Motor capacitor size calculator for start and run capacitor µF by motor hp or by kW at 230 V, µF from measured amps and volts, run capacitor tests against labels and stored energy.
Enter the motor horsepower to get start and run capacitor sizes for a 230 V single-phase motor.
Capacitor Size Diagram
Motor Capacitor Size Chart, 230 V
| Motor hp | Motor kW | Start Capacitor | Run Capacitor |
|---|---|---|---|
| 1/4 hp | 0.19 kW | 75-100 µF | 4-6 µF |
| 1/3 hp | 0.25 kW | 100-130 µF | 5-7.5 µF |
| 1/2 hp | 0.37 kW | 130-170 µF | 7.5-10 µF |
| 3/4 hp | 0.56 kW | 170-220 µF | 10-15 µF |
| 1 hp | 0.75 kW | 200-260 µF | 15-20 µF |
| 1.5 hp | 1.12 kW | 260-340 µF | 20-25 µF |
| 2 hp | 1.49 kW | 340-400 µF | 25-30 µF |
| 3 hp | 2.24 kW | 400-480 µF | 30-40 µF |
| 5 hp | 3.73 kW | 480-580 µF | 35-50 µF |
| 7.5 hp | 5.59 kW | 580-710 µF | 45-60 µF |
| 10 hp | 7.46 kW | 710-850 µF | 50-70 µF |
Dual Run Capacitors for AC Units (Compressor/Fan)
| Dual Run Size | Typical Use |
|---|---|
| 25/5 µF | Small fan motors, 1/4 hp compressors |
| 30/5 µF | 1/3 hp compressors, condenser fans |
| 35/5 µF | 1.5 to 2 ton AC |
| 40/5 µF | 2 to 2.5 ton AC |
| 45/5 µF | 2.5 to 3 ton AC |
| 50/5 µF | 3 to 3.5 ton AC |
| 55/5 µF | 3.5 to 4 ton AC |
| 60/5 µF | 4 to 5 ton AC |
Step-by-Step Math
Start and Run µF From a Motor Capacitor Size Calculator
A 1 hp, 230 V single-phase motor typically takes a 200-260 µF start capacitor and a 15-20 µF run capacitor. Larger motors climb in steps, reaching 710-850 µF start and 50-70 µF run at 10 hp.
| Motor | kW | Start capacitor | Run capacitor | Start current, 60 Hz | Start current, 50 Hz |
|---|---|---|---|---|---|
| 1/4 hp | 0.19 | 75-100 µF | 4-6 µF | 6.5-8.7 A | 5.4-7.2 A |
| 1/3 hp | 0.25 | 100-130 µF | 5-7.5 µF | 8.7-11.3 A | 7.2-9.4 A |
| 1/2 hp | 0.37 | 130-170 µF | 7.5-10 µF | 11.3-14.7 A | 9.4-12.3 A |
| 3/4 hp | 0.56 | 170-220 µF | 10-15 µF | 14.7-19.1 A | 12.3-15.9 A |
| 1 hp | 0.75 | 200-260 µF | 15-20 µF | 17.3-22.5 A | 14.5-18.8 A |
| 1.5 hp | 1.12 | 260-340 µF | 20-25 µF | 22.5-29.5 A | 18.8-24.6 A |
| 2 hp | 1.49 | 340-400 µF | 25-30 µF | 29.5-34.7 A | 24.6-28.9 A |
| 3 hp | 2.24 | 400-480 µF | 30-40 µF | 34.7-41.6 A | 28.9-34.7 A |
| 5 hp | 3.73 | 480-580 µF | 35-50 µF | 41.6-50.3 A | 34.7-41.9 A |
| 7.5 hp | 5.59 | 580-710 µF | 45-60 µF | 50.3-61.6 A | 41.9-51.3 A |
| 10 hp | 7.46 | 710-850 µF | 50-70 µF | 61.6-73.7 A | 51.3-61.4 A |
These are typical 230 V ranges for capacitor-start motors, not a design rule. The capacitor already in the motor, or the nameplate, beats any motor capacitor size calculator chart, because the right value depends on how the start winding was wound.
Metric motors map onto the nearest motor capacitor size calculator row by horsepower. A 0.75 kW motor is 1.006 hp, a 1.1 kW motor is 1.475 hp and a 2.2 kW motor is 2.95 hp, so they take the 1 hp, 1.5 hp and 3 hp rows.
The current columns in a motor capacitor size calculator result matter for wiring. The 1 hp start range pulls 17.3-22.5 A at 230 V and 60 Hz, and a sixth less on a 50 Hz supply.
Voltage rating follows the capacitor type. Start capacitors for 230 V motors are typically rated 220-330 V, with Franklin's pump boxes at 220 V, while run capacitors are rated 370 V or 440 V.
A 440 V run capacitor can replace a 370 V one of the same µF, but never the reverse, because the voltage across a run capacitor on a working motor often sits above the supply voltage.
Microfarads From Amps and Volts
A run capacitor carrying 3.75 A at 230 V and 60 Hz measures 43.25 µF. That motor capacitor size calculator reading comes from the running motor, with no need to pull the capacitor and bench-test it.
