Generator size calculator for running and starting watts by appliance or total wattage or amps, with the 80% rule, kVA at 0.80 PF, amps per phase and a check of your own generator.
Set how many of each appliance you will run at the same time to size the generator.
Home Essentials
550 W running · +1,350 W to start
60 W running · no start surge
75 W running · no start surge
25 W running · no start surge
1,140 W running · +2,850 W to start
1,200 W running · +3,000 W to start
575 W running · +1,440 W to start
Heating & Cooling
700 W running · +1,400 W to start
800 W running · +2,350 W to start
3,800 W running · +4,950 W to start
6,000 W running · +6,700 W to start
1,000 W running · +2,100 W to start
4,700 W running · +4,500 W to start
1,500 W running · no start surge
Kitchen & Laundry
625 W running · no start surge
1,000 W running · no start surge
1,300 W running · no start surge
3,800 W running · no start surge
Tools & Workshop
300 W running · +780 W to start
1,400 W running · +3,600 W to start
1,800 W running · +2,000 W to start
Your Own Appliances
Your Generator & Power Factor
Load vs Generator Diagram
Wattage Chart by Appliance
| Appliance | Qty | Running | Added Start | Running Total |
|---|---|---|---|---|
| Refrigerator / Freezer | 1 | 550 W | +1,350 W | 550 W |
| Light Bulb, 60 W | 6 | 60 W | 0 W | 360 W |
| LCD TV, 32 in | 1 | 75 W | 0 W | 75 W |
| Phone Charger | 2 | 25 W | 0 W | 50 W |
| Sump Pump, 1/2 hp | 1 | 1,200 W | +3,000 W | 1,200 W |
| Furnace Fan, 1/2 hp | 1 | 800 W | +2,350 W | 800 W |
| Microwave, 1,000 W | 1 | 1,000 W | 0 W | 1,000 W |
| Total | - | - | +3,000 W | 4,035 W |
Step-by-Step Math
Running and Starting Watts in a Generator Size Calculator
A common outage list runs at 4,035 W: a fridge, six 60 W bulbs, a TV, two phone chargers, a 1/2 hp sump pump, a 1/2 hp furnace fan and a 1,000 W microwave. It needs a 5,044 W running rating and 7,035 W of starting capacity.
Two separate checks set every generator size calculator result. The first divides the running load by the continuous load limit, 80% by default.
Prated is the generator's running rating in watts, ΣWrun is the running watts of everything on at once and L is the continuous load limit as a decimal. With 4,035 W and L = 0.80, the rating comes to 5,044 W.
Pstart is the peak the generator must deliver, and Wadd,max is the largest single added starting load. The sump pump adds 3,000 W, so the peak is 4,035 + 3,000 = 7,035 W.
Only the largest surge counts in a generator size calculator total, because motors start one at a time. The A-iPower generator manual's wattage worksheet uses the same rule, adding just the highest additional starting watts to total running watts.
A popular shortcut adds running and surge watts, then 20% more, and lands at 8,442 W. That pays for 3,398 W of running capacity the list never uses, when the two checks need only 5,044 W running and a 7,035 W peak.
Checked against a real machine, the same generator size calculator list sits at 53.8% load on a 7,500 W running, 9,375 W peak portable. It keeps 2,340 W of starting headroom after the sump pump kicks in.
A generator sizing calculator Excel sheet needs two cells for the same answer. Put =SUM(B2:B20)/0.8 for the running rating and =SUM(B2:B20)+MAX(C2:C20) for the peak, with running watts in column B and added starting watts in column C.
Energy is a different number. The same 4,035 W running for 24 hours uses 96.8 kWh, so a generator size calculator kWh figure sets fuel and run time, while the watt figures above set the generator itself.
Appliance Wattage Chart for Home Generator Sizing
A 2-ton, 24,000 BTU central AC needs 8,750 W to start, more than four times the 1,900 W a fridge needs at the same moment on a generator size calculator list.
