Conduit Fill Calculator

Updated

Conduit fill calculator for EMT, PVC, rigid and flex conduit: NEC fill percent with every ground wire counted, the smallest trade size and the most wires that one conduit can hold.

Conduit Fill Setup

Pick the conduit, then the wires going in it; the ground wire counts toward fill too.

wires
More Wire Sizes & Ground (EGC)no more wires · ground 1 × 10 AWG
wires
wires
wires
A
Cables, Derating & Pulling0 cables · 0 neutral off · over 24 in · 90° bends
cables
wires
°
3/4 in EMT Fill (40% Max for 4 wires)
15.83% Conduit Fill
0.0844 in² of wire in 0.533 in² of conduit
0.1286 in² Room Left
Allowed at 40%0.213 in²
Limit Used39.6%
Allowed area is 53% for one wire, 31% for two and 40% for three or more, measured against the conduit inside area.
1/2 in EMT Smallest Size
Fill at 1/2 in27.76%
Room at 1/2 in0.0376 in²
The smallest trade size of this conduit type that still holds every wire you entered, plus the fill it would then have.
10 × 10 AWG THHN Max
Room for More 10 AWGroom for 6 more
Area of One 10 AWG0.0211 in²
Most wires of your first size this conduit holds alone, using the 0.8 round-up rule for wires that are all one size.
100% Ampacity for 3 wires
Jam Ratio (1.05 D/d)5.28 · clear
Bends Left to 360°270°
Ampacity adjustment for current-carrying wires, the jam ratio for pulling three wires, and the bends left before you add a pull point.
Conduit Cross-Section Diagram4 wires · 15.83%
3/4 in EMT · ID 0.824 in15.83% filled · dashed ring = 40% limit3 × 10 AWG THHN = 0.0633 in²1 × 10 AWG THHN ground = 0.0211 in²
How Many Wires Fit in 3/4 in EMT21 sizes · 53/31/40%
Wire SizeTHHNXHHW-2TW / THWRHW-2
14 AWG22 wires15 wires15 wires7 wires
12 AWG16 wires11 wires11 wires6 wires
10 AWG10 wires8 wires8 wires5 wires
8 AWG6 wires5 wires5 wires2 wires
6 AWG4 wires3 wires3 wires1 wire
4 AWG2 wires2 wires1 wire1 wire
3 AWG1 wire1 wire1 wire1 wire
2 AWG1 wire1 wire1 wire1 wire
1 AWG1 wire1 wire1 wire1 wire
1/0 AWG1 wire1 wire1 wire1 wire
2/0 AWG1 wire1 wire1 wire1 wire
3/0 AWG1 wire1 wire1 wire0 wires
4/0 AWG1 wire1 wire0 wires0 wires
250 kcmil0 wires0 wires0 wires0 wires
300 kcmil0 wires0 wires0 wires0 wires
350 kcmil0 wires0 wires0 wires0 wires
400 kcmil0 wires0 wires0 wires0 wires
500 kcmil0 wires0 wires0 wires0 wires
600 kcmil0 wires0 wires0 wires0 wires
750 kcmil0 wires0 wires0 wires0 wires
1000 kcmil0 wires0 wires0 wires0 wires
EMT Conduit Fill Chart by Trade Size10 sizes
