Gas Load and Pipe Run

Enter the appliance input in BTU/h and the pipe length from the meter to the farthest appliance.

Gas Pressure and Heating Value7.00 in. w.c. supply, 0.50 in. w.c. drop
Fittings and Equivalent Length6 fittings
elbows
elbows
tees
Gas Pipe Size
1 in Black Iron Gas Pipe
Inside diameter 1.049 in, IFGC Equation 4-1, longest length method
220,142 BTU/h Pipe Capacity
Capacity Used81.8%
Room for More40,142 BTU/h
Most gas this size can carry at your length and allowed drop. Room for More is what you can still add.
0.34 in. w.c. Pressure Drop
Pressure at Outlet6.66 in. w.c.
Drop Allowance Used68.9%
Pressure lost from the meter to the farthest outlet at your load. It must stay within the allowed drop.
180.0 CFH Gas Flow
Equivalent Length81.0 ft
Minimum Inside Diameter0.972 in
Load ÷ heating value. Equivalent length adds the fittings to the run. Minimum ID is what the equation needs.
96.5 ft Max Run at This Size
Next Size Down Holds120,486 BTU/h
Next Size Up Holds433,370 BTU/h
Longest pipe this size can run at your load, fittings taken out. Neighbor sizes are rated at your length.
Gas Line Diagram7.00 in. w.c. in, 6.66 in. w.c. out
MeterFarthestOutlet1 in Black Iron7.00 in. w.c.6.66 in. w.c.60.0 ft pipe + 21.0 ft fittings and extraDrop 0.34 in. w.c. of 7.00 in. w.c. supply180,000 BTU/h = 180.0 CFH of natural gas
Appliance Branch Sizes
Gas Pipe Size ChartMBH by equivalent length
Black Iron10 ft20 ft30 ft40 ft50 ft60 ft80 ft100 ft150 ft200 ft
1/2 in1731199682726656504034
3/4 in3622492001711521371181048472
1 in682469377322286259222196158135
1-1/4 in1,401963774662587532455403324277
1-1/2 in2,1001,4431,159992880797682605486416
2 in4,0462,7812,2341,9121,6951,5361,3141,165936801
2-1/2 in6,4504,4343,5613,0482,7022,4482,0951,8571,4921,277
3 in11,4077,8416,2985,3914,7784,3293,7063,2852,6382,258
4 in23,27616,00112,85111,0009,7508,8347,5626,7025,3834,608
5 in42,12628,95923,25819,90817,64515,98913,68612,1309,7428,339
6 in68,23346,90637,67232,24528,58125,89822,16719,64815,78013,507
8 in140,25696,41977,43766,28358,74953,23445,56640,38732,43627,764
10 in254,840175,188140,701120,433106,74596,72482,79173,38158,93550,446
12 in403,561277,427222,812190,716169,040153,171131,107116,20693,32979,885
Step-by-Step Gas Pipe Sizing Math6 steps

Gas flow180,000 BTU/h ÷ 1,000 BTU/ft³ = 180.00 CFH

Equivalent length60 ft + (4 × 30 + 0 × 14 + 2 × 60) × 1.049 in ÷ 12 = 80.98 ft

Capacity, Eq. 4-1(19.17 × 1.049 × (0.5 ÷ (0.6094 × 80.98))^0.206)^(1 ÷ 0.381) = 220.1 CFH × 1,000 = 220,142 BTU/h

Minimum inside diameter180.00^0.381 ÷ (19.17 × (0.5 ÷ (0.6094 × 80.98))^0.206) = 0.972 in

Pressure drop0.6094 × 80.98 × (180.00^0.381 ÷ (19.17 × 1.049))^(1 ÷ 0.206) = 0.345 in. w.c.

Pressure at outlet7.00 in. w.c. - 0.34 in. w.c. = 6.66 in. w.c.

Size Carries the Full Load
Smallest Black Iron size that carries 180,000 BTU/h to the farthest outlet within the allowed drop.

Gas Pipe Size Calculator Capacity Chart in CFH and BTU

A 180,000 BTU/h natural gas load on a 60 ft run needs 1 in Schedule 40 black iron at a 0.5 in. w.c. drop. A 3/4 in pipe carries only 137 CFH at that length, about 137,000 BTU/h of 1,000 BTU/ft³ gas.

Gas pipe sizing, by hand or with a gas pipe size calculator, finds the smallest pipe that delivers the full load to the farthest outlet within the allowed pressure loss. The flow comes from the load divided by the gas heating value.

Q is the flow in cubic feet per hour, D the inside diameter in inches, ΔH the allowed drop in inches of water column, L the equivalent length in feet and Cr 0.6094 for natural gas.

