Chimney Flue Size Calculator for the flue area a fireplace opening or stove collar needs, the round or clay liner that fits, natural draft from chimney height, and the 3-2-10 rule.
Measure the fireplace opening width and height at the front of the firebox.
Draft and 3-2-10 Roof Check
Flue Cross-Section
Clay Liner Sizes and Openings Served
| Inside Diameter | Net Area | Largest Opening |
|---|---|---|
| 6 in | 28.0 sq in | 336 sq in |
| 7 in | 38.0 sq in | 456 sq in |
| 8 in | 50.0 sq in | 600 sq in |
| 10 in | 78.0 sq in | 936 sq in |
| 10 3/4 in | 90.0 sq in | 1,080 sq in |
| 12 in | 113 sq in | 1,356 sq in |
| 15 in | 176 sq in | 2,112 sq in |
| 18 in | 254 sq in | 3,048 sq in |
Step-by-Step Math
- Opening = 36 × 28 in = 1,008 sq in
- Minimum flue = 1,008 sq in ÷ 12 = 84.0 sq in
- Smallest standard round liner at or above it: 10 3/4 in = 90.0 sq in
- Draft = 0.0342 × 101,325 Pa × 6.10 m × (1/273.2 K - 1/477.6 K) = 33.1 Pa = 0.133 in w.c.
- Roof height = larger of 3 ft and (7 ft × 6/12 + 2 ft) = 5 ft 6 in
Chimney Flue Size Calculator Ratios for Round and Clay Liners
A fireplace flue needs a net inside area of at least 1/12 of the fireplace opening when round and 1/10 when square. A rectangular clay flue with sides at 2:1 or longer needs 1/8, under IRC Section R1003.15.1.
A_min is the minimum net flue area in sq in, W and H are the opening width and height in inches, and k is 12 for round, 10 for square or rectangular under 2:1, and 8 for rectangular at 2:1 or longer.
A 36 × 28 in opening is 1,008 sq in. Divided by 12 that is 84.0 sq in, so the round liner is a 10 3/4 in tile at 90 sq in net, 7% spare. Divided by 10 it is 100.8 sq in, which a 12 × 12 in clay tile at 102 sq in just covers.
Clay tiles are named by outside size, so a 12 × 12 in tile has 102 sq in inside, not 144. Every chimney flue size calculator check runs on that net figure, which is why a tile that looks big enough on the outside can still fall short.
d is the inside diameter in inches and A is the net area in sq in. The 84.0 sq in need works out to 10.34 in, a size no clay round is made in, so the chimney flue size calculator result steps up to the 10 3/4 in tile.
Stainless liners come in exact inside diameters, so for stainless the chimney diameter calculation stops at the first stock size above 10.34 in.
Openings Each Standard Liner Can Serve
Multiply a liner's net area by its ratio to get the largest fireplace opening it can serve, the reverse of a chimney flue size calculator estimate. A 12 in round tile at 113 sq in serves up to 1,356 sq in, about a 48 × 28 in opening.
Round net areas below come from IRC Table R1003.14(1), with each opening limit at 12 times the area. This chimney flue diameter chart reads backward from an existing flue to the biggest fireplace it can carry.
| Inside Diameter (in) | Inside Diameter (mm) | Net Area (sq in) | Largest Opening (sq in) |
|---|---|---|---|
| 6 | 152 | 28 | 336 |
| 7 | 178 | 38 | 456 |
| 8 | 203 | 50 | 600 |
| 10 | 254 | 78 | 936 |
| 10 3/4 | 273 | 90 | 1,080 |
| 12 | 305 | 113 | 1,356 |
| 15 | 381 | 176 | 2,112 |
| 18 | 457 | 254 | 3,048 |
Square and rectangular tiles from Table R1003.14(2) follow. Two of them, 4.5 × 13 and 8.5 × 18 in, sit at 2:1 or longer, so their limit is 8 times the net area instead of 10 in this masonry fireplace flue size chart.
| Outside Size (in) | Net Area (sq in) | Ratio Used | Largest Opening (sq in) |
|---|---|---|---|
| 4.5 × 8.5 | 23 | 1/10 | 230 |
| 4.5 × 13 | 34 | 1/8 | 272 |
| 8 × 8 | 42 | 1/10 | 420 |
| 8.5 × 8.5 | 49 | 1/10 | 490 |
| 8 × 12 | 67 | 1/10 | 670 |
| 8.5 × 13 | 76 | 1/10 | 760 |
| 12 × 12 | 102 | 1/10 | 1,020 |
| 8.5 × 18 | 101 | 1/8 | 808 |
| 13 × 13 | 127 | 1/10 | 1,270 |
| 12 × 16 | 131 | 1/10 | 1,310 |
| 13 × 18 | 173 | 1/10 | 1,730 |
| 16 × 16 | 181 | 1/10 | 1,810 |
| 16 × 20 | 222 | 1/10 | 2,220 |
| 18 × 18 | 233 | 1/10 | 2,330 |
| 20 × 20 | 298 | 1/10 | 2,980 |
| 20 × 24 | 335 | 1/10 | 3,350 |
| 24 × 24 | 431 | 1/10 | 4,310 |
Fireplace Sizes, Liners and Hearth Extensions
A 36 × 30 in opening at 1,080 sq in pushes a square flue from 12 × 12 to 13 × 13 in, while the round still fits a 10 3/4 in tile at exactly 90 sq in.
