UPS runtime calculator for backup time from load watts and battery V, Ah and count, with Peukert loss, battery health, VA and watt limits, and batteries needed to reach a set time.
Use the load in watts from the UPS display; battery V and Ah are printed on each battery.
Efficiency, Health & Peukert
UPS Rating Check
Shutdown Plan
Battery Bank Wiring
UPS Runtime by Wattage Chart
| Load | UPS Rating | Runtime | Simple Wh ÷ Load |
|---|---|---|---|
| 100 W | 10% | 1 h 1 min | 1 h 50 min |
| 250 W | 25% | 19.3 min | 44.1 min |
| 300 W | 30% | 15.4 min | 36.7 min |
| 500 W | 50% | 8.1 min | 22.0 min |
| 750 W | 75% | 4.9 min | 14.7 min |
| 1,000 W | 100% | 3.4 min | 11.0 min |
Runtime as Battery Health Drops
| Battery Health | Runtime | Change |
|---|---|---|
| 100% | 15.4 min | new battery |
| 90% | 13.5 min | -12% |
| 80% | 11.6 min | -24% |
| 70% | 9.8 min | -36% |
| 60% | 8.1 min | -47% |
| 50% | 6.5 min | -58% |
Step-by-Step UPS Runtime Math
UPS Runtime Calculator Check Against a 1500 VA Spec Sheet
A 1500 VA / 1000 W UPS on two 12 V 9 Ah batteries runs about 8 minutes at 500 W and 3.4 minutes at 1,000 W once Peukert loss is counted. The simple Wh ÷ load rule says 22 and 11 minutes, two to four times too long.
That battery set matches the CyberPower CP1500PFCLCD, whose product page lists 10 minutes at half load and 2.5 minutes at full load. The table puts both ups runtime calculator methods beside those published figures.
| Load | Share of 1,000 W | With Peukert (k 1.25) | Simple Wh ÷ load | CyberPower spec |
|---|---|---|---|---|
| 100 W | 10% | 1 h 1 min | 1 h 50 min | not listed |
| 300 W | 30% | 15.4 min | 36.7 min | not listed |
| 500 W | 50% | 8.1 min | 22.0 min | 10 min |
| 750 W | 75% | 4.9 min | 14.7 min | not listed |
| 1,000 W | 100% | 3.4 min | 11.0 min | 2.5 min |
The Peukert figure lands within 2 minutes of the maker's numbers at both points. The plain energy split misses by 12 and 8.5 minutes, which is why a UPS runtime calculator that only divides watt-hours by watts reads so high.
An apc ups runtime calculator or Eaton's runtime graphs give minutes for one maker's own battery packs. They make a sound cross-check on generic math, since they reflect that model's real cutoff voltage.
I is the battery current in amps, P is the load in watts, Vb is the bank voltage and η is the inverter efficiency. At 300 W, 24 V and 85%, the batteries supply 14.7 A, the first number any ups runtime calculator formula needs.
t is the runtime in hours, H is the 20-hour rating period, C is the rated Ah and k is the Peukert exponent. At 14.7 A on 9 Ah, t comes to 0.256 h, or 15.4 minutes.
The same math fits a spreadsheet for a ups runtime calculator excel sheet. With Ah in B1 and amps in B2, =20*(B1/(B2*20))^1.25*60 returns minutes for any load drawing more than the 20-hour current.
Below that current the full label Ah is available, so runtime is simply Ah ÷ amps. For this 24 V, 9 Ah bank the loss starts above about 9 W, so almost every real UPS load sits in the Peukert zone.
Runtime by Wattage for 7 Ah to 100 Ah Banks
Doubling the battery bank more than doubles runtime at the same load. Two 12 V 9 Ah batteries carry 300 W for 15.4 minutes, while four carry it for 36.5 minutes, because each battery then works at a gentler rate.
| Battery bank | Rated Wh | 100 W | 200 W | 300 W | 500 W | 800 W |
|---|---|---|---|---|---|---|
| 1 × 12 V 7 Ah | 84 Wh | 18.6 min | 7.8 min | 4.7 min | 2.5 min | 1.4 min |
| 1 × 12 V 9 Ah | 108 Wh | 25.5 min | 10.7 min | 6.5 min | 3.4 min | 1.9 min |
| 2 × 12 V 9 Ah | 216 Wh | 1 h 1 min | 25.5 min | 15.4 min | 8.1 min | 4.5 min |
| 4 × 12 V 9 Ah | 432 Wh | 2 h 24 min | 1 h 1 min | 36.5 min | 19.3 min | 10.7 min |
| 4 × 12 V 100 Ah | 4,800 Wh | 40 h 48 min | 20 h 24 min | 12 h 21 min | 6 h 31 min | 3 h 37 min |
Banks are wired in series to the stated count, at 85% efficiency on new sealed lead-acid, the basis of every ups runtime calculator watts figure here.