Trade SizeInside Diameter100% AreaAllowed (40%)Your FillMax 10 AWG THHNStatus
1/2 in (16)0.622 in0.304 in²0.122 in²27.76%5 wiresFits
3/4 in (21)0.824 in0.533 in²0.213 in²15.83%10 wiresFits
1 in (27)1.049 in0.864 in²0.346 in²9.77%16 wiresFits
1-1/4 in (35)1.380 in1.496 in²0.598 in²5.64%28 wiresFits
1-1/2 in (41)1.610 in2.036 in²0.814 in²4.15%38 wiresFits
2 in (53)2.067 in3.356 in²1.342 in²2.51%63 wiresFits
2-1/2 in (63)2.731 in5.858 in²2.343 in²1.44%111 wiresFits
3 in (78)3.356 in8.846 in²3.538 in²0.95%167 wiresFits
3-1/2 in (91)3.834 in11.545 in²4.618 in²0.73%219 wiresFits
4 in (103)4.334 in14.753 in²5.901 in²0.57%279 wiresFits
Fill Percentage Table for 3/4 in EMT53 / 31 / 40 / 60%
Wires in ConduitMax FillAllowed AreaMax 10 AWG THHNYour Fill vs Limit
1 wire53%0.283 in²fits--
2 wires31%0.165 in²fits--
3 or more wires40%0.213 in²10 wires15.83% of 40%
Nipple, 24 in or less60%0.320 in²15 wires--
Conduit Type Comparison12 types at 3/4 in
Conduit TypeInside Diameter100% AreaYour Fill at 3/4 inStatusSmallest That Fits
EMT - Metal Tubing0.824 in0.533 in²15.83%Fits1/2 in
ENT - Nonmetallic Tubing0.760 in0.454 in²18.59%Fits1/2 in
FMC - Flexible Metal0.824 in0.533 in²15.83%Fits1/2 in
IMC - Intermediate Metal0.864 in0.586 in²14.40%Fits1/2 in
LFNC-B (Gray)0.830 in0.541 in²15.60%Fits1/2 in
LFNC-A (Orange)0.825 in0.535 in²15.78%Fits1/2 in
LFMC - Liquidtight Metal0.830 in0.541 in²15.60%Fits1/2 in
RMC - Rigid Metal0.836 in0.549 in²15.37%Fits1/2 in
PVC Schedule 800.722 in0.409 in²20.64%Fits1/2 in
PVC Schedule 40 / HDPE0.804 in0.508 in²16.61%Fits1/2 in
PVC Type A0.910 in0.650 in²12.98%Fits1/2 in
PVC Type EB----Not made in 3/4 in--2 in
Step-by-Step Conduit Fill Math9 steps
Wire count3 + 1 = 4 wires → 40% limit (3 or more)
Wire area3 × 10 AWG THHN (0.0211 in² each) = 0.0633 in²
Ground wire size30 A breaker → 10 AWG copper ground (NEC Table 250.122)
Ground wire area1 × 10 AWG THHN (0.0211 in² each) = 0.0211 in²
Total wire area0.0633 in² + 0.0211 in² = 0.0844 in²
Conduit area3/4 in EMT: 100% = 0.533 in², 40% = 0.213 in²
Fill percent0.0844 in² ÷ 0.533 in² × 100 = 15.83%
Check0.0844 in² ≤ 0.213 in² → passes
Result15.83% Conduit Fill
Fits: 15.83% Fill in 3/4 in EMT (40% Max)
Your 4 wires use 0.0844 in² of the 0.213 in² allowed, and the ground wire is counted. The 30 A breaker calls for a 10 AWG copper ground (Table 250.122). At 4 to 6 current-carrying wires, ampacity drops to 80% (NEC 310.15(C)(1)).