Each row lists running watts, the extra watts a motor adds while starting, and the total at that moment, taken from Briggs & Stratton's generator wattage guide.
| Appliance | Running watts | Added starting watts | Total while starting |
|---|---|---|---|
| Refrigerator / freezer | 550 | 1,350 | 1,900 |
| Light bulb, 60 W | 60 | 0 | 60 |
| LCD TV, 32 in | 75 | 0 | 75 |
| Phone charger | 25 | 0 | 25 |
| Sump pump, 1/3 hp | 1,140 | 2,850 | 3,990 |
| Sump pump, 1/2 hp | 1,200 | 3,000 | 4,200 |
| Well pump, 1/3 hp | 575 | 1,440 | 2,015 |
| Furnace fan, 1/3 hp | 700 | 1,400 | 2,100 |
| Furnace fan, 1/2 hp | 800 | 2,350 | 3,150 |
| Central AC, 24,000 BTU | 3,800 | 4,950 | 8,750 |
| Central AC, 40,000 BTU | 6,000 | 6,700 | 12,700 |
| Window AC, 10,000 BTU | 1,000 | 2,100 | 3,100 |
| Heat pump | 4,700 | 4,500 | 9,200 |
| Space heater | 1,500 | 0 | 1,500 |
| Microwave, 625 W | 625 | 0 | 625 |
| Microwave, 1,000 W | 1,000 | 0 | 1,000 |
| Coffee maker | 1,300 | 0 | 1,300 |
| Electric water heater | 3,800 | 0 | 3,800 |
| Air compressor, 1/3 hp | 300 | 780 | 1,080 |
| Air compressor, 1 hp | 1,400 | 3,600 | 5,000 |
| Circular saw, 7 1/4 in | 1,800 | 2,000 | 3,800 |
Resistive loads such as heaters, kettles and coffee makers add no starting watts to a generator size calculator total. Motors and compressors do, which is why a 1 hp air compressor at 1,400 W running still needs 5,000 W for the first few seconds.
The heat pump row is unusual, with added starting watts below running watts. Its 9,200 W peak still makes it the item that sets the peak on most whole-house lists, ahead of a 2-ton central AC.
Watch for a 12,000 BTU window AC printed at 3,250 running watts in some generator manuals. At the ENERGY STAR room AC criteria CEER of 12.8 for that size, it runs near 12,000 ÷ 12.8 = 940 W.
The printed 3,250 W would inflate a generator size calculator result by about 2,300 W for that one window unit, enough to push a buyer up a whole generator size.
Nameplate figures beat any chart. Running watts are volts × amps from the label, as DTE Energy's generator worksheet notes, and a measured nameplate figure should replace any row that differs.
For a generator size calculator for home use, the chart doubles as the what-size-generator-do-I-need-for-my-house chart. Take the rows that run together, sum the running column, then add the single largest number from the added starting column.
kVA Ratings Converted to Usable Kilowatts
A 20 kVA generator delivers 16 kW at 0.8 power factor and should carry about 12.8 kW continuously under the 80% rule. Diesel sets are usually rated in kVA, so this conversion comes before any generator size calculator comparison.
PkW is usable real power, SkVA is the nameplate apparent power and PF is the power factor the rating assumes, 0.8 for most kVA-rated sets. Portable generators rated in watts skip this step.
