Generator Size Calculator

Updated

Generator size calculator for running and starting watts by appliance or total wattage or amps, with the 80% rule, kVA at 0.80 PF, amps per phase and a check of your own generator.

Generator Load

Set how many of each appliance you will run at the same time to size the generator.

% of rating
Home Essentials--
qty

550 W running · +1,350 W to start

qty

60 W running · no start surge

qty

75 W running · no start surge

qty

25 W running · no start surge

qty

1,140 W running · +2,850 W to start

qty

1,200 W running · +3,000 W to start

qty

575 W running · +1,440 W to start

Heating & Cooling--
qty

700 W running · +1,400 W to start

qty

800 W running · +2,350 W to start

qty

3,800 W running · +4,950 W to start

qty

6,000 W running · +6,700 W to start

qty

1,000 W running · +2,100 W to start

qty

4,700 W running · +4,500 W to start

qty

1,500 W running · no start surge

Kitchen & Laundry--
qty

625 W running · no start surge

qty

1,000 W running · no start surge

qty

1,300 W running · no start surge

qty

3,800 W running · no start surge

Tools & Workshop--
qty

300 W running · +780 W to start

qty

1,400 W running · +3,600 W to start

qty

1,800 W running · +2,000 W to start

Your Own Appliances--
W
W
W
W
Your Generator & Power Factor--
PF
h
5,044 W Generator Size
Running watts, with at least 7,035 W starting watts to start the Sump Pump, 1/2 hp
4,035 W Running Load
Biggest Starting Surge+3,000 W
Energy per 24 h96.8 kWh
Everything running at once, the single biggest motor surge, and the energy used.
6.30 kVA Generator at 0.8 PF
Full-Load Current, 240 V26.3 A
Starting Peak in kVA8.79 kVA
Apparent power rating to match, and the current the generator supplies at full load.
21.0 A Running Current at 240 V
All on One 120 V Leg42.0 A
Starting Current36.6 A
Amps your loads draw while running and starting, for breaker and cord sizing.
53.8% Load on Your Generator
Starting Headroom+2,340 W
Max Continuous Load6,000 W
Your generator checked against the running load and the starting peak below.
Load vs Generator Diagram53.8% of your generator
Running load4,035 WStarting peak7,035 WSize at 80% rule5,044 WYour generator, running7,500 WYour generator, peak9,375 W
Wattage Chart by Appliance7 items
ApplianceQtyRunningAdded StartRunning Total
Refrigerator / Freezer1550 W+1,350 W550 W
Light Bulb, 60 W660 W0 W360 W
LCD TV, 32 in175 W0 W75 W
Phone Charger225 W0 W50 W
Sump Pump, 1/2 hp11,200 W+3,000 W1,200 W
Furnace Fan, 1/2 hp1800 W+2,350 W800 W
Microwave, 1,000 W11,000 W0 W1,000 W
Total--+3,000 W4,035 W
Step-by-Step Math7 steps
1. Total Running Watts550 + 6 × 60 + 75 + 2 × 25 + 1,200 + 800 + 1,000 = 4,035 W
2. Largest Added StartSump Pump, 1/2 hp adds 3,000 W while starting
3. Starting Watts4,035 W + 3,000 W = 7,035 W
4. 80% Rule4,035 W ÷ 0.8 = 5,044 W running rating
5. Generator kVA5,044 W ÷ 0.8 PF = 6.30 kVA
6. Full-Load Current6.30 kVA ÷ (240 V) = 26.3 A
7. Your Generator4,035 W ÷ 7,500 W = 53.8% running; peak 9,375 W vs 7,035 W needed
Your Generator Covers This Load
The load uses 53.8% of the 7,500 W rating, and the 9,375 W peak covers the 7,035 W needed to start the Sump Pump, 1/2 hp.

