Boiler Size Calculator

Updated

Boiler size calculator for home heating and combi hot water: output and input in BTU/h and kW from floor area and climate, existing radiators, steam EDR, or a known room heat loss.

Boiler Size Setup

Pick the nearest city; its winter design temperature sets the heat loss per square foot.

Efficiency, Loop & Hot Water95% AFUE · +10% · ΔT 20°F · 58°F water
Recommended Boiler Output
88,000 BTU/h Combi Boiler
25.8 kW · 88.0 MBH · sized by space heating
92,632 BTU/h Input
Heat Loss at 15°F Design80,000 BTU/h
Baseboard to Give It Off (580 BTU/ft)138 ft
Input rating to shop for (output ÷ AFUE), plus the heat loss and the radiation that gives it off.
8.80 GPM Loop Flow
Copper Supply Pipe (Type L)1-inch
Water Speed in That Pipe3.42 ft/s
Heating loop flow from output ÷ (500 × ΔT) and the smallest Type L copper pipe at 4 ft/s (1.2 m/s) or less.
3.74 GPM Hot Water
Showers It Covers1.5 showers
Hot-Water Load (1 Shower)58,750 BTU/h
Hot water this combi makes at your shower temperature, and the load your showers put on it.
89 ft³/h Natural Gas
Propane · Oil at 95% AFUE1.01 gal/h · 0.67 gal/h
Electric Boiler at 240 V107 A
Fuel burned per hour at full fire for gas, propane and oil, and the current an electric boiler draws.
Boiler Size Chain80k Loss → 88k Output → 93k Input
Boiler Size Chain · 95% AFUEHeat Loss80,000 BTU/hSpace Heating Output ★88,000 BTU/hHot-Water Load58,750 BTU/hInput Rating92,632 BTU/h
Boiler Size by Design Temp15°F design: 40 BTU/sq ft
Winter Design TempExample CitiesHeat Loss FactorHeat LossBoiler OutputInput @ 95%
-47°F to -20°FFairbanks, Bemidji60 BTU/sq ft120,000 BTU/h132,000 BTU/h138,947 BTU/h
-19°F to 0°FMinneapolis, Chicago50 BTU/sq ft100,000 BTU/h110,000 BTU/h115,789 BTU/h
1°F to 15°F (Yours)Denver, New York40 BTU/sq ft80,000 BTU/h88,000 BTU/h92,632 BTU/h
16°F to 30°FAtlanta, Seattle30 BTU/sq ft60,000 BTU/h66,000 BTU/h69,474 BTU/h
31°F to 47°FHouston, Los Angeles20 BTU/sq ft40,000 BTU/h58,750 BTU/h61,842 BTU/h

Average home of 2,000 sq ft, with a 10% sizing allowance.

Boiler Size by Square Footage2,000 sq ft: 88k output
Home SizeHeat LossBoiler OutputInput @ 95%Loop Flow
1,000 sq ft40,000 BTU/h58,750 BTU/h61,842 BTU/h4.40 GPM
1,500 sq ft60,000 BTU/h66,000 BTU/h69,474 BTU/h6.60 GPM
2,000 sq ft (Yours)80,000 BTU/h88,000 BTU/h92,632 BTU/h8.80 GPM
2,500 sq ft100,000 BTU/h110,000 BTU/h115,789 BTU/h11.00 GPM
3,000 sq ft120,000 BTU/h132,000 BTU/h138,947 BTU/h13.20 GPM
4,000 sq ft160,000 BTU/h176,000 BTU/h185,263 BTU/h17.60 GPM
5,000 sq ft200,000 BTU/h220,000 BTU/h231,579 BTU/h22.00 GPM

At 15°F design, 40 BTU/sq ft heat loss; loop flow at 20°F ΔT.

Hot Water by Incoming Temp58°F water: 3.74 GPM
Incoming WaterRise to 105°FHot Water FlowShowers Covered
40°F65°F2.71 GPM1.1
45°F60°F2.93 GPM1.2
50°F55°F3.20 GPM1.3
55°F50°F3.52 GPM1.4
58°F (Yours)47°F3.74 GPM1.5
60°F45°F3.91 GPM1.6
65°F40°F4.40 GPM1.8
70°F35°F5.03 GPM2.0

Hot water 88,000 BTU/h can make; showers at 2.5 GPM each. Colder supply water means less hot-water flow.

