Breaker size calculator for amps, watts, kW or kVA loads: applies the NEC 125% continuous rule, picks the standard breaker, then sizes the wire, ground and voltage drop on the run.
Enter the load in amps or watts; loads that run 3 hours or more count as continuous.
Wire Type, Terminals & Derating
Wire Run & Voltage Drop
Breaker Load & Circuit Diagram
Breaker Size Chart, 240 V
| Breaker | Continuous (80%) | Continuous Power | Copper Wire | Aluminum Wire | Copper Ground | Your Load |
|---|---|---|---|---|---|---|
| 10 A | 8.0 A | 1,920 W | 14 AWG | 12 AWG | 14 AWG | not allowed |
| 15 A | 12.0 A | 2,880 W | 14 AWG | 12 AWG | 14 AWG | not allowed |
| 20 A | 16.0 A | 3,840 W | 12 AWG | 10 AWG | 12 AWG | not allowed |
| 25 A | 20.0 A | 4,800 W | 10 AWG | 10 AWG | 10 AWG | not allowed |
| 30 A | 24.0 A | 5,760 W | 10 AWG | 8 AWG | 10 AWG | not allowed |
| 35 A | 28.0 A | 6,720 W | 8 AWG | 8 AWG | 10 AWG | not allowed |
| 40 A | 32.0 A | 7,680 W | 8 AWG | 6 AWG | 10 AWG | recommended |
| 45 A | 36.0 A | 8,640 W | 6 AWG | 4 AWG | 10 AWG | allowed |
| 50 A | 40.0 A | 9,600 W | 6 AWG | 4 AWG | 10 AWG | allowed |
| 60 A | 48.0 A | 11,520 W | 4 AWG | 3 AWG | 10 AWG | allowed |
| 70 A | 56.0 A | 13,440 W | 4 AWG | 2 AWG | 8 AWG | allowed |
| 80 A | 64.0 A | 15,360 W | 3 AWG | 1 AWG | 8 AWG | allowed |
| 90 A | 72.0 A | 17,280 W | 2 AWG | 1/0 AWG | 8 AWG | allowed |
| 100 A | 80.0 A | 19,200 W | 1 AWG | 1/0 AWG | 8 AWG | allowed |
| 110 A | 88.0 A | 21,120 W | 2 AWG | 1/0 AWG | 6 AWG | allowed |
| 125 A | 100.0 A | 24,000 W | 1 AWG | 2/0 AWG | 6 AWG | allowed |
| 150 A | 120.0 A | 28,800 W | 1/0 AWG | 3/0 AWG | 6 AWG | allowed |
| 175 A | 140.0 A | 33,600 W | 2/0 AWG | 4/0 AWG | 6 AWG | allowed |
| 200 A | 160.0 A | 38,400 W | 3/0 AWG | 250 kcmil | 6 AWG | allowed |
| 225 A | 180.0 A | 43,200 W | 4/0 AWG | 300 kcmil | 4 AWG | allowed |
| 250 A | 200.0 A | 48,000 W | 250 kcmil | 350 kcmil | 4 AWG | allowed |
| 300 A | 240.0 A | 57,600 W | 350 kcmil | 500 kcmil | 4 AWG | allowed |
| 350 A | 280.0 A | 67,200 W | 500 kcmil | 750 kcmil | 3 AWG | allowed |
| 400 A | 320.0 A | 76,800 W | 600 kcmil | 1000 kcmil | 3 AWG | allowed |
| 450 A | 360.0 A | 86,400 W | 750 kcmil | parallel | 2 AWG | allowed |
| 500 A | 400.0 A | 96,000 W | 1000 kcmil | parallel | 2 AWG | allowed |
| 600 A | 480.0 A | 115,200 W | parallel | parallel | 1 AWG | allowed |
| 700 A | 560.0 A | 134,400 W | parallel | parallel | 1/0 AWG | allowed |
| 800 A | 640.0 A | 153,600 W | parallel | parallel | 1/0 AWG | allowed |