Every gas pipe size calculator built on code uses these constants, which match the low-pressure equation in California Plumbing Code section 1215.3.

Length1/2 in3/4 in1 in1-1/4 in1-1/2 in2 in
10 ft1733626821,4012,1004,046
20 ft1192494699631,4432,781
30 ft962003777741,1592,234
40 ft821713226629921,912
50 ft721522865878801,695
60 ft661372595327971,536
80 ft561182224556821,314
100 ft501041964036051,165
150 ft4084158324486936
200 ft3472135277416801

Values are CFH of natural gas in Schedule 40 steel at a 0.5 in. w.c. drop with no fittings added, tracking IFGC Table 402.4(2).

At 1,000 BTU/ft³, each CFH is 1,000 BTU/h, so this natural gas pipe sizing chart in BTU reads in thousands. The 60 ft row, for example, puts 3/4 in pipe at 137,000 BTU/h.

Doubling the length does not halve a gas pipe size calculator capacity. Going from 50 ft to 100 ft cuts 3/4 in pipe from 152 to 104 CFH, a loss of about 31%, because flow falls with length raised to the power 0.54.

Fittings Add Feet Before Any Sizing

In gas pipe size calculator terms, four 90° elbows and two tees on a 1 in line add 21 ft of equivalent length, so the 60 ft run sizes as 81 ft. That cuts 1 in capacity from 259 to 220 CFH, still enough for the 180 CFH load.

The fitting lengths come from fuel gas code Table A102.2, which rates a screwed 90° elbow at 30 pipe diameters, a 45° elbow at 14 and a tee at 60. On 3/4 in pipe the same set of fittings adds 16.5 ft.

Le is the equivalent length in feet, L the measured run, n the number of each fitting type and D the inside diameter in inches. A long run with many tees can gain more length from fittings than from the pipe itself.

Code capacity tables already allow for an ordinary number of fittings, so a gas pipe size calculator chart read at the measured length is the table method. Adding fittings on top is the engineering method, and it gives the more cautious answer.

Pressure Drop Allowance Changes the Answer

A 60 ft run of 1 in steel carries 196 CFH at a 0.3 in. w.c. drop, 259 CFH at 0.5 and 377 CFH at 1.0 in any gas pipe size calculator. More drop is the cheapest way to fit a load into a smaller pipe, if appliances still get enough pressure.

Allowed drop1 in steel at 60 ftChange from 0.5 in. w.c.
0.3 in. w.c.196 CFH-24%
0.5 in. w.c.259 CFHbaseline
1.0 in. w.c.377 CFH+46%
2.0 in. w.c.548 CFH+112%
3.0 in. w.c.682 CFH+163%

The allowed drop is the meter outlet pressure minus the lowest pressure the farthest appliance needs. If that appliance needs 5 in. w.c. on a 7 in. supply, up to 2 in. is available, and the capacity table above shows what each step buys.

The 3 in. w.c. row belongs to supplies of at least 8 in. w.c., the floor the code sets for its 3 in. drop CSST table, and 6 in. drops need at least 11 in. w.c. On a 7 in. supply a 3 in. drop would leave only 4 in. at the outlet.

Propane Versus Natural Gas Capacity

At 11 in. w.c. and a 0.5 in. drop, 3/4 in steel carries 235,000 BTU/h of propane over 60 ft, against 137,000 BTU/h of natural gas. Propane is denser, so less gas moves, but each cubic foot holds 2,516 BTU.

Length1/2 in3/4 in1 in1-1/4 in1-1/2 in
20 ft2034258011,6462,467
40 ft1402925511,1321,696
60 ft1122354429091,362
100 ft851783366891,033

Values are thousands of BTU/h of propane in Schedule 40 steel, using Cr 1.2462 from the same code table. The 180,000 BTU/h house load that needs 1 in on natural gas fits 3/4 in on propane, even with the four elbows and two tees.

A propane pipe size calculator has to run in BTU, not CFH. One CFH of propane is 2,516 BTU/h, so a natural gas chart read in BTU understates propane capacity by about 1.7 times at the same length.

Two psi Systems and the 5 psi Indoor Limit

At 2 psi supply with a 1 psi drop, 1/2 in steel carries 460 CFH over 100 ft, more than nine times its 50 CFH at 0.5 in. w.c. Elevated pressure is how long runs to large homes stay small.

P1 and P2 are the inlet and outlet pressures in psia, gauge plus 14.7, and Y is 0.9992 for natural gas. This high-pressure formula applies from 1.5 psi up, under the same code section as the low-pressure one.

Length at 2 psi, 1 psi drop1/2 in3/4 in1 in
50 ft669 CFH1,399 CFH2,636 CFH
100 ft460 CFH961 CFH1,812 CFH
200 ft316 CFH661 CFH1,245 CFH

Each appliance on a 2 psi system needs a line regulator, and the pipe after it is sized as its own low-pressure run.