Running and Starting Watts in a Generator Size Calculator

A common outage list runs at 4,035 W: a fridge, six 60 W bulbs, a TV, two phone chargers, a 1/2 hp sump pump, a 1/2 hp furnace fan and a 1,000 W microwave. It needs a 5,044 W running rating and 7,035 W of starting capacity.

Two separate checks set every generator size calculator result. The first divides the running load by the continuous load limit, 80% by default.

Prated is the generator's running rating in watts, ΣWrun is the running watts of everything on at once and L is the continuous load limit as a decimal. With 4,035 W and L = 0.80, the rating comes to 5,044 W.

Pstart is the peak the generator must deliver, and Wadd,max is the largest single added starting load. The sump pump adds 3,000 W, so the peak is 4,035 + 3,000 = 7,035 W.

Only the largest surge counts in a generator size calculator total, because motors start one at a time. The A-iPower generator manual's wattage worksheet uses the same rule, adding just the highest additional starting watts to total running watts.

A popular shortcut adds running and surge watts, then 20% more, and lands at 8,442 W. That pays for 3,398 W of running capacity the list never uses, when the two checks need only 5,044 W running and a 7,035 W peak.

Checked against a real machine, the same generator size calculator list sits at 53.8% load on a 7,500 W running, 9,375 W peak portable. It keeps 2,340 W of starting headroom after the sump pump kicks in.

A generator sizing calculator Excel sheet needs two cells for the same answer. Put =SUM(B2:B20)/0.8 for the running rating and =SUM(B2:B20)+MAX(C2:C20) for the peak, with running watts in column B and added starting watts in column C.

Energy is a different number. The same 4,035 W running for 24 hours uses 96.8 kWh, so a generator size calculator kWh figure sets fuel and run time, while the watt figures above set the generator itself.

Appliance Wattage Chart for Home Generator Sizing

A 2-ton, 24,000 BTU central AC needs 8,750 W to start, more than four times the 1,900 W a fridge needs at the same moment on a generator size calculator list.

Each row lists running watts, the extra watts a motor adds while starting, and the total at that moment, taken from Briggs & Stratton's generator wattage guide.

ApplianceRunning wattsAdded starting wattsTotal while starting
Refrigerator / freezer5501,3501,900
Light bulb, 60 W60060
LCD TV, 32 in75075
Phone charger25025
Sump pump, 1/3 hp1,1402,8503,990
Sump pump, 1/2 hp1,2003,0004,200
Well pump, 1/3 hp5751,4402,015
Furnace fan, 1/3 hp7001,4002,100
Furnace fan, 1/2 hp8002,3503,150
Central AC, 24,000 BTU3,8004,9508,750
Central AC, 40,000 BTU6,0006,70012,700
Window AC, 10,000 BTU1,0002,1003,100
Heat pump4,7004,5009,200
Space heater1,50001,500
Microwave, 625 W6250625
Microwave, 1,000 W1,00001,000
Coffee maker1,30001,300
Electric water heater3,80003,800
Air compressor, 1/3 hp3007801,080
Air compressor, 1 hp1,4003,6005,000
Circular saw, 7 1/4 in1,8002,0003,800

Resistive loads such as heaters, kettles and coffee makers add no starting watts to a generator size calculator total. Motors and compressors do, which is why a 1 hp air compressor at 1,400 W running still needs 5,000 W for the first few seconds.

The heat pump row is unusual, with added starting watts below running watts. Its 9,200 W peak still makes it the item that sets the peak on most whole-house lists, ahead of a 2-ton central AC.

Watch for a 12,000 BTU window AC printed at 3,250 running watts in some generator manuals. At the ENERGY STAR room AC criteria CEER of 12.8 for that size, it runs near 12,000 ÷ 12.8 = 940 W.

The printed 3,250 W would inflate a generator size calculator result by about 2,300 W for that one window unit, enough to push a buyer up a whole generator size.

Nameplate figures beat any chart. Running watts are volts × amps from the label, as DTE Energy's generator worksheet notes, and a measured nameplate figure should replace any row that differs.