Copper Wire Size and Breaker Table
| Wire Size | 60°C | 75°C | 90°C | After Corrections | Largest Breaker | Drop at 75 ft |
|---|---|---|---|---|---|---|
| 14 AWG Cu | 15 A | 20 A | 25 A | 15.0 A | 15 A | 5.89% |
| 12 AWG Cu | 20 A | 25 A | 30 A | 20.0 A | 20 A | 3.70% |
| 10 AWG Cu | 30 A | 35 A | 40 A | 30.0 A | 30 A | 2.33% |
| 8 AWG Cu | 40 A | 50 A | 55 A | 40.0 A | 40 A | 1.47% |
| 6 AWG Cu | 55 A | 65 A | 75 A | 55.0 A | 60 A | 0.92% |
| 4 AWG Cu | 70 A | 85 A | 95 A | 70.0 A | 70 A | 0.58% |
| 3 AWG Cu | 85 A | 100 A | 115 A | 85.0 A | 90 A | 0.46% |
| 2 AWG Cu | 95 A | 115 A | 130 A | 95.0 A | 100 A | 0.36% |
| 1 AWG Cu | 110 A | 130 A | 145 A | 130.0 A | 150 A | 0.29% |
| 1/0 AWG Cu | 125 A | 150 A | 170 A | 150.0 A | 150 A | 0.23% |
| 2/0 AWG Cu | 145 A | 175 A | 195 A | 175.0 A | 175 A | 0.18% |
| 3/0 AWG Cu | 165 A | 200 A | 225 A | 200.0 A | 200 A | 0.14% |
| 4/0 AWG Cu | 195 A | 230 A | 260 A | 230.0 A | 250 A | 0.11% |
| 250 kcmil Cu | 215 A | 255 A | 290 A | 255.0 A | 300 A | 0.10% |
| 300 kcmil Cu | 240 A | 285 A | 320 A | 285.0 A | 300 A | 0.08% |
| 350 kcmil Cu | 260 A | 310 A | 350 A | 310.0 A | 350 A | 0.07% |
| 400 kcmil Cu | 280 A | 335 A | 380 A | 335.0 A | 350 A | 0.06% |
| 500 kcmil Cu | 320 A | 380 A | 430 A | 380.0 A | 400 A | 0.05% |
| 600 kcmil Cu | 350 A | 420 A | 475 A | 420.0 A | 450 A | 0.04% |
| 750 kcmil Cu | 400 A | 475 A | 535 A | 475.0 A | 500 A | 0.03% |
| 1000 kcmil Cu | 455 A | 545 A | 615 A | 545.0 A | 600 A | 0.02% |
Motor Breaker Chart, 230 V
| Motor | Table Current | Wire Minimum (125%) | Max Breaker (250%) | Copper Wire |
|---|---|---|---|---|
| 1/6 HP | 2.2 A | 2.8 A | 10 A | 14 AWG Cu |
| 1/4 HP | 2.9 A | 3.6 A | 10 A | 14 AWG Cu |
| 1/3 HP | 3.6 A | 4.5 A | 10 A | 14 AWG Cu |
| 1/2 HP | 4.9 A | 6.1 A | 15 A | 14 AWG Cu |
| 3/4 HP | 6.9 A | 8.6 A | 20 A | 14 AWG Cu |
| 1 HP | 8.0 A | 10.0 A | 20 A | 14 AWG Cu |
| 1-1/2 HP | 10.0 A | 12.5 A | 25 A | 14 AWG Cu |
| 2 HP | 12.0 A | 15.0 A | 30 A | 14 AWG Cu |
| 3 HP | 17.0 A | 21.3 A | 45 A | 10 AWG Cu |
| 5 HP | 28.0 A | 35.0 A | 70 A | 8 AWG Cu |
| 7-1/2 HP | 40.0 A | 50.0 A | 100 A | 6 AWG Cu |
| 10 HP | 50.0 A | 62.5 A | 125 A | 6 AWG Cu |
Step-by-Step Breaker Size Math
Breaker Size Calculator Picks for Home and Shop Loads
Most household loads land on a 15, 20, 30, 50 or 60 A breaker once the 125% continuous rule is applied. The table runs common loads through the NEC math, with THHN copper, an 86 °F (30 °C) room and three wires in the run.