A gas pipe size calculator result at 2 psi covers only the elevated section. The fuel gas code caps piping inside buildings at 5 psi unless joints are welded or brazed or another listed condition is met.

CSST, Copper and PE Sized for One Load

In a gas pipe size calculator, 180,000 BTU/h over 60 ft takes 1 in black iron, Type L copper or buried PE, or 1-1/4 in CSST with an EHD of 37. CSST is corrugated, so it is sized by its own code tables rather than the smooth-pipe equation.

MaterialSize for 180,000 BTU/h at 60 ftEquivalent lengthCapacity at that length
Black iron, Schedule 401 in81.0 ft220.1 CFH
Copper tubing, Type L1 in80.5 ft207.8 CFH
Polyethylene, buried1 in81.5 ft235.0 CFH
CSST, EHD 371-1/4 in62.6 ft248 CFH

CSST tables already include four 90° bends and two end fittings, and each extra bend or fitting adds 1.3 ft. The two tees in the example add 2.6 ft, which is why its equivalent length stays near the measured 60 ft.

Each material carries its own code condition. CSST needs a bonding jumper of at least 6 AWG copper, copper tubing is barred where gas carries over 0.3 grains of hydrogen sulfide per 100 cu ft, and PE goes outdoors underground with a tracer wire.

Appliance Loads Under the Longest Length Method

A furnace at 80,000, water heater at 40,000, range at 65,000, dryer at 22,000 and fireplace at 30,000 BTU/h add to 237,000 BTU/h. At 60 ft with the same fittings, that main needs 1-1/4 in steel, rated 433 CFH at 87.6 ft equivalent.

Under the longest length method, every section is read at the distance from the meter to the farthest outlet, even short branches.

Each branch then carries only its own load, so at 60 ft the furnace and range need 3/4 in, while the water heater, dryer and fireplace each fit 1/2 in.

ApplianceLoadBranch size at 60 ftBranch capacity
Furnace80,000 BTU/h3/4 in120.5 CFH
Range65,000 BTU/h3/4 in120.5 CFH
Water heater40,000 BTU/h1/2 in59.3 CFH
Fireplace30,000 BTU/h1/2 in59.3 CFH
Dryer22,000 BTU/h1/2 in59.3 CFH

Branch capacities include four elbows and two tees on each branch, the same fittings as the gas pipe size calculator main.

A gas pipe size calculator for appliances should use the rating plate input, and the heating value from the gas supplier, since 1,050 BTU/ft³ gas needs only 171 CFH for the same 180,000 BTU/h.

Kilowatts, Cubic Meters and Millibars

For a gas pipe size calculator in metric, a 24 kW boiler draws 81,891 BTU/h, about 2.32 m³/h of 1,000 BTU/ft³ natural gas. On a straight 20 m steel run at a 1 mbar drop, the IFGC equation sizes it at 3/4 in, rated 116 CFH at that length.

One mbar equals 0.40 in. w.c. and 1 kW equals 3,412 BTU/h. A gas pipe size calculator UK or metric result in mm and kW still follows the same flow physics, but UK work is designed to BS 6891 and Australian and New Zealand work to AS/NZS 5601.

Those standards set their own pressure losses and pipe tables, so a metric IFGC answer is a cross-check rather than a compliance result there. In the US the IFGC or NFPA 54 governs, while Canada uses CSA B149.1.

Code Steps for Sizing a Gas Line

Each answer uses gas pipe size calculator settings of natural gas at 1,000 BTU/ft³, a 7 in. w.c. supply and a 0.5 in. drop in Schedule 40 steel, unless it names another gas or material.

What size gas pipe do I need?

Divide the total load in BTU/h by 1,000 for CFH, then find the smallest pipe that carries it at the length to the farthest outlet. A 100,000 BTU/h load at 50 ft needs 3/4 in, since 1/2 in carries only 72 CFH there.

Length decides as much as load. That same 3/4 in line carries 100 CFH only up to about 108 ft of equivalent length, so a longer or fitting-heavy run moves the same 100,000 BTU/h load to 1 in.

How do I calculate gas pipe sizing?

Add every appliance input, measure from the meter to the farthest outlet, add fitting length, and read or calculate capacity at that length for the allowed drop.

In any gas pipe size calculator for home layouts, the main carries the total and each branch carries its own appliances at the same length.

For the five-appliance house, 237,000 BTU/h at 60 ft plus fittings sets a 1-1/4 in main, and the branches drop to 3/4 in and 1/2 in. The Pipe Flow Calculator and Water Pipe Size Calculator cover liquid lines, which follow different equations.