Conduit Fill Calculator Results for Everyday Circuits

Most branch circuits fit in 1/2 in EMT (metric 16), and fill only gets tight at feeders. The table runs common THHN circuits through the NEC Chapter 9 math, with the ground sized from the breaker.

CircuitTHHN wiresGroundTotal areaSmallest EMTSmallest PVC Sch 40Smallest PVC Sch 80
15 A, 120 V2 × 14 AWG14 AWG0.0291 in² (18.8 mm²)1/2 in, 9.57%1/2 in, 10.21%1/2 in, 13.41%
20 A, 120 V2 × 12 AWG12 AWG0.0399 in² (25.7 mm²)1/2 in, 13.12%1/2 in, 14.00%1/2 in, 18.39%
20 A, 240 V + neutral3 × 12 AWG12 AWG0.0532 in² (34.3 mm²)1/2 in, 17.50%1/2 in, 18.67%1/2 in, 24.52%
Two 20 A, 120 V circuits4 × 12 AWG12 AWG0.0665 in² (42.9 mm²)1/2 in, 21.88%1/2 in, 23.33%1/2 in, 30.65%
30 A, 240 V + neutral3 × 10 AWG10 AWG0.0844 in² (54.5 mm²)1/2 in, 27.76%1/2 in, 29.61%1/2 in, 38.89%
40 A range3 × 8 AWG10 AWG0.1309 in² (84.5 mm²)3/4 in, 24.56%3/4 in, 25.77%3/4 in, 32.00%
50 A, 240 V + neutral3 × 6 AWG10 AWG0.1732 in² (111.7 mm²)3/4 in, 32.50%3/4 in, 34.09%1 in, 25.17%
60 A subpanel4 × 6 AWG10 AWG0.2239 in² (144.5 mm²)1 in, 25.91%1 in, 26.91%1 in, 32.54%
100 A feeder4 × 3 AWG8 AWG0.4258 in² (274.7 mm²)1-1/4 in, 28.46%1-1/4 in, 29.30%1-1/4 in, 34.42%
200 A feeder4 × 3/0 AWG6 AWG1.1223 in² (724.1 mm²)2 in, 33.44%2 in, 34.10%2 in, 39.05%

Each total includes the ground, so a conduit fill calculator total that skips it reads low. Every row with three or more wires is held to 40% of the conduit's inside area.

The ground sizes follow NEC Table 250.122: 14 AWG up to 15 A, 12 AWG up to 20 A, 10 AWG up to 60 A, 8 AWG up to 100 A and 6 AWG up to 200 A.

PVC Schedule 80 is the one that catches people. Its thicker wall cuts 3/4 in to 0.164 in² of usable area, so a 50 A circuit that passes in 3/4 in EMT needs 1 in Schedule 80.

Wire sizes here follow common practice; confirm yours with the Wire Size Calculator before you run conduit fill calculator numbers.

Table 1 Limits: 53, 31, 40 and 60 Percent

NEC Chapter 9 Table 1 allows 53% fill for one wire, 31% for two and 40% for three or more. Note 4 raises the limit to 60% for a nipple of 24 in (600 mm) or less between enclosures. These four limits sit behind every conduit fill calculator result.

Two wires get the lowest limit because two round wires side by side span the full diameter, so they bind at a bend before three wires that nest in a triangle.

With 40% alone, any conduit fill calculator count for one or two wires comes out wrong. The table puts each limit into square inches for 3/4 in EMT, inside diameter 0.824 in (20.9 mm).

Wires in conduitMax fillAllowed area, 3/4 in EMTMost 12 AWG THHN
1 wire53%0.283 in² (183 mm²)1
2 wires31%0.165 in² (106 mm²)2
3 or more40%0.213 in² (137 mm²)16
Nipple, 24 in or less60%0.320 in² (206 mm²)24

The nipple rule adds real room to any conduit fill calculator count. In 1/2 in EMT the count of 12 AWG THHN jumps from 9 to 13, and 10 AWG goes from 5 to 8. Short nipples are also exempt from ampacity adjustment, so the extra wires carry full rating.

Note 7 is the rule most charts skip. When all wires are the same size, a count that ends in .8 or more rounds up to the next whole wire. Below .8 it rounds down, even at .79.

Without the round-up, a conduit fill calculator chart comes up one wire short in each case below, where the ratio lands at .8 or higher.

THHN sizeEMT sizeAllowed area ÷ wire areaWithout Note 7With Note 7
14 AWG3/4 in21.962122
8 AWG3/4 in5.8256
6 AWG1 in6.8267
2 AWG1 in2.9923
1 AWG1-1/4 in3.8334
4 AWG1-1/2 in9.88910

The round-up never applies to mixed sizes. Once one wire differs, even a ground one size smaller, the total area must sit at or under the limit with no rounding.