For a generator size calculator for home use, the chart doubles as the what-size-generator-do-I-need-for-my-house chart. Take the rows that run together, sum the running column, then add the single largest number from the added starting column.

kVA Ratings Converted to Usable Kilowatts

A 20 kVA generator delivers 16 kW at 0.8 power factor and should carry about 12.8 kW continuously under the 80% rule. Diesel sets are usually rated in kVA, so this conversion comes before any generator size calculator comparison.

PkW is usable real power, SkVA is the nameplate apparent power and PF is the power factor the rating assumes, 0.8 for most kVA-rated sets. Portable generators rated in watts skip this step.

RatingkW at 0.8 PF80% continuousAmps, 230 VAmps, 240 VAmps, 400 V 3-phaseAmps, 480 V 3-phase
2.5 kVA2.0 kW1.6 kW10.9 A10.4 A3.6 A3.0 A
3.5 kVA2.8 kW2.24 kW15.2 A14.6 A5.1 A4.2 A
4.5 kVA3.6 kW2.88 kW19.6 A18.8 A6.5 A5.4 A
5 kVA4.0 kW3.2 kW21.7 A20.8 A7.2 A6.0 A
5.5 kVA4.4 kW3.52 kW23.9 A22.9 A7.9 A6.6 A
7.5 kVA6.0 kW4.8 kW32.6 A31.2 A10.8 A9.0 A
20 kVA16 kW12.8 kW87.0 A83.3 A28.9 A24.1 A
25 kVA20 kW16 kW109 A104 A36.1 A30.1 A
30 kVA24 kW19.2 kW130 A125 A43.3 A36.1 A
100 kVA80 kW64 kW435 A417 A144 A120 A
120 kVA96 kW76.8 kW522 A500 A173 A144 A
200 kVA160 kW128 kW870 A833 A289 A241 A
250 kVA200 kW160 kW1,087 A1,042 A361 A301 A
300 kVA240 kW192 kW1,304 A1,250 A433 A361 A
1,000 kVA800 kW640 kW4,348 A4,167 A1,443 A1,203 A

The same math runs backwards for kW-rated sets. A 100 kW generator is a 125 kVA machine at 0.8 power factor, and a 1,000 W portable should carry about 800 W for hours at a time.

Amps show why large sets run three-phase. A 250 kVA set would push 1,087 A on a 230 V single-phase supply, but only 361 A per phase at 400 V, which keeps cables and breakers to a practical size.

Three-Phase Generator Load From Amps

A 40 A, 480 V three-phase load at 0.8 power factor draws 26.6 kW running. With the 80% rule it needs a 33.3 kW running rating, or a 41.6 kVA set.

W is running watts, I is measured line current in amps, V is line-to-line voltage and PF is power factor. Single-phase loads use the same formula without the √3, so one generator size calculator method covers both.

40 A measured onRunning wattsRating at 80%Generator kVA
120 V single-phase3,840 W4,800 W6.0 kVA
230 V single-phase7,360 W9,200 W11.5 kVA
240 V single-phase7,680 W9,600 W12.0 kVA
208 V three-phase11,529 W14,411 W18.0 kVA
240 V three-phase13,302 W16,628 W20.8 kVA
400 V three-phase22,170 W27,713 W34.6 kVA
415 V three-phase23,002 W28,752 W35.9 kVA
480 V three-phase26,604 W33,255 W41.6 kVA

The same 40 A asks for very different generators, which is why a generator size calculator by amps always needs the voltage and phase. At 480 V three-phase, the load is almost seven times the 120 V figure.

The same two checks apply to a commercial generator size calculator estimate. A 480 V shop running 60 kW, with one motor adding 25 kW to start, needs a 75 kW running rating, 93.75 kVA, and an 85 kW peak, drawing 112.8 A per phase at full rating.

For a generator size calculator for RV use, a 30 A, 120 V cord tops out near 2,880 W at 0.8 power factor. A 3,600 W running rating covers that cord under the 80% rule, before any rooftop AC starting surge is added.