| Rating | kW at 0.8 PF | 80% continuous | Amps, 230 V | Amps, 240 V | Amps, 400 V 3-phase | Amps, 480 V 3-phase |
|---|---|---|---|---|---|---|
| 2.5 kVA | 2.0 kW | 1.6 kW | 10.9 A | 10.4 A | 3.6 A | 3.0 A |
| 3.5 kVA | 2.8 kW | 2.24 kW | 15.2 A | 14.6 A | 5.1 A | 4.2 A |
| 4.5 kVA | 3.6 kW | 2.88 kW | 19.6 A | 18.8 A | 6.5 A | 5.4 A |
| 5 kVA | 4.0 kW | 3.2 kW | 21.7 A | 20.8 A | 7.2 A | 6.0 A |
| 5.5 kVA | 4.4 kW | 3.52 kW | 23.9 A | 22.9 A | 7.9 A | 6.6 A |
| 7.5 kVA | 6.0 kW | 4.8 kW | 32.6 A | 31.2 A | 10.8 A | 9.0 A |
| 20 kVA | 16 kW | 12.8 kW | 87.0 A | 83.3 A | 28.9 A | 24.1 A |
| 25 kVA | 20 kW | 16 kW | 109 A | 104 A | 36.1 A | 30.1 A |
| 30 kVA | 24 kW | 19.2 kW | 130 A | 125 A | 43.3 A | 36.1 A |
| 100 kVA | 80 kW | 64 kW | 435 A | 417 A | 144 A | 120 A |
| 120 kVA | 96 kW | 76.8 kW | 522 A | 500 A | 173 A | 144 A |
| 200 kVA | 160 kW | 128 kW | 870 A | 833 A | 289 A | 241 A |
| 250 kVA | 200 kW | 160 kW | 1,087 A | 1,042 A | 361 A | 301 A |
| 300 kVA | 240 kW | 192 kW | 1,304 A | 1,250 A | 433 A | 361 A |
| 1,000 kVA | 800 kW | 640 kW | 4,348 A | 4,167 A | 1,443 A | 1,203 A |
The same math runs backwards for kW-rated sets. A 100 kW generator is a 125 kVA machine at 0.8 power factor, and a 1,000 W portable should carry about 800 W for hours at a time.
Amps show why large sets run three-phase. A 250 kVA set would push 1,087 A on a 230 V single-phase supply, but only 361 A per phase at 400 V, which keeps cables and breakers to a practical size.
Three-Phase Generator Load From Amps
A 40 A, 480 V three-phase load at 0.8 power factor draws 26.6 kW running. With the 80% rule it needs a 33.3 kW running rating, or a 41.6 kVA set.
W is running watts, I is measured line current in amps, V is line-to-line voltage and PF is power factor. Single-phase loads use the same formula without the √3, so one generator size calculator method covers both.
| 40 A measured on | Running watts | Rating at 80% | Generator kVA |
|---|---|---|---|
| 120 V single-phase | 3,840 W | 4,800 W | 6.0 kVA |
| 230 V single-phase | 7,360 W | 9,200 W | 11.5 kVA |
| 240 V single-phase | 7,680 W | 9,600 W | 12.0 kVA |
| 208 V three-phase | 11,529 W | 14,411 W | 18.0 kVA |
| 240 V three-phase | 13,302 W | 16,628 W | 20.8 kVA |
| 400 V three-phase | 22,170 W | 27,713 W | 34.6 kVA |
| 415 V three-phase | 23,002 W | 28,752 W | 35.9 kVA |
| 480 V three-phase | 26,604 W | 33,255 W | 41.6 kVA |
The same 40 A asks for very different generators, which is why a generator size calculator by amps always needs the voltage and phase. At 480 V three-phase, the load is almost seven times the 120 V figure.
The same two checks apply to a commercial generator size calculator estimate. A 480 V shop running 60 kW, with one motor adding 25 kW to start, needs a 75 kW running rating, 93.75 kVA, and an 85 kW peak, drawing 112.8 A per phase at full rating.
For a generator size calculator for RV use, a 30 A, 120 V cord tops out near 2,880 W at 0.8 power factor. A 3,600 W running rating covers that cord under the 80% rule, before any rooftop AC starting surge is added.
Split-phase homes need one more generator size calculator check. If all 4,035 W of the outage list sat on one 120 V leg, that leg would carry 42.0 A, double the 21.0 A figure worked out at 240 V, so spread 120 V loads across both legs.