Ground Wires Can Flip a Pass to a Fail

An equipment grounding conductor counts toward fill like any other wire, bare or insulated, in every conduit fill calculator total. Leaving it out is the most common way a hand count passes and the inspection fails.

A 40 A range circuit shows it. Three 8 AWG THHN use 0.1098 in², which fits the 0.122 in² allowed in 1/2 in EMT at 36.12%. Add the 10 AWG ground and the total becomes 0.1309 in², or 43.06%, so the run needs 3/4 in.

Nine 12 AWG THHN in 1/2 in EMT use 0.1197 in², just under the 0.122 in² limit. A tenth wire of the same size for the ground brings it to 0.1330 in². Note 7 can't save it, since 0.122 ÷ 0.0133 is 9.17, so the answer is still nine wires.

A bare stranded ground is smaller than an insulated one. A 10 AWG bare wire is 0.011 in² against 0.0211 in² for green THHN, per NEC Table 8.

With three 6 AWG THHN in 3/4 in EMT, a stranded bare ground drops fill from 32.50% to 30.60%. Solid bare 10 AWG is 0.008 in², which brings it to 30.04%, so check what goes on the reel.

Al Werning counts the bare ground in his worked EMT example for EC&M's guide to Chapter 9, using the Table 8 area for an 8 AWG bare conductor.

EMT, PVC and Rigid at the Same Trade Size

Trade size is a name, not a measurement. A 3/4 in raceway ranges from 0.722 in inside diameter for PVC Schedule 80 to 0.910 in for PVC Type A, and the wire count swings with it.

Conduit type3/4 in inside diameter3/4 in total area40% area12 AWG THHN in 1/2 in12 AWG THHN in 3/4 in12 AWG THHN in 1 in
EMT0.824 in0.533 in²0.213 in²91626
RMC (rigid)0.836 in0.549 in²0.220 in²91626
IMC0.864 in0.586 in²0.235 in²101729
FMC (flex)0.824 in0.533 in²0.213 in²91624
LFMC (liquidtight)0.830 in0.541 in²0.216 in²91626
ENT0.760 in0.454 in²0.181 in²71323
PVC Schedule 400.804 in0.508 in²0.203 in²81525
PVC Schedule 800.722 in0.409 in²0.164 in²61220
PVC Type A0.910 in0.650 in²0.260 in²111932

A PVC conduit fill calculator answer can't be copied onto EMT, and the reverse holds too. In 1/2 in, Schedule 80 holds 6 wires of 12 AWG where EMT holds 9.

HDPE uses the Schedule 40 dimensions in NEC Table 4, so Schedule 40 conduit fill calculator figures apply to it.

An EMT conduit fill calculator count also holds for rigid from 1/2 to 1 in, since the RMC bore is within 0.014 in of EMT at those sizes.

Flex is not always equal to EMT either. At 3/4 in the two match, but 1 in FMC has a 1.020 in bore against 1.049 in for EMT, so it holds 24 wires of 12 AWG instead of 26.

For EMT jobs, this is the THHN conduit fill calculator chart most people want. It counts same-size wires at the 40% limit with the Note 7 round-up.

THHN size1/2 in EMT3/4 in EMT1 in EMT1-1/4 in EMT1-1/2 in EMT2 in EMT
14 AWG1222356184138
12 AWG916264561101
10 AWG51016283863
8 AWG369162236
6 AWG247111626
4 AWG12471016
2 AWG1135711
1/0 AWG111347

The 6 AWG count in 1/2 in shows two Table 1 rules at work. Three won't fit, and two get only 31%, so the second 6 AWG fits only because 0.094 ÷ 0.0507 is 1.85, which Note 7 rounds up to two.