Step-by-Step MathOutput = Larger of Heat and Hot Water
  1. Home envelope: 11 to 35 years old, no major renovations → average.
  2. Heat loss factor: average home at 15°F design (1°F to 15°F band, New York, NY) → 40 BTU/sq ft.
  3. Heat loss: 2,000 sq ft × 40 BTU/sq ft = 80,000 BTU/h.
  4. Space heating output: 80,000 × 1.1 = 88,000 BTU/h.
  5. Combi hot-water load: 1 × 2.5 GPM × 500 × 47°F rise = 58,750 BTU/h.
  6. Loop flow: 88,000 ÷ (500 × 20°F) = 8.80 GPM → 1-inch Type L copper at 3.42 ft/s.
  7. Input at 95% AFUE: 88,000 ÷ 0.95 = 92,632 BTU/h; natural gas = 92,632 ÷ 1,036 = 89 ft³/h (0.93 therms/h).
  8. Boiler output = larger of 88,000 and 58,750 = 88,000 BTU/h (25.8 kW).
Recommended Boiler: 88,000 BTU/h Output
At 15°F design, your 2,000 sq ft home loses about 80,000 BTU/h. Choose a boiler with at least 88,000 BTU/h output (92,632 BTU/h input at 95% AFUE). It makes 3.74 GPM of 105°F water, about 1.5 showers.

Boiler Size Calculator Chart by Home Size and Climate

A 2,000 sq ft home of average build at a 15°F winter design temperature needs about 88,000 BTU/h of boiler output, or 25.8 kW. That comes from 40 BTU/h of heat loss per square foot plus a 10% sizing allowance.

Each colder design band adds 10 BTU/h per square foot in this boiler size calculator chart. It holds the house at average construction, and every cell is space heating output before any hot-water load.

Home Size-47°F to -20°F-19°F to 0°F1°F to 15°F16°F to 30°F31°F to 47°F
1,000 sq ft66,000 BTU/h (19.3 kW)55,000 BTU/h (16.1 kW)44,000 BTU/h (12.9 kW)33,000 BTU/h (9.7 kW)22,000 BTU/h (6.4 kW)
1,500 sq ft99,000 BTU/h (29.0 kW)82,500 BTU/h (24.2 kW)66,000 BTU/h (19.3 kW)49,500 BTU/h (14.5 kW)33,000 BTU/h (9.7 kW)
2,000 sq ft132,000 BTU/h (38.7 kW)110,000 BTU/h (32.2 kW)88,000 BTU/h (25.8 kW)66,000 BTU/h (19.3 kW)44,000 BTU/h (12.9 kW)
2,500 sq ft165,000 BTU/h (48.4 kW)137,500 BTU/h (40.3 kW)110,000 BTU/h (32.2 kW)82,500 BTU/h (24.2 kW)55,000 BTU/h (16.1 kW)
3,000 sq ft198,000 BTU/h (58.0 kW)165,000 BTU/h (48.4 kW)132,000 BTU/h (38.7 kW)99,000 BTU/h (29.0 kW)66,000 BTU/h (19.3 kW)
4,000 sq ft264,000 BTU/h (77.4 kW)220,000 BTU/h (64.5 kW)176,000 BTU/h (51.6 kW)132,000 BTU/h (38.7 kW)88,000 BTU/h (25.8 kW)

Fairbanks and Bemidji sit in the coldest band, Chicago and Minneapolis in the second, and New York and Denver in the middle one. Atlanta and Seattle fall in the fourth band, with Houston and Los Angeles in the warmest.

Outside the US, convert the local winter design temperature first. The middle band runs from about -17°C to -9°C, and 15°F equals -9.4°C, so UK, European or Australian readers can match a boiler size calculator result to the kW figures in brackets.

The design temperature is the cold-day figure a home must hold through, not the record low. A 99% design value is colder than 99% of the hours in a typical winter, so feeding a record low into a boiler size calculator overshoots the load.

Ducted homes need a furnace instead of a boiler, and the Furnace Size Calculator handles that warm-air case. Small homes in the two warmest bands often need less heat than one shower uses, which the combi section below covers.