| Load | Running current | Sizing current | Breaker | Copper wire, 60 °C terminals | Copper wire, 75 °C-marked terminals |
|---|---|---|---|---|---|
| Microwave, 1,500 W at 120 V | 12.5 A | 12.5 A | 15 A | 14 AWG | 14 AWG |
| Space heater, 1,500 W at 120 V | 12.5 A | 15.6 A | 20 A | 12 AWG | 12 AWG |
| Water heater, 4,500 W at 240 V | 18.8 A | 23.4 A | 25 A | 10 AWG | 10 AWG |
| Water heater, 5,500 W at 240 V | 22.9 A | 28.6 A | 30 A | 10 AWG | 10 AWG |
| Baseboard heat, 5,000 W at 240 V | 20.8 A | 26.0 A | 30 A | 10 AWG | 10 AWG |
| Electric dryer, 5,600 W at 240 V | 23.3 A | 23.3 A | 25 A | 10 AWG | 10 AWG |
| EV charger, 32 A | 32 A | 40.0 A | 40 A | 8 AWG | 8 AWG |
| EV charger, 40 A | 40 A | 50.0 A | 50 A | 6 AWG | 8 AWG |
| EV charger, 48 A | 48 A | 60.0 A | 60 A | 4 AWG | 6 AWG |
| Heat strip, 10 kW at 240 V | 41.7 A | 52.1 A | 60 A | 6 AWG | 6 AWG |
| Kettle, 2,200 W at 230 V | 9.6 A | 9.6 A | 15 A | 14 AWG | 14 AWG |
| Shower heater, 9 kW at 230 V | 39.1 A | 48.9 A | 50 A | 6 AWG | 8 AWG |
Water heaters, fixed space heat and EV chargers are continuous by code. NEC 422.13, 424.4(B) and 625.41 each call for 125% sizing, so a 4,500 W water heater needs 23.4 A of breaker, not 18.8 A.
A 4,500 W water heater is often shown on a 30 A breaker. The breaker size calculator result is 25 A, which is the legal minimum; 30 A is also allowed on the same 10 AWG copper, since 240.4(D) lets 10 AWG carry up to 30 A.
The dryer row is non-continuous, so 25 A is the minimum. Most dryer cords carry a 30 A plug, and 10 AWG copper covers a 30 A circuit, so 30 A is the usual install. Check the dryer's nameplate first.
Read each breaker size calculator row as a minimum. A larger breaker is legal only when the wire grows with it, since 240.4 ties every breaker to the wire it protects.
The 60 °C column matters most for EV chargers. A 40 A charger needs 8 AWG on 75 °C terminals but 6 AWG on 60 °C terminals, set by the breaker and charger markings.
Any breaker size calculator for home EV charging therefore needs the terminal rating, not just the wire's own 90 °C insulation rating.
Standard Breaker Sizes, Including the New 10 A
NEC 240.6(A) lists the standard ratings: 10, 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700 and 800 A, then 1,000 A up to 6,000 A.
The 10 A rating is new in the 2023 NEC. Under 210.23(A), a 10 A branch circuit is meant for lighting outlets, bath or laundry exhaust fans on a lighting circuit, and a gas fireplace on its own circuit.
EC&M's review of the 2023 change lists the loads it bans, including receptacle outlets, garage door openers and laundry equipment.
Round up, never down. A breaker size calculator total of 37.5 A means a 40 A breaker, not 35 A, since the breaker must be at least the sizing current.
That is why a tiny general load still rounds to 15 A. A 2,200 W kettle at 230 V draws 9.6 A, but it plugs into a receptacle, which a 10 A circuit can't feed, so any breaker size calculator answer for it should read 15 A.
