Heat Loss Calculator

Updated

Heat loss calculator for one room or a whole house, in BTU/hr, watts or kW, from wall, window, roof and floor U-values, air leakage and the design temperature, plus radiator sizes.

Room Size and Insulation

For the ambient temperature, use the coldest usual winter temperature where you live.

Additional InformationU 0.084 · 2 windows, 0 doors

Each door counts as 19.4 sq ft (1.8 m²). Windows and doors are taken out of the wall area.

Btu/h·ft²·°F
Btu/h·ft²·°F
Roof, Floor, Air and HeaterNo air leakage · 95% AFUE
ACH
% AFUE
Btu/h·ft²·°F
Btu/h·ft²·°F
At 70°F Inside and 0°F Outside
2,240 BTU/hr Heat Loss
The heat your heater must replace every hour on the coldest day
32.0 BTU/hr·°F Heat Loss
In Watts per Kelvin16.9 W/K
Largest LossWalls, 50.9%
Heat lost for each degree of temperature difference. Fix the largest loss first to cut it.
+968 BTU/hr at 0.5 ACH
Total With 0.5 ACH3,208 BTU/hr
Outside Air at 0.5 ACH13 CFM
Set air changes above 0 to add leakage to the total. Sealing drafts and gaps will cut it.
656 W Heater Size
Input Rating Needed2,358 BTU/hr
1,500 W Space Heaters1 heater
Buy a heater rated at or above this output. Fuel heaters need the higher input rating.
0.19 Tons Heat Pump
Load per sq ft11.7 BTU/hr
Heat Loss Indicator0.95 W/K·m²
Heat pumps lose output in cold weather. Check the rated output at your outdoor low.
Heat Loss by SurfaceLargest: Walls
SurfaceArea or VolumeU-Value (Btu/h·ft²·°F) or ACHHeat LossShare
Walls194 sq ft0.0841,141 BTU/hr50.9%
Windows30 sq ft0.299629 BTU/hr28.1%
Doors0 sq ft0.4230 BTU/hr0.0%
Ceiling192 sq ft0.035470 BTU/hr21.0%
Air Leakage1,536 cu ft0.00 ACH0 BTU/hr0.0%
Total--2,240 BTU/hr100.0%
Radiator Size for This RoomHeat pump: 4,351 BTU/hr

Radiators are rated at a 90°F difference between mean water and room temperature. Cooler water gives less heat, so a bigger radiator is needed.

Heating SystemWater-to-Room DifferenceOutput vs. CatalogRadiator Rating Needed
Standard Boiler90°F100.0%2,240 BTU/hr
Condensing Boiler72°F74.8%2,994 BTU/hr
Heat Pump54°F51.5%4,351 BTU/hr
Low-Temp Heat Pump45°F40.6%5,515 BTU/hr
Whole House, Room by RoomNo rooms added

Size each room above, name it and add it. The total is the heat loss for the whole house.

No rooms added yet.
Step-by-Step Heat Loss MathQ = U × A × ΔT
  1. Temperature difference: ΔT = 70°F - 0°F = 70°F
  2. External wall area: 28.00 ft × 8.00 ft = 224.00 sq ft, minus 30.00 sq ft of windows and doors = 194.00 sq ft
  3. Walls: 194.00 sq ft × U 0.084 = 16.296 BTU/hr·°F
  4. Windows: 2 × 15.00 sq ft = 30.00 sq ft × U 0.299 = 8.982 BTU/hr·°F
  5. Ceiling: 192.00 sq ft × U 0.035 = 6.720 BTU/hr·°F
  6. Heat loss coefficient: 16.296 + 8.982 + 6.720 = 31.998 BTU/hr·°F
  7. Heat loss: Q = 31.998 BTU/hr·°F × 70°F = 2,240 BTU/hr
Heat Loss Calculated
The walls lose the most heat here, at 50.9% of the total. Size each room on its own when picking radiators.

Heat Loss Calculator Worksheet for a 16 by 12 Room

To calculate heat loss, multiply each surface's area by its U-value and by the indoor-outdoor temperature difference. Then add the air leakage and total it. A 16 by 12 ft top-floor bedroom loses 2,917 BTU/hr at 70°F inside and 0°F outside.