Sizing Math: Heat Loss to Output to Input

Boiler size is a rate of heat, measured in BTU per hour in the US and in kilowatts almost everywhere else. Cabinet dimensions play no part, so a wall-hung 24 kW combi and a floor-standing 24 kW cast-iron boiler deliver the same heat.

Cabinet size matters for the cupboard, not for a boiler size calculator estimate. Here is how to calculate boiler size by hand.

Every boiler size calculator estimate starts from the home's design heat loss, then adds a margin so the boiler is not flat out on the coldest day.

Here Qout is the required boiler output in BTU/h, A is the heated floor area in square feet, F is the heat-loss factor in BTU/h per square foot, and a is the sizing allowance as a decimal, usually 0.10.

Qin is the input rating on the nameplate, and AFUE is the annual fuel utilization efficiency as a decimal. One kilowatt equals 3,412 BTU/h, the factor the U.S. Energy Information Administration lists for a kilowatthour.

For the 2,000 sq ft example, 2,000 × 40 gives 80,000 BTU/h of heat loss. Multiplying by 1.1 gives 88,000 BTU/h of output, and dividing by 0.95 gives 92,632 BTU/h of input, or 27.1 kW.

Shoppers often compare the wrong number. US boilers list input and output side by side, and only the output, called the DOE heating capacity, should match the boiler size calculator result.

AFUEOutput NeededInput Rating to BuyInput in kW
95%88,000 BTU/h92,632 BTU/h27.1 kW
90%88,000 BTU/h97,778 BTU/h28.7 kW
85%88,000 BTU/h103,529 BTU/h30.3 kW
82%88,000 BTU/h107,317 BTU/h31.5 kW
80%88,000 BTU/h110,000 BTU/h32.2 kW

A 100,000 BTU/h input boiler at 82% AFUE gives only 82,000 BTU/h of output, which falls short of the 88,000 BTU/h boiler size calculator target for this house. The same input at 95% AFUE gives 95,000 BTU/h and covers it.

A room-by-room Manual J load beats any per-square-foot factor. The Heat Loss Calculator builds that load from walls, windows and air leakage, and that figure can replace the area estimate in a boiler size calculator run.

Combi Boilers Sized by Hot Water Demand

A combi heats shower water as it flows, and that load often beats the space heating load. One 2.5 GPM shower raised from 58°F to 105°F needs 58,750 BTU/h, or 17.2 kW, which is more than many small homes need for heat.

That is why a combi boiler size calculator result for a small home is usually set by showers rather than floor area.

N is the number of showers running at once, GPM is the flow per head, and ΔT is the rise from the incoming water to shower temperature in °F. The 500 comes from 8.33 lb per gallon times 60 minutes times 1 BTU per pound per °F.

Showers at Once40°F Inlet50°F Inlet58°F Inlet70°F Inlet
181,250 BTU/h (23.8 kW)68,750 BTU/h (20.1 kW)58,750 BTU/h (17.2 kW)43,750 BTU/h (12.8 kW)
2162,500 BTU/h (47.6 kW)137,500 BTU/h (40.3 kW)117,500 BTU/h (34.4 kW)87,500 BTU/h (25.6 kW)
3243,750 BTU/h (71.4 kW)206,250 BTU/h (60.4 kW)176,250 BTU/h (51.7 kW)131,250 BTU/h (38.5 kW)

Showers at 2.5 GPM each and 105°F at the head. Use winter inlet water for any boiler size calculator estimate, since the same shower needs 38% more heat at 40°F than at 58°F.

Reading the same math backwards shows what common combi ratings deliver. Any kW answer from a combi boiler size calculator can be read as hot water flow once the inlet temperature is known.

Combi RatingFlow at 58°F InletShowers at 58°FFlow at 40°F InletShowers at 40°F
24 kW (81,891 BTU/h)3.48 GPM (13.2 L/min)1.42.52 GPM (9.5 L/min)1.0
28 kW (95,540 BTU/h)4.07 GPM (15.4 L/min)1.62.94 GPM (11.1 L/min)1.2
30 kW (102,364 BTU/h)4.36 GPM (16.5 L/min)1.73.15 GPM (11.9 L/min)1.3
35 kW (119,425 BTU/h)5.08 GPM (19.2 L/min)2.03.67 GPM (13.9 L/min)1.5
40 kW (136,486 BTU/h)5.81 GPM (22.0 L/min)2.34.20 GPM (15.9 L/min)1.7

A 24 kW combi covers one shower in any season. A 35 kW unit runs two showers with 58°F supply water but only 1.5 at 40°F, so a boiler size calculator result near 35 kW in a cold region often points to a stored tank instead.