Fuses add 1, 3 and 6 A ratings below the smallest breaker. Those small sizes matter for control transformers, where a breaker size calculator result can fall below 10 A.
Receptacle circuits narrow the list further. A circuit with two or more receptacles must be 15, 20, 30, 40 or 50 A under 210.21(B)(3).
A 22 A load gets 25 A on a hardwired circuit but 30 A on a receptacle circuit, so a breaker size calculator answer depends on whether outlets are involved.
Outside North America, miniature breakers follow IEC 60898-1, with ratings such as 6, 10, 16, 20, 25, 32, 40 and 63 A.
The 125% NEC rule and AWG wire sizes don't carry over. Use the local wiring rules and the AWG to mm² Calculator to compare cable sizes.
The same applies to any breaker size calculator Australia or UK readers use, since AS/NZS 3000 and BS 7671 set their own cable tables and derating methods.
Wire Size Has to Match the Breaker
The breaker protects the wire, so the wire sets the largest breaker allowed. NEC 240.4(D) caps 14 AWG copper at 15 A, 12 AWG at 20 A and 10 AWG at 30 A, whatever its table ampacity says. That cap overrides any breaker size calculator total.
That cap answers a common question. A 30 A breaker on 10 AWG copper rated 35 A at 75 °C is legal, but a 35 A breaker is not, because 240.4(D) holds 10 AWG to 30 A.
| Breaker | Copper, Auto terminals | Copper, 75 °C-marked terminals | Aluminum, Auto terminals | Copper ground |
|---|---|---|---|---|
| 15 A | 14 AWG | 14 AWG | 12 AWG | 14 AWG |
| 20 A | 12 AWG | 12 AWG | 10 AWG | 12 AWG |
| 30 A | 10 AWG | 10 AWG | 8 AWG | 10 AWG |
| 40 A | 8 AWG | 8 AWG | 6 AWG | 10 AWG |
| 50 A | 6 AWG | 8 AWG | 4 AWG | 10 AWG |
| 60 A | 4 AWG | 6 AWG | 3 AWG | 10 AWG |
| 70 A | 4 AWG | 4 AWG | 2 AWG | 8 AWG |
| 100 A | 1 AWG | 3 AWG | 1/0 AWG | 8 AWG |
| 110 A | 2 AWG | 2 AWG | 1/0 AWG | 6 AWG |
| 125 A | 1 AWG | 1 AWG | 2/0 AWG | 6 AWG |
| 150 A | 1/0 AWG | 1/0 AWG | 3/0 AWG | 6 AWG |
| 200 A | 3/0 AWG | 3/0 AWG | 250 kcmil | 6 AWG |
Each size assumes the breaker carries a continuous load at its 80% limit, so the wire must handle the full breaker rating at the terminals. Auto terminals mean the 60 °C column up to 100 A and 75 °C above. Grounds come from NEC Table 250.122.
The 100 A and 110 A rows look backward but are right. A 100 A breaker sits in the 60 °C group and needs 1 AWG copper, while 110 A moves to the 75 °C column, where 2 AWG carries 115 A.
Terminal temperature decides the column. Under 110.14(C)(1)(a), circuits of 100 A or less use the 60 °C column unless the equipment is marked 75 °C, as Eaton's conductor ampacity guide sets out.
At 50 A that is the gap between 8 AWG and 6 AWG, so a breaker size calculator set to 75 °C undersizes the wire on 60 °C equipment.
The 90 °C rating of THHN is a starting point for heat and bundling corrections, not a breaker rating.
NM-B works the same way: 334.80 lets it start corrections from the 90 °C column, but the result can't exceed the 60 °C ampacity, so a 40 A EV charger on NM-B needs 6 AWG.