Q is the heat loss in BTU/hr or watts, U is the surface's heat flow per unit area per degree, A is its area, and ΔT is the inside temperature minus the outside design temperature.

The room has two outside walls (16 + 12 = 28 ft long, 8 ft high), two 15 sq ft low-E windows, an R-30 attic above and 0.35 air changes per hour. Its gross outside wall is 224 sq ft, and taking out 30 sq ft of glass leaves 194 sq ft of wall.

SurfaceArea or volumeU-value or rateUA (BTU/hr·°F)Heat loss at 70°F ΔTShare
2×4 wall, R-13194 sq ft0.08416.2961,141 BTU/hr39.1%
Double-pane low-E windows30 sq ft0.2998.982629 BTU/hr21.6%
Attic ceiling, R-30192 sq ft0.0356.720470 BTU/hr16.1%
Air leakage1,536 cu ft0.35 ACH × 0.0189.677677 BTU/hr23.2%
Total192 sq ft floor-41.6752,917 BTU/hr100%

The 41.675 total is the room's heat loss coefficient, the most useful heat loss calculator number to keep. Every extra degree of cold outside costs this room another 41.7 BTU/hr. In metric that coefficient is 22.0 W/K, and the total is 855 W.

Only the walls that face outdoors count in a room heat loss calculator worksheet. A wall shared with another heated room has almost no temperature difference, so it adds nothing. The floor drops out here too, because a heated room sits below.

U-Values Behind Walls, Windows and Roofs

A single-pane metal window loses 7,150 BTU/hr per 100 sq ft at a 70°F difference. An R-30 attic loses 245 BTU/hr over the same area. That 29-fold spread is why the U-value matters more than any other input to a heat loss calculator for home use.

AssemblyU (BTU/hr·ft²·°F)U (W/m²·K)Loss per 100 sq ft at 70°F ΔT
Solid brick, 4 in (105 mm)0.5283.003,698 BTU/hr
Solid brick, no extra insulation0.3872.202,712 BTU/hr
Brick cavity wall0.2591.471,812 BTU/hr
Insulated brick cavity wall0.0880.50616 BTU/hr
2×4 wall, R-130.0840.48588 BTU/hr
2×6 wall, R-200.0600.34420 BTU/hr
2×6 wall, R-20 + R-5 foam0.0450.26315 BTU/hr
Single pane, metal frame1.0215.807,150 BTU/hr
Single pane, wood or vinyl0.8815.006,164 BTU/hr
Double pane, older0.5112.903,575 BTU/hr
Double pane, low-E0.2991.702,096 BTU/hr
Triple pane0.2001.141,400 BTU/hr
External door0.4232.402,959 BTU/hr
Uninsulated roof space0.4052.302,835 BTU/hr
Attic, R-300.0350.20245 BTU/hr
Attic, R-600.0240.14168 BTU/hr
Solid concrete ground floor0.2821.601,972 BTU/hr
Floor over crawl space, R-190.0470.27329 BTU/hr

The brick, glazing, roof and floor values match the U-values that Stelrad publishes for its radiator sizing, rated to BS EN 442. For a heat loss calculator estimate, a door counts as 1.8 m² (19.4 sq ft) at 2.4 W/m²·K.

An R-13 wall is not U = 1/13, which would give 0.077, but the whole 2×4 wall runs at 0.084, about 9% worse, because wood studs carry heat past the insulation. Use whole-assembly U-values, not the label, in any residential heat loss calculation.

To build a U-value from layers of drywall, sheathing and insulation, add the R-values with the R-Value Calculator and take the reciprocal. Divide a metric U-value by 5.678 before using it in an imperial heat loss calculator sum.

Air Leakage Can Rival the Walls

Leaving air leakage out of a heat loss calculator total cuts the bedroom's figure from 2,917 to 2,240 BTU/hr, a 23% understatement. At 1 air change per hour, leakage becomes the largest single loss, at 46.4% of the room total.

V is the room volume in cubic feet and ACH is the number of times the room's air is replaced each hour.

The 0.018 BTU/ft³·°F comes from air at 0.075 lb/ft³ times its specific heat of 0.24 BTU/lb·°F. In metric the same constant is 0.33 W/m³·K, with V in m³.