Two 12 V 18 Ah batteries hold the same 432 Wh as four 12 V 9 Ah and give the same minutes, since both draw the same amps per Ah.
A single 12 V 7 Ah battery suits the smallest UPS units. At 100 W it lasts 18.6 minutes, so a ups runtime calculator 12v estimate for a router and modem at 30 W to 50 W stretches much further than for a desktop PC.
The 12 hour run time UPS question needs a large external bank. Four 12 V 100 Ah batteries at 48 V hold a 300 W load for 12 h 21 min, and the same bank runs 100 W for over 40 hours.
Each row also works as a ups runtime by wattage chart for any UPS with that battery set, whatever its VA rating. The VA number caps the load; the batteries set the minutes.
Peukert Cuts Lead-Acid Minutes at High Load
A sealed lead-acid bank drained in about 15 minutes delivers only 42% of its label Ah. That is the Peukert effect, and lithium iron phosphate loses far less of its rating at the same rate.
| Load on 2 × 12 V 9 Ah | Discharge rate | Lead-acid (k 1.25) | LiFePO4 (k 1.05) | No Peukert (k 1.00) |
|---|---|---|---|---|
| 100 W | 0.54C | 1 h 1 min | 1 h 38 min | 1 h 50 min |
| 300 W | 1.63C | 15.4 min | 30.8 min | 36.7 min |
| 500 W | 2.72C | 8.1 min | 18.0 min | 22.0 min |
| 1,000 W | 5.45C | 3.4 min | 8.7 min | 11.0 min |
The discharge rate is battery amps divided by rated Ah, the C-rate a ups runtime calculator formula hinges on. At 300 W the 24 V bank draws 14.7 A from 9 Ah, a 1.63C rate, which is 33 times faster than the 20-hour rate the Ah figure assumes.
Victron uses k = 1.25 as its default for lead-acid and advises changing it only for lithium, according to its battery monitor manual. The same page warns that very high currents give even less than a fixed exponent predicts.
That warning explains the full-load row in the spec check above, where 3.4 minutes beats the published 2.5. Near full load, treat any ups runtime calculator figure as an upper limit and keep the maker's own minutes as the floor.
The point where that gap opens is about 4C on lead-acid. On two 12 V 9 Ah batteries that is 750 W at 4.08C and 1,000 W at 5.45C, so the top two rows of the spec check need the most margin.
Swapping lead-acid for LiFePO4 of the same Ah roughly doubles runtime at 300 W in the same ups runtime calculator run, from 15.4 to 30.8 minutes. The Battery Size Calculator sizes a lithium bank for loads outside a UPS.
Battery Age and the Runtime Chart
A lead-acid bank at 80% of its new capacity cuts runtime by 24%, not 20%. At 300 W on two 12 V 9 Ah batteries that is 11.6 minutes instead of 15.4, because the faster relative drain adds Peukert loss on top of the lost capacity.
| Battery health | Runtime at 300 W | Change from new | Runtime at 1,000 W |
|---|---|---|---|
| 100% | 15.4 min | new battery | 3.4 min |
| 90% | 13.5 min | -12% | 3.0 min |
| 80% | 11.6 min | -24% | 2.6 min |
| 70% | 9.8 min | -36% | 2.2 min |
| 60% | 8.1 min | -47% | 1.8 min |
| 50% | 6.5 min | -58% | 1.5 min |
Health is the share of label capacity the batteries still hold, and the one ups runtime calculator input that changes every year.
A runtime test against the UPS's own self-test reading, or the minutes it lasted in the last outage, is the practical way to set it.
A UPS battery life chart in the usual sense tracks this decline over years of service. In any ups runtime calculator estimate, the drop from new to 60% health turns 15 minutes into 8 at the same load.
A bank at 60% health running a 300 W load gives the same 8.1 minutes that a new bank gives at 500 W. Sizing for the aged state keeps a shutdown plan valid in year three as well as on day one.
The Battery Life Calculator covers how long a battery lasts on a steady DC load, without the inverter and VA limits a UPS adds.
Hours of Backup, 30 Minutes to 12 Hours
One hour at 300 W needs three strings of two 12 V 9 Ah batteries, six batteries in all, against the 14.7 Ah a simple energy split asks for. Two hours needs six strings, or twelve batteries.
| Target | Load | Ah needed at 24 V | Simple Wh ÷ load Ah | 12 V 9 Ah batteries | Runtime delivered |
|---|---|---|---|---|---|
| 30 min | 300 W | 15.4 Ah | 7.4 Ah | 4 | 36.5 min |
| 1 h | 300 W | 26.8 Ah | 14.7 Ah | 6 | 1 h 1 min |
| 2 h | 300 W | 46.6 Ah | 29.4 Ah | 12 | 2 h 24 min |
| 4 h | 100 W | 27.1 Ah | 19.6 Ah | 8 | 5 h 43 min |
| 8 h | 100 W | 47.1 Ah | 39.2 Ah | 12 | 9 h 29 min |
| 12 h | 100 W | 65.2 Ah | 58.8 Ah | 16 | 13 h 36 min |
The gap between the two Ah columns shrinks as the target grows. At 30 minutes Peukert doubles the Ah needed, while at 12 hours it adds only 11%.