The rows below run the same chimney flue size calculator math over common masonry fireplace openings, from a 30 × 24 in firebox to a 60 × 36 in walk-in style hearth.
| Opening (in) | Area (sq in) | Area (sq ft) | Round Need (sq in) | Round Liner (in) | Square Need (sq in) | Clay Tile (in) | Hearth Front / Side (in) |
|---|---|---|---|---|---|---|---|
| 30 × 24 | 720 | 5.00 | 60.0 | 10 | 72.0 | 8.5 × 13 | 16 / 8 |
| 32 × 26 | 832 | 5.78 | 69.3 | 10 | 83.2 | 12 × 12 | 16 / 8 |
| 36 × 24 | 864 | 6.00 | 72.0 | 10 | 86.4 | 12 × 12 | 20 / 12 |
| 36 × 28 | 1,008 | 7.00 | 84.0 | 10 3/4 | 100.8 | 12 × 12 | 20 / 12 |
| 36 × 30 | 1,080 | 7.50 | 90.0 | 10 3/4 | 108.0 | 13 × 13 | 20 / 12 |
| 42 × 30 | 1,260 | 8.75 | 105.0 | 12 | 126.0 | 13 × 13 | 20 / 12 |
| 48 × 32 | 1,536 | 10.67 | 128.0 | 15 | 153.6 | 13 × 18 | 20 / 12 |
| 60 × 36 | 2,160 | 15.00 | 180.0 | 18 | 216.0 | 16 × 20 | 20 / 12 |
Opening area also sets the hearth. At 6 sq ft (864 sq in) or more, the IRC hearth extension grows from 16 in in front and 8 in each side to 20 in and 12 in, and a 36 × 24 in opening lands exactly on that line.
Going from 32 × 26 in to 36 × 24 in adds only 32 sq in of opening but 4 in of hearth depth and 4 in on each side, so a chimney flue size calculator check on a wider firebox should include the slab in front.
Elongated Clay Tiles Lose a Fifth of Their Reach
An 8.5 × 18 in tile has 101 sq in net, almost the same as a 12 × 12 in tile at 102 sq in. It serves only 808 sq in of opening against 1,020, because its 2.12:1 shape puts it under the 1/8 rule in any chimney flue size calculator math.
On a 36 × 28 in fireplace, the 12 × 12 passes with 100.8 sq in needed. The 8.5 × 18 needs 126 sq in for the same opening and falls 25 sq in short, though an area-only chimney flue size chart would call the two tiles equal.
The same 20% cut hits the 4.5 × 13 in tile, whose 34 sq in serves 272 sq in of opening instead of 340. Any chimney flue size calculator check on an oval or slot-shaped flue should start with the long side divided by the short side.
The ratio is measured on the tile's outside size. A 4.5 × 8.5 in tile is 1.89:1 and keeps the 1/10 rule, so it serves 230 sq in, while the next tile up at 4.5 × 13 in crosses 2:1 and drops to 1/8.
Wood Stove Liners Between 1x and 3x the Collar
A wood stove flue must be no smaller than the collar, per IRC R1003.14, and no larger than 3 times the collar area on an inside chimney. On a chimney with a face exposed to outdoor cold, the cap is 2 times.
The 3 and 2 times caps come from Washington Association of Building Officials rules quoted in The Chimney Sweep's liner sizing guide, which rates a same-size stainless liner as the best chimney flue size calculator match.
| Collar (in) | Collar Area (sq in) | Round Liner (in) | 3× Cap (sq in) | 2× Cap, Exterior (sq in) | Clay Tiles Within 3× (in) |
|---|---|---|---|---|---|
| 5 | 19.6 | 5 | 58.9 | 39.3 | 4.5 × 8.5, 4.5 × 13, 8 × 8, 8.5 × 8.5 |
| 6 | 28.3 | 6 | 84.8 | 56.5 | 4.5 × 13, 8 × 8, 8.5 × 8.5, 8 × 12, 8.5 × 13 |
| 7 | 38.5 | 7 | 115.5 | 77.0 | 8 × 8, 8.5 × 8.5, 8 × 12, 8.5 × 13, 12 × 12, 8.5 × 18 |
| 8 | 50.3 | 8 | 150.8 | 100.5 | 8 × 12, 8.5 × 13, 12 × 12, 8.5 × 18, 13 × 13, 12 × 16 |
A 6 in collar on an existing 13 × 13 in clay flue is 4.49 times the collar area, so that chimney flue size calculator check fails and the flue takes a 6 in stainless liner.