Radiators, Baseboard and EDR on an Existing System

On a replacement job, the radiation already on the walls is a second check on any boiler size calculator estimate.

Fin-tube baseboard rated 580 BTU/h per foot at 180°F average water gives off 69,600 BTU/h from 120 ft, or 76,560 BTU/h with the 10% allowance.

Cast-iron hot-water radiators are rated in square feet of EDR, equivalent direct radiation, at 150 BTU/h per square foot. A house with 400 sq ft of EDR needs 60,000 BTU/h for the radiators and 66,000 BTU/h of boiler output.

Panel radiators add up from the rated output on each one. Twelve double panels at 5,911 BTU/h give 70,932 BTU/h, so the boiler needs 78,025 BTU/h, or 22.9 kW, with the 10% allowance.

The table runs the other way, from boiler ratings to the radiation each one serves with a 10% margin. Panel radiator counts use a double-panel 600 × 1000 mm radiator rated 5,911 BTU/h (1,732 W) at ΔT50 on the Stelrad Compact data sheet.

Boiler OutputRadiation It ServesBaseboard at 580 BTU/ftCast-Iron EDR600 × 1000 Double Panels
18 kW (61,419 BTU/h)16.4 kW96 ft372 sq ft9.4
24 kW (81,891 BTU/h)21.8 kW128 ft496 sq ft12.6
28 kW (95,540 BTU/h)25.5 kW150 ft579 sq ft14.7
30 kW (102,364 BTU/h)27.3 kW160 ft620 sq ft15.7
35 kW (119,425 BTU/h)31.8 kW187 ft724 sq ft18.4

Radiator and baseboard ratings drop when a condensing boiler runs cooler water. A system that barely heats the house at 180°F will fall short at 140°F, however large the boiler size calculator estimate for the building comes out.

Radiation count can also flag an oversized system. If the baseboard adds up to 140,000 BTU/h but the house loses only 80,000 BTU/h, size the boiler from the heat loss and let the extra emitters run cooler water.

Steam Boilers Need the Gross Rating

A steam boiler size calculator estimate follows its own rule, because steam radiators and their piping behave differently from hot-water loops.

Steam radiators give off 240 BTU/h per square foot of EDR, and the piping and pickup allowance adds 33% on top. A home with 400 sq ft of steam EDR needs 96,000 BTU/h net and 127,680 BTU/h of gross output.

EDR is the total equivalent direct radiation of every connected radiator in square feet, 240 is the steam rating per square foot, and 1.33 is the combined piping and pickup factor used by steam specialists.

Connected EDRNet Radiator LoadGross (DOE) OutputGross in kWInput at 80% AFUECondensate Return
200 sq ft48,000 BTU/h63,840 BTU/h18.7 kW79,800 BTU/h49 lb/h
300 sq ft72,000 BTU/h95,760 BTU/h28.1 kW119,700 BTU/h74 lb/h
400 sq ft96,000 BTU/h127,680 BTU/h37.4 kW159,600 BTU/h99 lb/h
600 sq ft144,000 BTU/h191,520 BTU/h56.1 kW239,400 BTU/h148 lb/h
800 sq ft192,000 BTU/h255,360 BTU/h74.8 kW319,200 BTU/h198 lb/h

Compare the 1.33 result with the boiler's gross (DOE) output, never its net I=B=R rating. Steam pros on the Heating Help Strictly Steam forum point out that the net rating already includes the pickup factor.

Matching the old boiler's nameplate is the other common miss. Many steam systems lost radiators over the years, so an 800 sq ft EDR boiler serving 400 sq ft of radiation is twice the size a boiler size calculator estimate would call for.

Insulation, Property Age and Extensions

Construction quality moves the heat-loss factor by 5 BTU/h per square foot either way at a given design temperature. For a 2,000 sq ft home at 15°F, that swing changes the boiler by 11,000 BTU/h in each direction.