House tightnessACHOutside air leaking inLeakage lossRoom totalLeakage share
Not counted00 CFM0 BTU/hr2,240 BTU/hr0%
Very tight new home0.25 CFM387 BTU/hr2,627 BTU/hr14.7%
Tight home0.359 CFM677 BTU/hr2,917 BTU/hr23.2%
Average home0.513 CFM968 BTU/hr3,208 BTU/hr30.2%
Older, drafty home1.026 CFM1,935 BTU/hr4,175 BTU/hr46.4%
Very leaky home1.538 CFM2,903 BTU/hr5,143 BTU/hr56.4%

In a heat loss calculator for home sizing, a well-insulated room makes leakage look bigger, because the walls and attic lose so little.

Draft sealing in an R-13 house often saves more heat than adding insulation. Going from 1.0 to 0.35 ACH here saves 1,258 BTU/hr, more than all the wall loss.

A blower-door result is given at 50 Pa, not at natural conditions, so it needs converting before use. To turn a measured airflow and room size into ACH, run the numbers through the Air Changes per Hour Calculator.

Square Footage Rules Miss Room Position

The same 192 sq ft floor plan loses anywhere from 1,882 to 4,866 BTU/hr at 0°F, depending on where the room sits and how many walls face outdoors.

That is 9.8 to 25.3 BTU/hr per sq ft, a 2.6-fold spread in the heat loss calculator room result with identical construction.

Room position (R-13, low-E, 0.35 ACH)1 outside wall2 outside walls3 outside walls4 outside walls
Middle floor, heated above and below1,882 (9.8/sq ft)2,447 (12.7/sq ft)3,199 (16.7/sq ft)3,764 (19.6/sq ft)
Top floor, R-30 attic above2,353 (12.3/sq ft)2,917 (15.2/sq ft)3,670 (19.1/sq ft)4,234 (22.1/sq ft)
Ground floor, R-19 over crawl space2,514 (13.1/sq ft)3,078 (16.0/sq ft)3,831 (20.0/sq ft)4,396 (22.9/sq ft)
Single-story, attic and crawl space2,984 (15.5/sq ft)3,549 (18.5/sq ft)4,302 (22.4/sq ft)4,866 (25.3/sq ft)

All values are BTU/hr at 70°F inside and 0°F outside, with one 1-wall layout taken along the 16 ft side. A corner room in a single-story house needs 89% more heat than a middle-floor room of the same size with one outside wall.

Construction moves it further. Swap in uninsulated brick, single-pane wood windows, an uninsulated roof space and 1 ACH, and the same top-floor room loses 14,490 BTU/hr, or 75.5 BTU/hr per sq ft. That is five times the insulated version.

A flat heat loss calculator by square footage rate of 30 to 60 BTU per sq ft would put this room at 5,760 to 11,520 BTU/hr.

That is two to four times the insulated room's real loss and still too low for the drafty brick one. Radiators sized room by room need the surface method.

Design Temperature Moves the Answer

Each 10°F colder outside adds 417 BTU/hr to the 16 by 12 bedroom, because its coefficient is 41.7 BTU/hr per °F. Feed a heat loss calculator the local winter design temperature, not the record low and not the January average.

Outside temperatureΔT to 70°FHeat lossWatts
30°F (-1.1°C)40°F1,667 BTU/hr489 W
20°F (-6.7°C)50°F2,084 BTU/hr611 W
10°F (-12.2°C)60°F2,500 BTU/hr733 W
0°F (-17.8°C)70°F2,917 BTU/hr855 W
-10°F (-23.3°C)80°F3,334 BTU/hr977 W
-20°F (-28.9°C)90°F3,751 BTU/hr1,099 W

Heating designers use the 99% or 99.6% winter design temperature from ASHRAE climatic design data. Outside air is colder than that for only 35 to 88 hours a year. Sizing to a once-a-decade low adds capacity the system will short-cycle on all season.

The inside temperature matters just as much in a heat loss calculation. Designing a bedroom at 64°F instead of 70°F cuts the ΔT from 70 to 64 and the loss by 8.6%, from 2,917 to 2,667 BTU/hr.