An 8 × 12 in tile on the same 6 in collar is 2.37 times the collar area. That passes on a chimney inside the house but breaks the 2 times cap where the chimney runs up an outside wall.
Englander's manual for a 6 in collar model sets the same window, a liner of at least the collar area and no more than 84.8 sq in, which is 3 times 28.3 sq in.
Gas and oil appliances are sized by input rating from vent tables, the data behind a chimney liner sizing chart in BTU. Collar area only sets the minimum under R1003.14, so a chimney flue size calculator figure for gas is a floor.
Draft Pressure by Height and Flue Temperature
A 20 ft chimney with 400°F flue gas and 32°F outdoor air makes about 0.133 in w.c., or 33.1 Pa, of theoretical draft at sea level. Draft rises in direct proportion to height and with the gap between flue and outdoor temperature.
ΔP is draft in Pa, C is 0.0342 K/m, a is air pressure in Pa, h is chimney height in m, and T_o and T_i are outdoor and flue gas temperatures in kelvin, per the stack effect equation.
All rows below assume 32°F outdoor air at sea level. A 10 ft stack at 250°F makes less than a quarter of the draft of a 30 ft stack at 400°F, which is why short chimneys draw poorly even on a correct chimney flue size calculator minimum.
| Chimney Height (ft) | 250°F Flue (in w.c.) | 400°F Flue (in w.c.) | 600°F Flue (in w.c.) |
|---|---|---|---|
| 10 (3.05 m) | 0.048 | 0.066 | 0.083 |
| 15 (4.57 m) | 0.072 | 0.100 | 0.125 |
| 20 (6.10 m) | 0.095 | 0.133 | 0.166 |
| 30 (9.14 m) | 0.143 | 0.199 | 0.250 |
| 40 (12.19 m) | 0.191 | 0.266 | 0.333 |
Thin air cuts draft. At 5,000 ft the air pressure falls to about 84,300 Pa, and the same 20 ft, 400°F chimney drops to 0.111 in w.c., 17% less. At 7,000 ft it is 0.103 in w.c., a loss no chimney flue size calculator ratio adjusts for.
These are static figures with no gas moving, and friction lowers the real reading. Englander's manual also caps operating draft at 0.05 in w.c., so a tall hot flue is not always better.
Rise Above the Roof by Pitch and Ridge Distance
On a 6/12 roof with the ridge 7 ft away, a chimney needs 5 ft 6 in above the point where it leaves the roof, because the ridge rises 3 ft 6 in and the top must clear it by 2 ft. Flat roofs and low pitches near the ridge stop at the 3 ft minimum.
Each cell is the height above the highest point where the chimney leaves the roof, using the roof rise over the first 10 ft of level run. This height check is separate from the chimney flue size calculator area check.
| Roof Pitch | Ridge 2 ft Away | Ridge 4 ft Away | Ridge 7 ft Away | Ridge 10 ft Away | Ridge 15 ft Away |
|---|---|---|---|---|---|
| 4/12 | 3 ft | 3 ft 4 in | 4 ft 4 in | 5 ft 4 in | 5 ft 4 in |
| 6/12 | 3 ft | 4 ft | 5 ft 6 in | 7 ft | 7 ft |
| 8/12 | 3 ft 4 in | 4 ft 8 in | 6 ft 8 in | 8 ft 8 in | 8 ft 8 in |
| 12/12 | 4 ft | 6 ft | 9 ft | 12 ft | 12 ft |
Past 10 ft the ridge no longer counts. With the ridge 15 ft away on a 12/12 roof, the 12 ft stack meets the rule while ending 3 ft below ridge level, and the 10 ft and 15 ft columns read the same for that reason.
The Chimney Height Calculator carries this through to total stack height, and the Roof Pitch Calculator turns a measured rise and run or angle into the x/12 pitch these rows use.
Flue Diameter in mm From a Metric Opening
A 914 × 711 mm opening, the metric match of 36 × 28 in, is 6,499 cm². One twelfth is 541.5 cm², met by a 273 mm round liner at 581 cm², and one tenth is 650 cm², met by a 305 × 305 mm clay tile at 658 cm².
