Water pipe size calculator for copper, PEX, CPVC, PVC and steel from GPM or fixture units, checking velocity limits, Hazen-Williams friction loss and pressure left at each fixture.
Enter peak flow or fixture units, then pick the pipe material and run length.
Water Pressure and Friction Loss
Pipe Size and Pressure Diagram
Water Pipe Size Chart
| Copper Type L | Inside Diameter | Velocity | Friction per 100 ft | Flow at Limit | Result |
|---|---|---|---|---|---|
| 1/2 in | 0.545 in | 13.8 fps | 65.93 psi | 5.8 GPM | Too Fast |
| 3/4 in | 0.785 in | 6.6 fps | 11.17 psi | 12.1 GPM | Fits |
| 1 in | 1.025 in | 3.9 fps | 3.05 psi | 20.6 GPM | Fits |
| 1-1/4 in | 1.265 in | 2.6 fps | 1.10 psi | 31.3 GPM | Fits |
| 1-1/2 in | 1.505 in | 1.8 fps | 0.47 psi | 44.4 GPM | Fits |
| 2 in | 1.985 in | 1.0 fps | 0.12 psi | 77.2 GPM | Fits |
| 2-1/2 in | 2.465 in | 0.7 fps | 0.04 psi | 119.0 GPM | Fits |
| 3 in | 2.945 in | 0.5 fps | 0.02 psi | 169.9 GPM | Fits |
| 4 in | 3.905 in | 0.3 fps | 0.00 psi | 298.6 GPM | Fits |
Step-by-Step Pipe Sizing Math
Minimum inside diameter√(0.4085 × 10.00 GPM ÷ 8 fps) = 0.715 in
Velocity in 3/4 in0.4085 × 10.00 ÷ 0.785² = 6.63 fps
Friction per 100 ft0.2083 × (100 ÷ 140)^1.852 × 10.00^1.852 ÷ 0.785^4.8655 = 25.80 ft × 0.433 = 11.17 psi
Run friction loss100.0 ft × 1.5 = 150.0 ft × 11.170 ÷ 100 = 16.76 psi
Pressure at fixture60.00 - 16.76 - 10.0 ft × 0.433 - 0.00 = 38.91 psi
Sizing With a Water Pipe Size Calculator: Flow, Velocity, Diameter
A 10 GPM copper line kept under 8 fps needs an inside diameter of at least 0.715 in, so 3/4 in Type L copper fits. Its 0.785 in bore carries that flow at 6.63 fps.
d is the minimum inside diameter in inches, Q is the flow in GPM and v is the velocity limit in feet per second. The 0.4085 constant folds the circle area and the GPM-to-cubic-feet conversion into one number.
Nominal size is a label, not the bore. A 3/4 in pipe runs from 0.681 in inside for PEX SDR 9 to 0.824 in for Schedule 40 PVC.
A water pipe size calculator in inches therefore has to work from the inside diameter of the real material. Comparing the 0.715 in minimum with each bore is what picks the size.
hf is the Hazen-Williams friction head in feet per 100 ft of pipe and C is the roughness factor. Multiply by 0.433 for psi. The Hazen Williams Equation Calculator runs that loss on its own.
Flow Each Pipe Carries at Its Velocity Limit
At 8 fps, 3/4 in Type L copper carries 12.1 GPM and 1 in carries 20.6 GPM. At 5 fps, the same 3/4 in pipe drops to 7.5 GPM, which is why hot water lines often come out a size larger.