Heat and crowding can change the wire without changing the breaker size calculator result. These cases hold a 24 A continuous load on a 30 A breaker and a 40 A EV charger on a 50 A breaker, both with THHN copper on Auto terminals.
| Ambient | Current-carrying wires | Combined factor | 24 A load, 30 A breaker | 40 A EV, 50 A breaker |
|---|---|---|---|---|
| 86 °F (30 °C) | 3 | 1.00 | 10 AWG | 6 AWG |
| 86 °F (30 °C) | 6 | 0.80 | 10 AWG | 6 AWG |
| 104 °F (40 °C) | 6 | 0.73 | 10 AWG | 6 AWG |
| 122 °F (50 °C) | 6 | 0.66 | 10 AWG | 6 AWG |
| 122 °F (50 °C) | 9 | 0.57 | 8 AWG | 4 AWG |
The last EV row shows a trap. At 0.57, 6 AWG still carries 43.1 A, enough for the 40 A load, but that only allows a 45 A breaker under 240.4(B). Protecting it on 50 A takes 4 AWG.
Without that protection check, a breaker size calculator total would wrongly pass 6 AWG on a 50 A breaker in that hot, crowded run.
The Wire Ampacity Calculator runs the same corrections for any wire, and the Conduit Fill Calculator counts how many current-carrying wires share the pipe.
Watts per Breaker at 120, 230, 240 and 480 V
A 20 A breaker at 120 V carries 1,920 W continuously and 2,400 W for loads under three hours. Continuous means running three hours or more, which caps the load at 80% of the breaker rating.
| Breaker | 120 V | 230 V | 240 V | 208 V three-phase | 480 V three-phase |
|---|---|---|---|---|---|
| 15 A | 1,440 / 1,800 W | 2,760 / 3,450 W | 2,880 / 3,600 W | 4,323 / 5,404 W | 9,977 / 12,471 W |
| 20 A | 1,920 / 2,400 W | 3,680 / 4,600 W | 3,840 / 4,800 W | 5,764 / 7,205 W | 13,302 / 16,628 W |
| 30 A | 2,880 / 3,600 W | 5,520 / 6,900 W | 5,760 / 7,200 W | 8,646 / 10,808 W | 19,953 / 24,942 W |
| 40 A | 3,840 / 4,800 W | 7,360 / 9,200 W | 7,680 / 9,600 W | 11,529 / 14,411 W | 26,604 / 33,255 W |
| 50 A | 4,800 / 6,000 W | 9,200 / 11,500 W | 9,600 / 12,000 W | 14,411 / 18,013 W | 33,255 / 41,569 W |
Each cell reads continuous / short-term watts at a power factor of 1.0. A 15 A breaker at 120 V handles 1,440 W of heaters or lights left on for hours, and 1,800 W for a short burst such as a hair dryer.
Watts alone can't size a breaker, because the same 3,600 W draws 30 A at 120 V but 15 A at 240 V. Convert to amps at the real voltage before any breaker size calculator step.
To rebuild this breaker size calculator chart in Excel, multiply amps by volts by 0.8 for continuous watts, and by 1.732 more for three-phase. Drop the 0.8 for loads under three hours.
A main breaker size calculator works the same way at panel scale, but it starts from NEC Article 220 demand loads, which run well below the sum of every nameplate in the house.
Three-Phase Breaker Math With Power Factor
Three-phase current is watts divided by 1.732 times the line voltage times the power factor. A 25 kW load at 208 V and 0.85 power factor draws 81.6 A; the same load at 480 V draws 35.4 A.
The first formula covers single-phase breaker size calculator math and the second covers three-phase. I is current in amps, P is real power in watts, V is the line-to-line voltage and PF is the power factor. For DC and resistive loads, PF is 1.