Chimney flue size calculator in mm results use the same ratios on cm², since 1 sq in is 6.4516 cm². The liner sizes below are US clay sizes converted to mm, so a local metric liner should be checked by its listed net area.
| Opening (mm) | Area (cm²) | Round Need (cm²) | Round Liner, mm (cm²) | Clay Tile, mm (cm²) |
|---|---|---|---|---|
| 600 × 600 | 3,600 | 300.0 | 203 (323) | 203 × 305 (432) |
| 700 × 600 | 4,200 | 350.0 | 254 (503) | 203 × 305 (432) |
| 800 × 600 | 4,800 | 400.0 | 254 (503) | 216 × 330 (490) |
| 900 × 700 | 6,300 | 525.0 | 273 (581) | 305 × 305 (658) |
| 1000 × 700 | 7,000 | 583.3 | 305 (729) | 330 × 330 (819) |
Older Code Tables List Smaller Net Areas
The 2003 IRC listed a 13 × 13 in tile at 122 sq in net, while the current table lists 127. A 1,250 sq in opening needs 125 sq in square, so the same tile fails under the old figure and passes under the new one.
The 2003 list also used 7 1/2 and 11 1/2 in nominal sizes, with 8 1/2 × 8 1/2 in at 47 sq in against 49 today. A 24 × 20 in opening needs 48 sq in square, a chimney flue size calculator result that sits right between the two editions.
For an existing chimney, measure the tile's inside width and depth before any chimney flue size calculator check. The ratio tests the net inside area, and a reading from the tile itself settles which edition's number applies.
Sizing Purpose, Draft and Shared Flues
A wrong flue shows up as smoke in the room or creosote on the liner, and both trace back to the ratio between the flue and what burns below it, the core of every chimney flue size calculator check.
What is a flue size calculator?
It is a sizing check for the smallest net flue area. For a 40 × 30 in fireplace, the chimney flue size calculator minimum is 1,200 sq in divided by 12, or 100 sq in, so a 12 in round tile at 113 sq in clears it.
A square flue on the same opening needs 120 sq in and a 13 × 13 in tile. For a wood stove the starting point is the collar instead of the opening, and for gas it is the input rating.
Why is chimney flue sizing important?
Flue size sets how fast smoke moves up the chimney. Too small, and a fireplace spills smoke into the room. Too large, and slow gas cools on the way up and leaves creosote on the liner walls.
A 5 in stove collar on a 12 × 12 in clay flue fails a chimney flue size calculator check at 5.19 times the collar, well past the 3 times limit. That stove needs a 5 in liner, or a 4.5 × 8.5 in clay tile at 23 sq in, which is 1.17 times the collar.
How do you calculate a chimney draft?
Run the stack equation with height in meters and both temperatures in kelvin. On an 80°F day, a 15 ft chimney with 250°F gas makes only 0.051 in w.c., half the 0.100 in w.c. it makes with 400°F gas at 32°F.
Poor draft comes from the same terms: a short stack, a cool flue, warm outdoor air, high elevation, or a flue so big the gas slows and cools.
How do I size a flue for a fireplace?
Measure the width and height at the front of the firebox, multiply them, then divide by 12 for a round flue or 10 for a square one. A 34 × 27 in opening is 918 sq in, so it needs 76.5 sq in round or 91.8 sq in square.
The smallest round tile at or above 76.5 sq in is 10 in at 78 sq in, the same rounding up behind any chimney flue size calculator answer. The smallest square tile at or above 91.8 sq in is 12 × 12 in at 102 sq in, since 8.5 × 13 in stops at 76 sq in.
Does chimney height matter?
Height changes both draft and the chimney flue size calculator answer. IRC R1003.15.2 allows a chimney to be sized from a chart instead of the ratio, with height measured from the firebox floor to the top of the flue.
Older FHA guidance cited by InspectAPedia used 1/8 instead of 1/10 under 15 ft. That takes a 36 × 28 in fireplace from 100.8 to 126 sq in, and from a 12 × 12 to a 13 × 13 in tile.
Can I connect multiple appliances to one flue?
Only when the shared flue is sized for all of them. IRC R1003.14 sends a chimney flue serving several appliance vents to the mechanical code, Section M1805.3, rather than the single-collar rule behind a chimney flue size calculator stove result.
Fuel gas codes also keep a gas appliance off a flue that serves a wood stove or fireplace. Separate flues in one chimney need a masonry wythe at least 4 in thick between the linings, per R1003.13.
What is the 3-2-10 rule for chimneys?
A chimney must end at least 3 ft above the highest point where it passes through the roof and at least 2 ft above any part of the building within 10 ft. Englander's manual repeats the same three numbers for its stoves.
On a 5/12 roof with the ridge 12 ft away, the roof 10 ft upslope is 4 ft 2 in higher. The chimney then needs 6 ft 2 in above the roof and ends 1 ft 2 in above ridge level, since the ridge itself is 5 ft up.