| Pipe (limit) | 1/2 in | 3/4 in | 1 in | 1-1/4 in | 1-1/2 in | 2 in |
|---|---|---|---|---|---|---|
| Copper Type L, 8 fps | 5.8 GPM | 12.1 GPM | 20.6 GPM | 31.3 GPM | 44.4 GPM | 77.2 GPM |
| Copper Type L, 5 fps | 3.6 GPM | 7.5 GPM | 12.9 GPM | 19.6 GPM | 27.7 GPM | 48.2 GPM |
| PEX SDR 9, 5 fps | 2.9 GPM | 5.7 GPM | 9.4 GPM | 14.0 GPM | 19.5 GPM | 33.4 GPM |
| CPVC SDR 11, 5 fps | 2.9 GPM | 6.3 GPM | 10.4 GPM | 15.5 GPM | 21.6 GPM | 37.0 GPM |
| PVC Schedule 40, 5 fps | 4.7 GPM | 8.3 GPM | 13.5 GPM | 23.3 GPM | 31.7 GPM | 52.3 GPM |
A pipe size calculation chart like this is a velocity-only water pipe size calculator result. It answers what fits at a given speed, not whether enough pressure reaches the far fixture, which the next section covers.
The 5 fps figure is common for irrigation mains. Washington State University calls it a somewhat arbitrary threshold and also checks friction loss, elevation and water hammer.
A water pipe size calculator for irrigation should therefore not stop at velocity. Long laterals lose more to friction than to speed, as the next table shows for house lines too.
Friction Loss Sometimes Picks the Bigger Pipe
A 10 GPM line run 200 ft upstairs can pass the water pipe size calculator velocity test in 3/4 in copper and still fail on pressure. With 50 psi supply, 15 psi needed at the fixture and a 20 ft rise, only 26.34 psi is left for friction.
Ps is the supply pressure, Pr the pressure the fixture needs, h the rise in feet and Pm the meter loss, all in psi. Each foot of rise costs 0.433 psi, so a 20 ft climb uses 8.66 psi.
With a 50% allowance for fittings, the 200 ft run counts as 300 ft. In 3/4 in Type L copper, 10 GPM loses 33.51 psi over that length, more than the 26.34 psi available, so the size goes to 1 in, which loses only 9.15 psi.
| Flow, copper Type L | 50 ft run | 100 ft run | 200 ft run |
|---|---|---|---|
| 5 GPM | 1/2 in, 13.7 psi | 1/2 in, 27.4 psi | 3/4 in, 9.3 psi |
| 10 GPM | 3/4 in, 8.4 psi | 3/4 in, 16.8 psi | 3/4 in, 33.5 psi |
| 15 GPM | 1 in, 4.8 psi | 1 in, 9.7 psi | 1 in, 19.4 psi |
| 20 GPM | 1 in, 8.3 psi | 1 in, 16.5 psi | 1 in, 33.0 psi |
| 30 GPM | 1-1/4 in, 6.3 psi | 1-1/4 in, 12.6 psi | 1-1/4 in, 25.2 psi |
The water pipe size calculator table uses 60 psi supply, 8 psi needed at the fixture, a 10 ft rise, a 50% fittings allowance and C 140, which leaves 47.67 psi for friction. Each cell gives the size that passes both tests and its friction loss.
At 5 GPM, 1/2 in copper is fine to 100 ft but loses too much over 200 ft, so the long run steps up to 3/4 in. Pipe age matters too, since 1 in copper at 10 GPM over 150 ft loses 4.58 psi at C 140 but 8.53 psi at C 100.
Supply pressure and pump head convert at 2.31 ft per psi in any water pipe size calculator pressure budget. The Pump Pressure Calculator handles that side when the supply comes from a pump or tank.
Fixture Units Converted to Design GPM
For a water pipe size calculator for plumbing, thirty water supply fixture units (WSFU) mean 23.3 GPM in a flush-tank building but 42 GPM where toilets use flushometer valves. That gap moves the copper main from 1-1/4 in to 1-1/2 in.