| Continuous load | Supply | Current | × 125% | Breaker | Copper wire |
|---|---|---|---|---|---|
| 10 kW, PF 1.0 | 240 V single-phase | 41.7 A | 52.1 A | 60 A | 6 AWG |
| 10 kW, PF 0.9 | 208 V three-phase | 30.8 A | 38.6 A | 40 A | 8 AWG |
| 10 kW, PF 0.9 | 400 V three-phase | 16.0 A | 20.1 A | 25 A | 10 AWG |
| 10 kW, PF 0.9 | 480 V three-phase | 13.4 A | 16.7 A | 20 A | 12 AWG |
| 25 kW, PF 0.85 | 208 V three-phase | 81.6 A | 102.0 A | 110 A | 2 AWG |
| 25 kW, PF 0.85 | 480 V three-phase | 35.4 A | 44.2 A | 45 A | 6 AWG |
| 50 kW, PF 0.9 | 480 V three-phase | 66.8 A | 83.5 A | 90 A | 3 AWG |
The 400 V row lands on 20.1 A, just past 20 A, so a 3-phase breaker size calculator result jumps to 25 A. A slightly better power factor of 0.91 would bring it back under 20 A.
Power factor only applies to watts. A load given in kVA or VA already includes it, so divide kVA by volts (and by 1.732 for three-phase) with no PF term in any breaker size calculator total.
Motor Breakers at 250% of NEC Table Current
A motor breaker can be up to 250% of the motor's full-load current under NEC 430.52, rounded up to the next standard size. A 5 HP, 230 V single-phase motor at 28 A gets a 70 A breaker on 8 AWG copper, or 10 AWG where the terminals are marked 75 °C.
Starting current is the reason. Inrush often runs several times the running current, so a 125% breaker would trip on every start. Overload protection is separate and is set from the nameplate amps under 430.32.
The current comes from NEC Table 430.248 (single-phase) or Table 430.250 (three-phase), not the nameplate FLA, per 430.6(A)(1). The wire is sized at 125% of that table current under 430.22.
Every row below follows the same breaker size calculator for motors sequence: table current, × 2.5, next standard size, then 125% wire.
| Motor | Table current | 250% limit | Breaker | Wire minimum (125%) | Copper wire, Auto terminals |
|---|---|---|---|---|---|
| 1 HP, 115 V single-phase | 16 A | 40.0 A | 40 A | 20.0 A | 12 AWG |
| 2 HP, 230 V single-phase | 12 A | 30.0 A | 30 A | 15.0 A | 14 AWG |
| 3 HP, 230 V single-phase | 17 A | 42.5 A | 45 A | 21.3 A | 10 AWG |
| 5 HP, 230 V single-phase | 28 A | 70.0 A | 70 A | 35.0 A | 8 AWG |
| 10 HP, 208 V three-phase | 30.8 A | 77.0 A | 80 A | 38.5 A | 8 AWG |
| 10 HP, 460 V three-phase | 14 A | 35.0 A | 35 A | 17.5 A | 12 AWG |
| 25 HP, 460 V three-phase | 34 A | 85.0 A | 90 A | 42.5 A | 6 AWG |
| 50 HP, 460 V three-phase | 65 A | 162.5 A | 175 A | 81.3 A | 4 AWG |
A 40 A breaker on 12 AWG looks wrong but is legal for the 1 HP motor. Motor circuits follow 240.4(G) and Article 430, so the 240.4(D) cap of 20 A doesn't apply; 12 AWG only has to carry the 20 A wire minimum.
For motors, the breaker size calculator result is the largest legal breaker. Starting with a smaller one, such as 175% or 200%, is fine if it holds through the start.
Nameplate amps in a breaker size calculator for motors give a different, usually smaller, number than the NEC table, which is why the table value governs.
Air Conditioner MCA and MOCP on the Nameplate
For an AC unit or heat pump, the wire follows the MCA (minimum circuit ampacity) and the breaker follows the MOCP (maximum overcurrent protection). Both come from the outdoor unit's nameplate under NEC Article 440.