A long target means a slow discharge, which is the one case where a plain energy-split ups runtime calculator comes close to the real minutes.
Whole strings round the result up, so most targets come out longer than asked. A ups runtime calculator with battery count in whole strings, like this table, matches how batteries are actually bought and wired.
Few desktop UPS units take this many batteries. Past about 30 minutes, an external battery cabinet or a model with an expansion port is the usual route, and the UPS charger must be sized to refill the larger bank.
VA, Watts and Power Factor on the Nameplate
A UPS must stay inside both its VA and its watt rating. A 1,000 W load at 0.9 power factor is 1,111 VA, which uses 100% of a 1500 VA / 1000 W unit's watts but only 74% of its VA.
| Load | Power factor | Apparent load | Share of 1,000 W | Share of 1,500 VA |
|---|---|---|---|---|
| 900 W | 0.9 | 1,000 VA | 90% | 67% |
| 1,000 W | 0.9 | 1,111 VA | 100% | 74% |
| 800 W | 0.6 | 1,333 VA | 80% | 89% |
| 1,350 W | 0.9 | 1,500 VA | 135% | 100% |
Modern PCs and servers with power-factor-corrected supplies run near 0.9 to 1.0, so the watt limit binds first. Older or uncorrected loads near 0.6 can hit the VA limit while still well under the watt rating.
Runtime follows watts, not VA, because the batteries supply real power, so the watts input to a ups runtime calculator matters more than the VA badge.
The 1500 VA label says nothing about minutes, which is why 600 VA, 1000 VA, 2000 VA and 3000 VA ups runtime figures depend on the battery inside each model.
A load above 80% of either rating leaves little room for startup surges or a device added later. The Electrical Power Calculator converts amps and volts from a device label to watts for this check.
Shutdown Timing for Servers and NAS
At 300 W with a 5-minute shutdown, the trigger must fire by 10.4 minutes into the outage, with a third of the battery left. At 1,000 W on the same 2 × 12 V 9 Ah bank, a 5-minute shutdown cannot finish at all.
| Load | Runtime | Trigger for 2-min shutdown | Trigger for 5-min shutdown | Trigger for 10-min shutdown |
|---|---|---|---|---|
| 300 W | 15.4 min | 13.4 min | 10.4 min | 5.4 min |
| 500 W | 8.1 min | 6.1 min | 3.1 min | too short |
| 750 W | 4.9 min | 2.9 min | too short | too short |
| 1,000 W | 3.4 min | 1.4 min | too short | too short |
The largest load that still allows a 5-minute shutdown on this bank is 736 W, and a 10-minute shutdown caps it at 423 W. Above those loads the fix is more batteries or less equipment on the battery outlets.
A shutdown runs at full load, so its energy comes out at the fastest rate. At 300 W, 5 minutes of shutdown draws about 29 Wh from the bank.
That reserve is why the trigger point in a ups runtime calculator plan sits well before the battery's last minutes.
Set the shutdown on minutes remaining or on a fixed delay after transfer, using the trigger from a ups runtime calculator run with the aged battery figure. A new-battery trigger leaves no margin once the bank reaches 60% health.
Spec Sheets, Calculators and Why Minutes Differ
These answers use the 2 × 12 V 9 Ah, 1500 VA / 1000 W example above, on new sealed lead-acid batteries, unless they say otherwise.
What is the difference between ups power calculator & uninterruptible power supply calculator?
They usually answer different questions. A UPS power or load calculator adds up the watts and VA of connected devices to choose a UPS size, while a runtime calculator takes that load and the batteries and returns minutes of backup.
A 600 W load fits a 1500 VA / 1000 W unit on the sizing side, yet runs only 6.5 minutes on its stock batteries. Both checks are needed, and the ups runtime calculator online result is the one that decides whether a shutdown can finish.
Why is UPS runtime different?
Real runtime differs from a ups runtime calculator estimate because of battery age, temperature, inverter efficiency and discharge rate.
A bank at 80% health gives 24% fewer minutes, and a high load drains lead-acid capacity faster than the label Ah suggests.
Inverter efficiency adds spread as well. At 500 W, 80% efficiency gives 7.5 minutes and 95% gives 9.3, so the same batteries can differ by almost 2 minutes between two UPS designs.