The demand numbers come from IPC Table E103.3(3), the Hunter demand table in the International Plumbing Code. Some states print their own reading of the curve, so the flushometer column can differ slightly by jurisdiction.
| WSFU | Flush tanks, GPM | Copper L at 8 fps | Flushometer valves, GPM | Copper L at 8 fps |
|---|---|---|---|---|
| 10 | 14.6 | 1 in | 27.0 | 1-1/4 in |
| 20 | 19.6 | 1 in | 35.0 | 1-1/2 in |
| 30 | 23.3 | 1-1/4 in | 42.0 | 1-1/2 in |
| 40 | 26.3 | 1-1/4 in | 46.0 | 2 in |
| 50 | 29.1 | 1-1/4 in | 50.0 | 2 in |
| 100 | 43.5 | 1-1/2 in | 67.5 | 2 in |
Sizes in the table come from the 100 ft run and default pressure budget above. Between listed rows the demand is read by straight-line interpolation, so 27 WSFU on flush tanks gives 22.2 GPM.
The flushometer column starts at 5 WSFU, which already means 15 GPM. A water supply pipe sizing estimate for a single flushometer toilet therefore starts near 1 in copper, while a flush-tank house of that load needs only 9.4 GPM.
PEX, CPVC and Copper Need Different Sizes
In water pipe size calculator terms, the same 10 GPM over 100 ft takes 3/4 in Type L copper at 8 fps but 1-1/4 in PEX at 5 fps. Bore size and the velocity limit, not the nominal label, decide the plumbing pipe size.
| Material (C factor, limit) | Size for 10 GPM | Velocity | Friction over 150 ft |
|---|---|---|---|
| Copper Type L (140, 8 fps) | 3/4 in | 6.63 fps | 16.76 psi |
| Copper Type M (140, 8 fps) | 3/4 in | 6.21 fps | 14.30 psi |
| Galvanized steel (120, 8 fps) | 3/4 in | 6.02 fps | 17.61 psi |
| CPVC SDR 11 (150, 5 fps) | 1 in | 4.82 fps | 6.78 psi |
| PVC Schedule 40 (150, 5 fps) | 1 in | 3.71 fps | 3.60 psi |
| PEX SDR 9 (150, 5 fps) | 1-1/4 in | 3.57 fps | 3.28 psi |
The velocity limit is a design choice worth checking with the maker. The FlowGuard Gold CPVC installation guide recommends 4 to 8 fps and a C value of 150, and at 8 fps 3/4 in CPVC carries exactly 10 GPM.
Schedule 40 PVC is a cold-water pipe and is not made for hot supply. Hot lines go in CPVC, PEX or copper, where the lower hot-water limit often adds a size, as 10 GPM in copper at 5 fps needs 1 in.
A larger water pipe size calculator result also means more standing water to purge from the line before hot water reaches the tap.
Fifty feet of 3/4 in copper holds 1.26 gal, which takes about 30 seconds to clear at a 2.5 GPM shower, and the Pipe Volume Calculator covers other lengths.
Liters per Minute, m/s and Millimeter Bores
For a water pipe size calculator in mm, a 30 L/min PEX line at 1.5 m/s or less needs 1 in pipe with a 22.2 mm bore, flowing at 1.29 m/s. A 40 L/min copper line at 2.44 m/s or less fits 3/4 in Type L with a 19.9 mm bore, at 2.14 m/s.
Metric limits match the imperial ones, since 8 fps is 2.44 m/s and 5 fps is 1.52 m/s. Water pipe size calculator sizing in mm works from the bore, so the right commercial size is the first one whose inside diameter meets that minimum.
Flow in L/min converts at 3.785 L per US gallon. The Liters per Minute Calculator and Gallons Per Minute Calculator (GPM) measure a real fixture flow from a bucket test.
Good Pipe Size Decisions in Practice
The answer below reuses the water pipe size calculator example of a 100 ft copper run and pressure budget from the friction section, unless it names another material or length.
What is a good pipe size?
A good pipe size is the smallest one that keeps velocity under the limit and still leaves the fixture its required pressure. For 10 GPM in Type L copper over 100 ft, 3/4 in does both, with 6.63 fps and 38.9 psi left at the fixture.
Going up a size buys pressure and quiet at the cost of pipe and waiting time. One inch copper at the same flow runs 3.89 fps and loses 4.58 psi, but holds 4.29 gal per 100 ft against 2.51 gal for 3/4 in.