C is capacitance in µF, I is the current in the capacitor lead in amps, f is the supply frequency in Hz and V is the voltage measured across the capacitor terminals, which on a running motor is often above the line voltage.
At 60 Hz the constant 106 ÷ (2π × 60) works out to 2,652, so service techs use µF = 2,652 × A ÷ V. At 50 Hz the constant is 3,183. ACHR News walks through the same test: 4.4 A × 2,652 ÷ 335 V = 34.8 µF.
| Capacitor current | µF at 230 V, 60 Hz | µF at 230 V, 50 Hz |
|---|---|---|
| 0.5 A | 5.77 | 6.92 |
| 1 A | 11.53 | 13.84 |
| 1.5 A | 17.30 | 20.76 |
| 2 A | 23.07 | 27.68 |
| 3 A | 34.60 | 41.52 |
| 5 A | 57.66 | 69.20 |
| 10 A | 115.3 | 138.4 |
| 20 A | 230.7 | 276.8 |
Frequency changes the answer by 20%. Moving a motor from 60 Hz to 50 Hz, a 20 µF run capacitor would need to become 24 µF to carry the same current, which is why a motor capacitor size calculator for 50 Hz work cannot reuse a 60 Hz figure.
Some charts size from startup energy with C = 2E ÷ V², which only finds the capacitor that stores E joules at V volts. At 230 V, 9 J gives 340.3 µF, and the same 9 J at 110 V gives 1,488 µF.
No motor nameplate lists startup energy, so the amps-and-volts method is the sounder motor capacitor size calculator basis whenever the motor can be run and measured safely.
Weak Run Capacitors and the Replace Point
A 45 µF run capacitor reading 43.25 µF is 3.9% low and still good. Replace it once it falls below 42.75 µF, 5% under its label, because a weak run capacitor raises motor current and heat.
| Label | Replace below (5%) | Replace below (6%) |
|---|---|---|
| 5 µF | 4.75 µF | 4.70 µF |
| 7.5 µF | 7.13 µF | 7.05 µF |
| 10 µF | 9.50 µF | 9.40 µF |
| 15 µF | 14.25 µF | 14.10 µF |
| 20 µF | 19.00 µF | 18.80 µF |
| 25 µF | 23.75 µF | 23.50 µF |
| 30 µF | 28.50 µF | 28.20 µF |
| 35 µF | 33.25 µF | 32.90 µF |
| 40 µF | 38.00 µF | 37.60 µF |
| 45 µF | 42.75 µF | 42.30 µF |
| 50 µF | 47.50 µF | 47.00 µF |
The printed tolerance decides which motor capacitor size calculator column applies. ACHR News notes that many run capacitors allow ±6%, so a can marked ±6% is still in spec at 42.3 µF, while a ±5% can of the same label is already due for replacement.
Start capacitors follow a different rule. They are marked as a range, such as 105-126 µF, so a reading anywhere inside that range is good, and the 5% replace point does not apply to them.
A reading well above the label also points to a problem. Check the meter, the clamp position and the voltage across the terminals before trusting any motor capacitor size calculator result that comes out more than 5% high.
Dual Run Capacitor Sizes for AC Compressors
A 3 ton central AC typically uses a 45/5 or 50/5 µF dual run capacitor, the larger number for the compressor and the 5 µF section for the condenser fan. Each step of about half a ton adds 5 µF on the compressor side.
| Dual run size | Typical use |
|---|---|
| 25/5 µF | Small fan motors, 1/4 hp compressors |
| 30/5 µF | 1/3 hp compressors, condenser fans |
| 35/5 µF | 1.5 to 2 ton AC |
| 40/5 µF | 2 to 2.5 ton AC |
| 45/5 µF | 2.5 to 3 ton AC |
| 50/5 µF | 3 to 3.5 ton AC |
| 55/5 µF | 3.5 to 4 ton AC |
| 60/5 µF | 4 to 5 ton AC |
The three terminals are C for common, HERM for the compressor and FAN for the fan motor. Each section gets its own motor capacitor size calculator test, with the clamp on the HERM or FAN wire and the meter across that terminal and C.
A 45/5 µF capacitor carrying 5.4 A on HERM with 335 V across it reads 42.8 µF, right on the 5% replace line. The same can carrying 0.62 A on FAN reads 4.91 µF, only 1.8% low, so one section can fail while the other is fine.
Dual run capacitors are rated 370 V or 440 V, the same as single run capacitors, and the 440 V swap rule applies to them too.
The tonnage column is a starting point for any compressor capacitor size chart or motor capacitor size calculator estimate; the label on the old can or the condenser wiring diagram sets the exact pair.