House EnvelopeTypical AgeFactorHeat LossBoiler OutputInput at 95%
DraftyOver 35 years, not renovated45 BTU/sq ft90,000 BTU/h99,000 BTU/h (29.0 kW)104,211 BTU/h
Average11 to 35 years, or older and renovated40 BTU/sq ft80,000 BTU/h88,000 BTU/h (25.8 kW)92,632 BTU/h
Well sealedUnder 10 years, or 11 to 35 and renovated35 BTU/sq ft70,000 BTU/h77,000 BTU/h (22.6 kW)81,053 BTU/h

Insulation work can drop a home a full row and shrink the next boiler size calculator result by 11,000 BTU/h. The R-Value Calculator shows how much a wall or attic upgrade raises the assembly's resistance before the boiler is chosen.

An extension adds its own load on top of the margin. A 400 sq ft addition at 15°F with average construction adds 17,600 BTU/h of output, or 5.2 kW, while the original 10% allowance on 2,000 sq ft only covered 8,800 BTU/h.

So a boiler sized tight for the original house will run short after the addition. Rerun the boiler size calculator with the new total area of 2,400 sq ft, which gives 105,600 BTU/h, before deciding to keep the old unit.

Too Big or Too Small: What Each Costs

An undersized boiler struggles only on cold days. A 66,000 BTU/h boiler in a house that loses 80,000 BTU/h at design temperature falls 14,000 BTU/h short of the boiler size calculator figure, so rooms drift below the setpoint in a cold snap.

An oversized boiler costs money every day. It fires, overshoots and shuts off in short cycles, and a condensing unit that cycles hard spends less time in the low return temperatures that earn its efficiency rating.

Combis in warm regions show the problem most clearly, because the shower load sets the size while the heating load stays small. These cases use one 2.5 GPM shower and 58°F supply water.

HomeDesign TempHeating Output NeededShower LoadShower ÷ Heating
1,000 sq ft, well sealed32°F16,500 BTU/h (4.8 kW)58,750 BTU/h (17.2 kW)3.6×
1,500 sq ft, well sealed22°F41,250 BTU/h (12.1 kW)58,750 BTU/h (17.2 kW)1.4×
1,200 sq ft, average30°F39,600 BTU/h (11.6 kW)58,750 BTU/h (17.2 kW)1.5×

Once the shower load reaches twice the heating load, check that the combi turns down to the heating figure. If it cannot, a system boiler with an indirect tank stops the short cycling, and the Water Heater Size Calculator sizes that tank.

A bigger boiler is better only up to the 10% to 15% boiler size calculator margin that covers a cold snap or a sluggish morning warm-up. Past that, extra capacity buys nothing on design days and wastes fuel on mild ones.

Loop Flow and Pipe Size for the Heating Circuit

An 88,000 BTU/h boiler on a 20°F temperature drop moves 8.8 GPM through the heating loop, and 1-inch Type L copper carries that at 3.42 ft/s. Pipe sized below that boiler size calculator flow makes the loop noisy and starves the far radiators.

Qout is the boiler's space heating output in BTU/h and ΔT is the drop between supply and return water in °F. Baseboard, radiator and radiant floor loops can all run up to a 20°F drop, per contractor Ted Schmelling in PHCP Pros.

Velocity v is in ft/s and d is the pipe's inside diameter in inches, taken from ASTM B88 Type L sizes. The table keeps each pipe at 4 ft/s or less, a common limit for quiet hydronic flow.

Boiler OutputFlow at 20°F ΔTType L PipeSpeedFlow at 10°F ΔTType L PipeSpeed
40,000 BTU/h4.00 GPM (15.1 L/min)3/4-inch2.65 ft/s8.00 GPM (30.3 L/min)1-inch3.11 ft/s
60,000 BTU/h6.00 GPM (22.7 L/min)3/4-inch3.98 ft/s12.00 GPM (45.4 L/min)1-1/4-inch3.06 ft/s
88,000 BTU/h8.80 GPM (33.3 L/min)1-inch3.42 ft/s17.60 GPM (66.6 L/min)1-1/2-inch3.17 ft/s
120,000 BTU/h12.00 GPM (45.4 L/min)1-1/4-inch3.06 ft/s24.00 GPM (90.8 L/min)2-inch2.49 ft/s
176,000 BTU/h17.60 GPM (66.6 L/min)1-1/2-inch3.17 ft/s35.20 GPM (133.2 L/min)2-inch3.65 ft/s

An underfloor heating boiler size calculator result stays the same for a radiant floor, since the building loses the same heat. The same 20°F column applies, and a tighter 10°F drop doubles the flow and pushes the main up one or two pipe sizes.