Boiler, Furnace and Space Heater Size From the Loss

A boiler or furnace must deliver the summed heat loss calculator total as output, so the fuel input is the loss divided by efficiency. The 2,917 BTU/hr bedroom needs 3,071 BTU/hr of input at 95% efficiency, or 3,646 BTU/hr at 80%.

A heat loss calculator for boiler size works on the whole house, not one room. The four-room, 720 sq ft single-story house in the room-by-room answer below totals 14,116 BTU/hr, so 14,859 BTU/hr of input at 95%.

Heat source16 by 12 bedroom (2,917 BTU/hr)720 sq ft house (14,116 BTU/hr)
Boiler or furnace input at 95%3,071 BTU/hr14,859 BTU/hr
Boiler or furnace input at 80%3,646 BTU/hr17,645 BTU/hr
Electric heat at 240 V3.6 A17.2 A
1,500 W space heaters13
Heat pump at design temperature0.24 ton1.18 tons

Electric resistance heat is 100% efficient, so the watts equal the heat loss calculator result. A 1,500 W heater makes 5,118 BTU/hr, enough for the bedroom.

Fixed electric heat is a continuous load under NEC Article 424, so the 17.2 A house load needs a circuit rated for at least 21.5 A.

Heat pump tonnage counts at the design temperature, not at the 47°F rating point. Check the manufacturer's cold-climate output table before matching 1.18 tons to the house. A load this low often falls below the smallest gas furnace sold.

From a known heat loss, the matching equipment comes from the Boiler Size Calculator for hot-water systems, or from the Furnace Size Calculator for forced air.

Radiator Size at ΔT50 and at Heat Pump Temperatures

Radiator sizing from a heat loss calculator starts with the catalog rating, which is the output at a 50 K (90°F) difference between mean water and room temperature.

At heat pump water temperatures the same radiator gives about half that, so the bedroom's 855 W loss needs a 1,661 W catalog radiator.

F is the share of catalog output a radiator gives at a lower water-to-room difference ΔT in kelvin. The 1.3 exponent is the usual panel radiator value under BS EN 442, the rating standard Stelrad quotes for ΔT50.

Heating systemWater-to-room differenceOutput vs. catalogCatalog rating for an 855 W roomIn BTU/hr
Standard boiler50 K (90°F)100.0%855 W2,917 BTU/hr
Condensing boiler40 K (72°F)74.8%1,143 W3,899 BTU/hr
Heat pump30 K (54°F)51.5%1,661 W5,667 BTU/hr
Low-temperature heat pump25 K (45°F)40.6%2,105 W7,183 BTU/hr

A 50 K difference means water averaging 70°C in a 20°C room. A heat pump running 55°C flow and 45°C return averages 50°C, only 30 K above the room. That is why heat pump conversions often keep the boiler but swap or add radiators.

For a heat loss calculator for heat pumps, the room-by-room total sets the unit size, and the per-room loss sets each radiator. A room whose current radiator rates below the ΔT30 figure will run cool on the design day.

Kilowatts for a Metric Room

On a metric heat loss calculator, a 5 by 4 m ground-floor living room with an insulated cavity wall loses 1.158 kW at 21°C inside and -3°C outside. That is 57.9 W per m² of floor, and the uninsulated floor is the biggest single loss.

The room has two outside walls 2.4 m high, two 1.5 m² double-glazed windows (U 2.5), one door, a standard ground floor (U 1.0) and 0.5 air changes per hour. The -3°C outside figure matches the external design temperature Stelrad's UK sizing assumes.

SurfaceArea or volumeU-value (W/m²·K) or ACHHeat loss at 24 KShare
Insulated cavity wall16.8 m²0.50202 W17.4%
Double glazing3.0 m²2.50180 W15.5%
External door1.8 m²2.40104 W9.0%
Ground floor20.0 m²1.00480 W41.4%
Air leakage48.0 m³0.5 ACH193 W16.7%
Total20.0 m² floor-1,158 W100%

In a heat loss calculator UK result, the uninsulated floor carries 41% of the loss even with a modern wall. Floor insulation is the first fix here, ahead of new windows. The room needs a 1,158 W radiator at ΔT50, or 2,250 W at a heat pump's ΔT30.

A heat loss calculator kW answer converts directly. 1 kW is 3,412 BTU/hr, so this room loses 3,953 BTU/hr. MCS-certified heat pump installers in the UK work room by room to BS EN 12831, which follows the same surface-plus-ventilation method.