Pump Control Boxes Break the Chart
A 2 hp, 230 V submersible pump runs on a 105-126 µF start capacitor and a 20 µF run capacitor, not the 340-400 µF and 25-30 µF a general motor capacitor size calculator chart lists. Three-wire pump motors are wound for their own control boxes.
| Submersible motor, 230 V | Start capacitor | Run capacitor | General chart start |
|---|---|---|---|
| 1/3 hp | 43-53 µF, 220 V | None | 100-130 µF |
| 1/2 hp | 59-71 µF, 220 V | None | 130-170 µF |
| 1 hp | 105-126 µF, 220 V | None | 200-260 µF |
| 1-1.5 hp, standard box | 105-126 µF, 220 V | 10 µF, 370 V | 200-340 µF |
| 2 hp, standard box | 105-126 µF, 220 V | 20 µF, 370 V | 340-400 µF |
The pump values come from Franklin Electric's application manual, table 48 for fractional sizes and table 49 for integral sizes. They run at roughly a third to a half of the general motor capacitor size calculator figures.
Fitting a general-chart 340 µF start capacitor in a 2 hp pump box would put about three times the intended capacitance on the start winding. Replace pump capacitors with the part number printed in the control box.
Supply voltage changes the numbers sharply too. Franklin lists a 1/3 hp pump at 159-191 µF on 115 V against 43-53 µF on 230 V, close to four times the capacitance for half the voltage.
Answers for 1 HP, 1.5 HP and Pump Motors
Most motor capacitor size calculator questions come down to the motor's horsepower, supply and type. Each answer below uses 230 V unless it says otherwise, with currents at 60 Hz and 50 Hz where they differ.
How to calculate capacitor size for motor?
Start from the old capacitor's label or the motor nameplate. With neither, use a typical chart by horsepower, or measure the running current in the capacitor lead and the voltage across it, then divide by 2πfV.
For a measured 1.5 A at 230 V, that gives 17.30 µF at 60 Hz or 20.76 µF at 50 Hz. Round any motor capacitor size calculator result to the nearest standard value, such as 17.5 µF or 20 µF, at the same or a higher voltage rating.
What size capacitor for 1.5 HP motor?
A 1.5 hp, 230 V capacitor-start motor typically takes a 260-340 µF start capacitor and a 20-25 µF run capacitor. A 1.1 kW motor, at 1.475 hp, falls in the same motor capacitor size calculator row.
A 1 hp or 0.75 kW motor takes 200-260 µF start and 15-20 µF run, often written as MFD. A 2 hp motor takes 340-400 µF and 25-30 µF, a 1/3 hp motor 100-130 µF and 5-7.5 µF, and 3, 5 and 7.5 hp sit in the chart above.
What size capacitor is needed for a 1.5 kW submersible pump?
A 1.5 kW submersible pump is a 2 hp motor, and Franklin Electric's 2 hp, 230 V standard control box uses a 105-126 µF start capacitor and a 20 µF, 370 V run capacitor.
That start capacitor draws about 9.1-10.9 A at 230 V and 60 Hz while the pump starts. The general 2 hp motor capacitor size calculator row of 340-400 µF would be far too large for a pump motor.
How many amps is a 1.5 HP motor?
A 1.5 hp single-phase motor draws 10 A at 230 V and 20 A at 115 V, per NEC Table 430.248, as reproduced in Elliott Electric's motor current table.
Those full-load currents size wire and breakers, separate from any motor capacitor size calculator figure. The Motor Current Calculator works out current for other sizes and voltages.
Can I use a bigger capacitor on a motor?
A bigger µF run capacitor is a poor swap. Replacing a 20 µF run capacitor with 25 µF raises its current at 230 V and 60 Hz from 1.73 A to 2.17 A, 25% more through the start winding, which heats the motor.
A higher voltage rating is the safe kind of bigger, as long as the µF value still matches the label within its printed tolerance.
How big should a motor run capacitor be?
Run capacitors on 230 V motors usually sit between 4 µF for a 1/4 hp motor and 70 µF for a 10 hp motor. Start capacitors are roughly ten to twenty times larger, from 75 µF up to 850 µF.
A normal run capacitor for a 1 hp motor is 15-20 µF, drawing 1.30-1.73 A at 60 Hz or 1.08-1.45 A at 50 Hz. A run capacitor far outside its motor capacitor size calculator range usually belongs to a different motor.
What units are used to measure a capacitor?
Capacitance is measured in farads, and motor capacitors are marked in microfarads, µF, often written MFD or uF. One µF is one millionth of a farad, so a 45 µF capacitor is 0.000045 F.
A label reading 2.5 means 2.5 µF, a typical ceiling fan capacitor. At 230 V and 50 Hz it carries 0.18 A, with a reactance of about 1,273 Ω.
How to calculate capacitor for 3 phase motor?
Three-phase induction motors start and run without start or run capacitors. Capacitors on three-phase motors correct power factor and are sized in kVAR, which the Power Factor Correction Calculator works out.
The link between the two units is Q = 2πfCV². A 25 µF capacitor on 400 V at 50 Hz supplies about 1.26 kVAR of reactive power, so power factor banks need far larger capacitance than a motor capacitor size calculator chart lists.
What is the 3 formula of power?
The three power formulas are P = V × I, P = I² × R and P = V² ÷ R. For an AC motor, real power adds the power factor, P = V × I × PF, and a capacitor's reactive power is Q = V × I.
A 25 µF capacitor at 400 V and 50 Hz carries 3.14 A, so Q = 400 × 3.14 = 1,257 VAR, the same 1.26 kVAR as the three-phase answer above.