Fuel Burn and Electric Boiler Current

An 88,000 BTU/h output boiler at 95% AFUE burns 89 cubic feet of natural gas an hour at full fire, or 0.93 therms. The same output from an electric boiler draws 107 amps at 240 volts, which most homes cannot add without a service upgrade.

Fuel burn equals the boiler size calculator input rating divided by the fuel's heat content, so efficiency moves fuel use as much as boiler size does.

The EIA conversion table gives 1,036 BTU per cubic foot of natural gas, 91,452 BTU per gallon of propane and 138,500 BTU per gallon of heating oil.

Boiler OutputInput at 95%Natural GasPropane at 95%Oil at 85%Electric at 240 V
60,000 BTU/h (17.6 kW)63,158 BTU/h61 ft³/h0.69 gal/h0.51 gal/h73 A
88,000 BTU/h (25.8 kW)92,632 BTU/h89 ft³/h1.01 gal/h0.75 gal/h107 A
120,000 BTU/h (35.2 kW)126,316 BTU/h122 ft³/h1.38 gal/h1.02 gal/h147 A
176,000 BTU/h (51.6 kW)185,263 BTU/h179 ft³/h2.03 gal/h1.49 gal/h215 A

The oil column uses 85% AFUE as an example, so swap in the AFUE printed on the oil boiler's label. A gas boiler size calculator figure and an oil one share the same output, but the oil boiler needs a larger input to reach it.

The gas column also sets the gas meter and pipe size. An 89 ft³/h boiler plus a 40,000 BTU/h range and a dryer can outgrow an older meter, so add every appliance before signing off the electric or gas boiler size calculator result.

Above 300,000 BTU/h: Commercial Boiler Territory

Federal consumer rules stop at 300,000 BTU/h of input. The definition in 10 CFR 430.2 covers low-pressure steam and hot-water boilers below that line.

Larger units fall under commercial equipment rules. A boiler size calculator result above 285,000 BTU/h of output at 95% AFUE is past the consumer range.

AFUELargest Consumer OutputOutput in kWHome Size at 15°F (40 BTU/sq ft)Home Size at -20°F or Colder (60 BTU/sq ft)
95%284,999 BTU/h83.5 kW6,477 sq ft4,318 sq ft
90%269,999 BTU/h79.1 kW6,136 sq ft4,091 sq ft
85%254,999 BTU/h74.7 kW5,795 sq ft3,864 sq ft
80%239,999 BTU/h70.3 kW5,455 sq ft3,636 sq ft

Home sizes assume average construction and the 10% allowance. A larger house, a small apartment block or an industrial boiler size calculator job usually lands on two smaller boilers staged together, which also turn down better in mild weather.

Quick Answers on Boiler Size and Type

These answers use the same heat-loss factors, shower math and 10% allowance as the tables above, so the numbers line up across the page.

What is a boiler size calculator?

A boiler size calculator result is the minimum heat output, in BTU/h or kW, that a boiler must deliver on a design-temperature day. It covers space heating and, for a combi, the hot water for showers running at the same time.

The math multiplies floor area by a heat-loss factor tied to climate and construction, adds a margin, and compares that with the shower load. A 2,000 sq ft average home at 15°F lands at 88,000 BTU/h of output and 92,632 BTU/h of input at 95% AFUE.

How do I choose a boiler size?

Choose a boiler whose rated output, not input, meets or slightly beats the boiler size calculator result, since input includes the efficiency loss.

So what size boiler do I need for an 88,000 BTU/h answer? A 95% AFUE model with about 92,600 BTU/h of input, or a 25.8 kW output rating outside the US.

Then settle the type. A combi suits one bathroom or two showers in mild supply water, while two or more showers in cold regions point to a system boiler with a tank, sized for heating alone.