Calculating Heat Loss by Hand, Imperial and Metric

Each heat loss calculator answer below uses the same surface-plus-air method as the worksheet above, so the numbers can be checked with a pencil.

How to calculate heat formula?

The general heat formula is Q = m × c × ΔT, mass times specific heat times temperature change. Heat loss through a building uses the rate form, Q = U × A × ΔT for each surface, plus a ventilation term for the air.

The ventilation term is the mass formula applied to air. One cubic foot of air weighs 0.075 lb and holds 0.24 BTU per lb per °F, so 0.075 × 0.24 = 0.018 BTU per cu ft per °F. Multiply by the cubic feet replaced each hour to get BTU/hr.

This BTU calculation formula gives 1,536 × 0.35 × 0.018 × 70 = 677 BTU/hr of leakage for the 16 by 12 bedroom. The heat loss equation then adds 1,141 for walls, 629 for windows and 470 for the ceiling, for 2,917 BTU/hr.

How do you calculate heat loss in imperial units?

Use U in BTU/hr·ft²·°F, areas in square feet, volume in cubic feet and ΔT in °F, and the answer comes out in BTU/hr. Convert a metric U-value by dividing by 5.678, so a U 1.7 W/m²·K low-E window is 0.299.

When only an R-value is known for a heat loss calculator input, U = 1/R for that layer alone. A real assembly needs the framing included, which is why an R-13 wall uses 0.084 rather than 0.077. Divide BTU/hr by 3.412 for watts, or by 12,000 for tons.

How do I calculate heat loss in a multi-room home?

Work out each room on its own with only its outside walls, windows and doors, then add the rooms. A 720 sq ft single-story house built this way totals 14,116 BTU/hr at 70°F inside and 0°F outside.

RoomFloor areaWindows and doorsHeat lossBTU/hr per sq ft
Living room, 20 × 15 ft300 sq ft3 windows, 1 door5,565 BTU/hr18.5
Kitchen, 12 × 12 ft144 sq ft1 window, 1 door3,104 BTU/hr21.6
Bedroom 1, 12 × 12 ft144 sq ft2 windows2,916 BTU/hr20.2
Bedroom 2, 12 × 11 ft132 sq ft1 window2,531 BTU/hr19.2
Whole house720 sq ft-14,116 BTU/hr19.6

Every room has two outside walls, 8 ft ceilings, R-13 walls, low-E glass, an R-30 attic, R-19 over the crawl space and 0.35 ACH. The kitchen loses the most per square foot because its door adds 8.2 BTU/hr per °F on a small floor.

In a whole-house heat loss calculator sum, never count a shared interior wall twice, or at all when both sides are heated. Summing whole rooms keeps each outside surface in exactly one room, which is what a whole-house heat load needs.

How is the heat loss indicator calculated?

The heat loss indicator is the heat loss coefficient in W/K divided by the floor area in m². The 5 by 4 m UK living room has a coefficient of 48.27 W/K over 20 m², so its HLI is 2.41 W/K·m².

HTC is the heat transfer coefficient, the sum of every U × A plus the ventilation term, in W/K. Afloor is the heated floor area. HLI ignores the outside temperature, so homes in different climates compare directly on one heat loss calculator scale.

Ireland's SEAI heat pump grant uses HLI as its readiness test, with 2.0 W/K·m² as the standard limit. The 720 sq ft house above scores 1.59 for the whole home, while the drafty brick bedroom scores 6.12.

What are the different types of heat loss calculators?

The three common types are square-footage rules, room-by-room surface calculations, and pipe or tank surface calculators. Only the room-by-room heat loss calculator method finds which surface loses the most heat and sizes individual radiators.

A simple heat loss calculator estimate comes from floor area times a BTU-per-square-foot rate, fast but blind to construction.

The surface method sums U × A × ΔT plus air leakage. ACCA Manual J in the US and BS EN 12831 in Europe extend it with ground temperatures and thermal bridging.

A pipe heat loss calculator works on an insulated surface instead of a room, and so does a tank version.

Those use the insulation thickness and conductivity, often to ASTM C680, and the Insulation Surface Temperature Calculator covers the hot-pipe side of that job.