AC, Fridge and House-Size Answers
Most generator size calculator questions come down to the AC and how the starting surge stacks up. Each answer uses the chart above and 0.8 power factor for kVA-rated sets, with the starting rating equal to the running rating unless stated.
How do I calculate what size generator I need?
Add the running watts of everything on at once, divide by 0.8, then check that the generator's peak covers running watts plus the largest single starting surge. Both numbers must fit.
A workshop generator size calculator list with a 1 hp air compressor, a 7 1/4 in circular saw and four 60 W lights runs at 3,440 W. It needs a 4,300 W running rating, or 5.38 kVA, and a 7,040 W peak because the compressor adds 3,600 W to start.
How big is a 1000 kVA generator?
A 1,000 kVA generator delivers 800 kW at 0.8 power factor and should carry about 640 kW continuously. At 480 V three-phase, its full-load current is 1,203 A per phase.
The kVA table above runs the same numbers for 2.5 to 300 kVA sets. Every kVA rating scales the same way, so a 200 kVA set gives 160 kW and a 300 kVA set gives 240 kW.
Can a 4.5 kVA generator carry 1.5 hp AC?
It can run one, but starting is the limit. A 4.5 kVA set gives 3,600 W, or 2,880 W continuous. A 1.5 ton (18,000 BTU) AC at ENERGY STAR's CEER of 12.6 runs near 1,430 W, leaving 2,170 W for its starting surge.
A 5 kVA set leaves 2,570 W for the same surge with 3,200 W continuous, which makes it the safer choice for a fixed-speed compressor. A 1.5 hp motor is about 1,120 W of shaft power, or roughly 1.4 kVA running at 0.8 power factor.
Can a 3.5 kVA generator carry AC and fridge?
Running both is fine, but starting them together is not. A 10,000 BTU window AC and a fridge run at 1,550 W, and starting the AC with the fridge on needs 3,650 W, against 2,800 W from a 3.5 kVA set.
A 4.5 kVA set misses by only 50 W. Start the AC first, at 3,100 W, then the fridge, at 2,900 W with the AC running, and both stay under 3,600 W. A 5 kVA set starts them in any order with 350 W to spare.
How many AC can a 25 kVA generator have?
A 25 kVA set runs 16 window ACs of 10,000 BTU, or 3 central ACs of 24,000 BTU, started one at a time. The central AC count is set by its 4,950 W starting surge, not by running watts.
| Generator | Usable kW | 10,000 BTU window ACs | 24,000 BTU central ACs |
|---|---|---|---|
| 5 kVA | 4.0 | 1 | 0 |
| 5.5 kVA | 4.4 | 2 | 0 |
| 7.5 kVA | 6.0 | 3 | 0 |
| 25 kVA | 20 | 16 | 3 |
| 100 kVA | 80 | 64 | 16 |
Three ACs on a 5 kW generator show the starting trap. Three 10,000 BTU units run at 3,000 W, within the 4,000 W continuous limit, but starting the third with two running needs 5,100 W, 100 W more than the set gives.
What size generator for a 1200 sq ft house?
A 1,200 sq ft (111 m²) home with a 2-ton central AC needs about a 10 kW generator. The outage list plus a 24,000 BTU AC runs at 7,835 W, giving a 9,794 W running rating and a 12,785 W starting peak.
Floor area never enters the generator size calculator math; the loads do. Drop the central AC and the same house needs a 5,044 W running rating, while adding an electric water heater would push the running load past 11,600 W.
What is the 80% rule for generators?
In generator size calculator terms, the 80% rule keeps the continuous load at or below 80% of the generator's running rating. A 7,500 W generator should carry about 6,000 W for hours at a time, leaving 1,500 W for motor starts and heat.
Running above 80% works for a short burst, but long outages at full load shorten engine life. The 4,035 W outage list sits at 53.8% on that 7,500 W set, well inside the rule.