What size boiler for a 2000 sq ft house?

A 2,000 sq ft house of average build needs about 88,000 BTU/h of output (25.8 kW) at a 15°F design temperature. On the boiler size calculator chart above, the range runs from 44,000 BTU/h in the warmest US band to 132,000 BTU/h in the coldest.

Construction moves it by 11,000 BTU/h each way, so a drafty older house at 15°F needs 99,000 BTU/h and a new tight one needs 77,000 BTU/h.

What size boiler for a 4 bedroom house?

A 4-bedroom house of 2,500 sq ft at 15°F with average construction needs about 110,000 BTU/h of heating output, or 32.2 kW. In a colder -19°F to 0°F climate that rises to 137,500 BTU/h, or 40.3 kW.

For a combi, hot water often decides between 28 kW and 35 kW. Two 2.5 GPM showers at once need 117,500 BTU/h (34.4 kW) with 58°F supply water, so 35 kW covers them while 28 kW manages about 1.6 showers.

With 40°F winter supply water, the same two showers need 47.6 kW, beyond most wall-hung combis. A system boiler of about 32 kW with a stored tank handles that household better.

What combi boiler size for a 2 bathroom, 3 bedroom modern house?

A modern, well-sealed 3-bedroom home of 1,600 sq ft at 15°F needs only about 61,600 BTU/h, or 18.1 kW, for heating. The combi size comes from hot water instead.

One shower at a time needs 17.2 kW with 58°F supply water, so a 24 kW combi gives margin. If both bathrooms run showers together, the load reaches 34.4 kW and the home needs a 35 kW combi or a system boiler.

How big should a residential boiler be?

Across the boiler size calculator chart, most homes need between 44,000 and 132,000 BTU/h of output, or about 13 to 39 kW. That spans a 1,000 sq ft house in a mild climate up to a 3,000 sq ft house in a cold one, at average construction.

Standard combis sold in the UK run 24 to 35 kW because their size follows shower flow. Consumer boilers stop at 300,000 BTU/h of input, roughly 285,000 BTU/h of output at 95% AFUE.

How is boiler size measured?

Boiler size is measured as heat output per hour, in BTU/h, in MBH (thousands of BTU/h) or in kilowatts. A boiler size calculator result of 88,000 BTU/h is 88 MBH or 25.8 kW, whatever the cabinet measures.

US nameplates also list input, which is larger by the efficiency loss. Steam boilers add a third figure, the net I=B=R rating in square feet of EDR, which already includes the 1.33 pickup factor.

How many radiators can a 24kW boiler run?

A 24 kW boiler can serve about 21.8 kW of radiators while keeping a 10% margin. That is 12.6 double-panel 600 × 1000 radiators at 5,911 BTU/h each, 496 sq ft of cast-iron EDR, or 128 ft of baseboard at 580 BTU/h per foot.

Use the central-heating output from the boiler's data sheet, since many combis list a lower heating figure than their hot-water rating. Smaller or single-panel radiators raise the count, and ratings drop at lower flow temperatures.

What flow rate do I need for a combi boiler?

For a combi boiler size calculator estimate, each shower needs about 2.5 GPM, or 9.5 L/min, at 105°F.

A combi's hot water flow equals its output divided by 500 times the temperature rise, so a 24 kW unit gives 3.48 GPM with 58°F inlet water and 2.52 GPM at 40°F.

Three things set the flow you get: the boiler's output, the incoming water temperature and the shower temperature. The cold main must also supply at least that flow, or the combi cannot reach its rated figure.

What is the difference between a combi and system boiler?

A combi heats water on demand with no tank, so its size follows the showers running at once. A system boiler heats an indirect tank and the radiators, so its size follows space heating, and the tank covers peak hot water.

An 88,000 BTU/h system boiler reheats a tank to 120°F from 58°F supply water at about 170 gallons per hour. Replacing a regular boiler with a combi works when peak showers fit the combi flow table above.

For a small apartment, a combi usually fits the boiler size calculator numbers. An 800 sq ft well-sealed unit at 15°F needs about 30,800 BTU/h for heat, while one shower needs 58,750 BTU/h, so a 24 kW combi handles both.