draws 50 A, where the same 35.33 kW at unity would need 42.5 A. The extra 7.5 A does no work.

Cable loss rises with the square of current, so the card also reports Added Line Loss. At 0.85 the lines waste 38.41% more than they would at unity. The table holds 480 V and 50 A and changes only the power factor.

Power factorReal powerReactive powerPhase angleAdded line loss
141.57 kW0 kVAR0°0%
0.9539.49 kW12.98 kVAR18.19°10.8%
0.937.41 kW18.12 kVAR25.84°23.46%
0.8535.33 kW21.9 kVAR31.79°38.41%
0.833.26 kW24.94 kVAR36.87°56.25%
0.729.1 kW29.69 kVAR45.57°104.1%

Apparent power stays at 41.57 kVA in every row, because volts and amps have not changed. At 0.7 the supply carries the same current but delivers 12.47 kW less, and delivering the same kW at 0.7 would more than double the line loss. Power factor goes in as a decimal, so 85% is entered as 0.85.

Three-Phase Against Single-Phase Power

Three-phase is used because it moves more power on less copper. Kuphaldt's chapter on three-phase power systems compares three ways to feed a 30 kW load at 120 V. Single-phase needs 250 A per conductor, split-phase needs 125 A and three-phase needs 83.33 A.

Over 1,000 foot runs that example needs more than half a ton of copper on single-phase, about 600 lb on split-phase and about 500 lb on three-phase. The highest voltage in the three-phase case is 208 V, lower than the 240 V of split-phase.

Single-phase AC uses one alternating voltage on two wires. The fourth card of the Three-Phase Power Calculator shows Same Load on Single-Phase for comparison. The default load would draw 86.6 A as a two-wire load at 480 V, against 50 A per line on three-phase, a ratio of 1.732.

Single-phase kW is volts times amps times power factor, with no 1.732. A 240 V, 100 A single-phase supply delivers 24 kW at unity, while 240 V three-phase at 100 A delivers 41.57 kW. As a single phase power calculator, the Electrical Power Calculator handles that case.

3-Phase Power Calculator Excel Formulas

A 3-phase power calculator in Excel needs three entries and six formulas. The cells below reproduce the Voltage and Current mode, and the last row runs kW back to amps as a check.

CellQuantityEntry or formulaResult
B1Line-to-line voltage, V480480
B2Line current, A5050
B3Power factor0.850.85
B4Apparent power, kVA=SQRT(3)*B1*B2/100041.57
B5Real power, kW=B4*B335.33
B6Reactive power, kVAR=SQRT(B4^2-B5^2)21.90
B7Phase angle, degrees=DEGREES(ACOS(B3))31.79
B8Line-to-neutral voltage, V=B1/SQRT(3)277.1
B9Amps from kW=B5*1000/(SQRT(3)*B1*B3)50

For a 3-phase power calculation formula PDF, the Print Results button under the Three-Phase Power Calculator prints the answer, the cards and the formula lines with your numbers, and the print dialog can save them as a PDF. Copy Results puts the same text on the clipboard.

From kW to kWh and Horsepower

A three-phase supply has no kWh figure of its own. Energy is real power times running hours, so the 35.33 kW from the Three-Phase Power Calculator default uses 282.6 kWh over an 8 hour shift. The Energy Consumption Calculator turns that into a cost at your rate.

One kW is 1.341 horsepower, since one horsepower is 745.7 W. The 35.33 kW default is 47.38 hp of electrical input. A motor's shaft output is lower than its input, so nameplate horsepower cannot be read straight from the kW drawn.