| Nameplate MCA | Nameplate MOCP | Breaker | Copper wire, Auto terminals | Copper wire, 75 °C-marked terminals |
|---|---|---|---|---|
| 14.2 A | 20 A | 20 A | 14 AWG | 14 AWG |
| 18 A | 25 A | 25 A | 12 AWG | 14 AWG |
| 23 A | 35 A | 35 A | 10 AWG | 12 AWG |
| 23 A | 37 A | 35 A | 10 AWG | 12 AWG |
| 26 A | 40 A | 40 A | 10 AWG | 10 AWG |
| 32 A | 50 A | 50 A | 8 AWG | 10 AWG |
| 42.5 A | 60 A | 60 A | 6 AWG | 8 AWG |
The MOCP is a ceiling, so a nameplate that reads 37 A gets the next size down, 35 A. Rounding up is not allowed here, unlike motors and general loads, so a breaker size calculator total for AC units always rounds down.
A 35 A breaker on 10 or 12 AWG copper is the case that surprises people. A 23 A MCA needs 10 AWG on 60 °C terminals, but 12 AWG at 25 A is enough where they are marked 75 °C.
Either way the breaker runs above the wire's normal 240.4(D) limit. Article 440 allows that so the breaker can ride through compressor starts.
The MCA already includes the 125% factor for the compressor, so no breaker size calculator multiplier is applied to it again. Use an HACR-rated breaker if the nameplate asks for one.
Transformer Primary Breakers Under Table 450.3(B)
A transformer protected on the primary only gets a breaker of up to 125% of primary current when that current is 9 A or more, rounded up to the next standard size. Below 9 A the limit is 167%, and below 2 A it is 300%, with no rounding up.
Those three tiers come from NEC Table 450.3(B) for transformers of 1,000 V or less, also laid out in Eaton's transformer protection guide.
| Transformer | Primary current | Limit | Maximum | Primary breaker |
|---|---|---|---|---|
| 1.5 kVA, 240 V single-phase | 6.25 A | 167% | 10.44 A | 10 A |
| 3 kVA, 480 V three-phase | 3.61 A | 167% | 6.03 A | 6 A fuse |
| 9 kVA, 480 V three-phase | 10.83 A | 125% | 13.53 A | 15 A |
| 30 kVA, 480 V three-phase | 36.08 A | 125% | 45.11 A | 50 A |
| 45 kVA, 480 V three-phase | 54.13 A | 125% | 67.66 A | 70 A |
| 75 kVA, 480 V three-phase | 90.21 A | 125% | 112.76 A | 125 A |
| 112.5 kVA, 480 V three-phase | 135.32 A | 125% | 169.15 A | 175 A |
The 3 kVA case has no breaker at all. Its 6.03 A ceiling sits below the smallest 10 A breaker, so a 6 A fuse is the largest device allowed. The secondary side is sized separately.
Below 9 A, any breaker size calculator for transformers has to stop rounding up. A 1.5 kVA unit at 240 V allows 10.44 A, so 10 A is the limit, never 15 A.
Long Runs Grow the Wire, Not the Breaker
Voltage drop never changes the breaker, because distance never enters the breaker size calculator math. A 20 A circuit with a 16 A continuous load at 120 V stays on 20 A at any length; only the wire gets bigger to hold the drop near 3%.
Vd is the drop in volts, K is 12.9 for copper or 21.2 for aluminum, I is the running current, L is the one-way length in feet and CM is the wire's area in circular mils. For three-phase, 1.732 replaces the 2.
| One-way run | Drop on 12 AWG | Wire for 3% or less | Breaker |
|---|---|---|---|
| 50 ft (15 m) | 2.63% | 12 AWG | 20 A |
| 75 ft (23 m) | 3.95% | 10 AWG | 20 A |
| 100 ft (30 m) | 5.27% | 8 AWG | 20 A |
| 150 ft (46 m) | 7.90% | 6 AWG | 20 A |
At 120 V, 12 AWG holds 3% for only about 57 ft at 16 A. A 48 A EV charger at 240 V needs 4 AWG on 60 °C terminals, which holds 3% to about 243 ft. At 250 ft the drop is 3.09%, so that run moves to 3 AWG on the same 60 A breaker.
The Voltage Drop Calculator handles other loads and voltages, and the Wire Size Calculator finds the gauge for ampacity and drop together.