Split-phase homes need one more generator size calculator check. If all 4,035 W of the outage list sat on one 120 V leg, that leg would carry 42.0 A, double the 21.0 A figure worked out at 240 V, so spread 120 V loads across both legs.

AC, Fridge and House-Size Answers

Most generator size calculator questions come down to the AC and how the starting surge stacks up. Each answer uses the chart above and 0.8 power factor for kVA-rated sets, with the starting rating equal to the running rating unless stated.

How do I calculate what size generator I need?

Add the running watts of everything on at once, divide by 0.8, then check that the generator's peak covers running watts plus the largest single starting surge. Both numbers must fit.

A workshop generator size calculator list with a 1 hp air compressor, a 7 1/4 in circular saw and four 60 W lights runs at 3,440 W. It needs a 4,300 W running rating, or 5.38 kVA, and a 7,040 W peak because the compressor adds 3,600 W to start.

How big is a 1000 kVA generator?

A 1,000 kVA generator delivers 800 kW at 0.8 power factor and should carry about 640 kW continuously. At 480 V three-phase, its full-load current is 1,203 A per phase.

The kVA table above runs the same numbers for 2.5 to 300 kVA sets. Every kVA rating scales the same way, so a 200 kVA set gives 160 kW and a 300 kVA set gives 240 kW.

Can a 4.5 kVA generator carry 1.5 hp AC?

It can run one, but starting is the limit. A 4.5 kVA set gives 3,600 W, or 2,880 W continuous. A 1.5 ton (18,000 BTU) AC at ENERGY STAR's CEER of 12.6 runs near 1,430 W, leaving 2,170 W for its starting surge.

A 5 kVA set leaves 2,570 W for the same surge with 3,200 W continuous, which makes it the safer choice for a fixed-speed compressor. A 1.5 hp motor is about 1,120 W of shaft power, or roughly 1.4 kVA running at 0.8 power factor.

Can a 3.5 kVA generator carry AC and fridge?

Running both is fine, but starting them together is not. A 10,000 BTU window AC and a fridge run at 1,550 W, and starting the AC with the fridge on needs 3,650 W, against 2,800 W from a 3.5 kVA set.

A 4.5 kVA set misses by only 50 W. Start the AC first, at 3,100 W, then the fridge, at 2,900 W with the AC running, and both stay under 3,600 W. A 5 kVA set starts them in any order with 350 W to spare.

How many AC can a 25 kVA generator have?

A 25 kVA set runs 16 window ACs of 10,000 BTU, or 3 central ACs of 24,000 BTU, started one at a time. The central AC count is set by its 4,950 W starting surge, not by running watts.

GeneratorUsable kW10,000 BTU window ACs24,000 BTU central ACs
5 kVA4.010
5.5 kVA4.420
7.5 kVA6.030
25 kVA20163
100 kVA806416

Three ACs on a 5 kW generator show the starting trap. Three 10,000 BTU units run at 3,000 W, within the 4,000 W continuous limit, but starting the third with two running needs 5,100 W, 100 W more than the set gives.

What size generator for a 1200 sq ft house?

A 1,200 sq ft (111 m²) home with a 2-ton central AC needs about a 10 kW generator. The outage list plus a 24,000 BTU AC runs at 7,835 W, giving a 9,794 W running rating and a 12,785 W starting peak.

Floor area never enters the generator size calculator math; the loads do. Drop the central AC and the same house needs a 5,044 W running rating, while adding an electric water heater would push the running load past 11,600 W.

What is the 80% rule for generators?

In generator size calculator terms, the 80% rule keeps the continuous load at or below 80% of the generator's running rating. A 7,500 W generator should carry about 6,000 W for hours at a time, leaving 1,500 W for motor starts and heat.

Running above 80% works for a short burst, but long outages at full load shorten engine life. The 4,035 W outage list sits at 53.8% on that 7,500 W set, well inside the rule.