Upsizing, Tripping and Continuous Load Calls
Unless a case says otherwise, wire sizes below assume copper THHN in an 86 °F (30 °C) room with three current-carrying wires, on 60 °C terminals up to 100 A and 75 °C above.
Do I need a breaker size if I have a continuous load?
A continuous load needs a breaker of at least 125% of its current, per NEC 210.20(A). A load that runs three hours or more counts, such as a heater, an EV charger or store lighting.
B is the breaker rating, Ic is the continuous current and In is any non-continuous current on the same circuit.
The 80% rule is the same limit read the other way, since 1 ÷ 1.25 = 0.80. The 125% step comes before rounding in any breaker size calculator.
A standard breaker is listed to carry only 80% of its rating for that long inside a panel. Breakers listed for 100% duty skip the 125% factor, but those are mostly large commercial frames.
How do I find the correct breaker size?
Convert the load to amps, add 25% if it is continuous, then round up to the next standard size. A 5,000 W baseboard heater at 240 V draws 20.8 A; × 1.25 gives 26.0 A, so the answer is 30 A.
Then check the wire. That 30 A breaker needs 10 AWG copper with a 10 AWG ground, and the drop over 75 ft is 1.62%. Run as a non-continuous load, the same 5,000 W would only need 25 A. That is the full breaker size calculator sequence by hand.
How do I use a circuit breaker size calculator?
Gather five facts first: the load in amps or watts, the voltage, single- or three-phase, whether it runs three hours or more, and the wire material. Motors need horsepower, and AC units need the nameplate MCA and MOCP.
A single-phase breaker size calculator and a three-phase one need the same facts, plus the power factor when the load is given in watts.
A circuit breaker size calculator and breaker sizing are the same job when the result includes the wire check. A breaker number alone, without the wire and terminal rating behind it, is only half of the answer.
What size circuit breaker do I Need?
The load sets the minimum and the wire sets the maximum. For general circuits, 14 AWG copper takes 15 A, 12 AWG takes 20 A and 10 AWG takes 30 A; above that, the wire table decides.
A breaker size calculator for home circuits starts from those three caps, then checks the load against them before anything is bought.
A 7,200 W EV charger at 240 V draws 30 A, needs 37.5 A after the 125% factor, and lands on 40 A with 8 AWG copper. A 48 A charger needs 60 A and 4 AWG, or 6 AWG where the terminals are marked 75 °C.
Can I replace a breaker with a bigger breaker?
Only when the wire is rated for the bigger breaker. Swapping a 20 A breaker for a 30 A on 12 AWG copper breaks 240.4(D) and lets the wire overheat before anything trips.
A breaker that keeps tripping is doing its job. Measure the load first; if it truly needs 30 A, pull 10 AWG copper and then fit the 30 A breaker. No breaker size calculator result justifies a bigger breaker on the same wire.
How do I properly size breakers for circuits with multiple types of loads?
Add 125% of the continuous part to 100% of the rest. A circuit with 30 A of continuous heat and 20 A of other load needs 57.5 A, so it gets a 60 A breaker on 4 AWG copper.
Motors on a shared feeder add 125% of the largest motor's table current under 430.24. Panel and service sizing use the demand factors of NEC Article 220.
Those demand factors shrink the total well below the sum of nameplates, which keeps whole-panel math separate from branch-circuit breaker size calculator work.
What's the difference between interrupting capacity (AIC/kAIC) and continuous current rating?
The current rating is what a breaker carries before it trips on overload; the interrupting rating is the largest fault current it can safely break. A 20 A breaker can carry 20 A but must stop thousands of amps in a short circuit.
NEC 110.9 requires the interrupting rating to meet the fault current available at the panel. Standard residential breakers are commonly rated 10 kA, with 22 kA and higher versions where the utility transformer is large or close.
Interrupting rating sits outside breaker size calculator math. Read it from the panel label and the fault-current figure the utility supplies.