Insulation Type Changes the Wire Count

Insulation, not copper, decides most of the area at small sizes. A 12 AWG wire takes 0.0133 in² as THHN but 0.0353 in² as RHW-2 with an outer cover, so the same 3/4 in EMT holds 16 or 6.

Settle the insulation before any conduit fill calculator check, since 12 AWG XHHW-2 takes 36% more room than THHN.

Wire sizeTHHN / THWN-2XHHW-2TW, THW, THHW, THW-2RHW-2 with cover
14 AWG0.0097 in², 22 wires0.0139 in², 15 wires0.0139 in², 15 wires0.0293 in², 7 wires
12 AWG0.0133 in², 16 wires0.0181 in², 11 wires0.0181 in², 11 wires0.0353 in², 6 wires
10 AWG0.0211 in², 10 wires0.0243 in², 8 wires0.0243 in², 8 wires0.0437 in², 5 wires
8 AWG0.0366 in², 6 wires0.0437 in², 5 wires0.0437 in², 5 wires0.0835 in², 2 wires
6 AWG0.0507 in², 4 wires0.0590 in², 3 wires0.0726 in², 3 wires0.1041 in², 1 wire

Counts are for 3/4 in EMT at the 40% limit. Areas come from NEC Chapter 9 Table 5, reproduced in this ICC Table 5 sample.

THW from 14 to 8 AWG is a known trap. Table 5 lists THW, THHW and THW-2 at the TW areas, 0.0139 in² for 14 AWG. The 0.0209 in² figure belongs to RHH and RHW without an outer cover.

A conduit fill calculator chart that lists 14 AWG THW at 0.0209 in² puts 10 wires in 3/4 in EMT instead of 15. Electricians on the ECN forum traced the same mix-up to the THW rows of Annex C.

Sizing Conduit for Mixed Wire Sizes

For mixed sizes, add every wire's Table 5 area, then find the first trade size whose 40% area is equal or larger. Dividing the total by 0.40 gives the smallest total inside area that can work.

Single-size charts can't mix gauges, so mixed runs need a summed-area conduit fill calculator check. Leave out the Note 7 round-up, which only applies when every wire is the same size.

Here F is fill in percent, n is the number of wires of each size, A is the area of one wire from Table 5 or Table 8, and Ac is the conduit's total inside area from Table 4.

Take three 4 AWG THHN, one 6 AWG THHN neutral and one 8 AWG THHN ground. The total is 3 × 0.0824 + 0.0507 + 0.0366 = 0.3345 in² (215.8 mm²). That needs at least 0.3345 ÷ 0.40 = 0.836 in² of conduit.

Conduit40% area at 1 inFill at 1 inSmallest that passes
EMT0.346 in²38.72%1 in
RMC0.355 in²37.71%1 in
PVC Schedule 400.333 in²40.20%1-1/4 in, 23.02%
PVC Schedule 800.275 in²48.62%1-1/4 in, 27.04%

The 1 in Schedule 40 run misses by 0.0015 in², a gap no puller would notice. Note 7 can't round it in because the sizes are mixed, so the code answer is 1-1/4 in.

The same sum works in a spreadsheet, the logic behind any conduit fill calculator Excel sheet. Use one row per wire size, multiply quantity by Table 5 area, total the rows, then divide by 0.40.

A circuit upsized for distance changes this math. If the Voltage Drop Calculator pushes 10 AWG to 8 AWG on a long run, rerun the conduit fill calculator total with the larger area before buying pipe.

Cat 6, Fire Alarm and Low-Voltage Cable Fill

A multiconductor cable counts as one wire under Chapter 9 Note 9, sized by its outside diameter. A flat or oval cable uses its widest dimension as the circle diameter, so read the OD from the cable spec sheet.

Here d is the cable's outside diameter and A is the area that goes into the fill total. A 0.25 in (6.4 mm) cable covers 0.0491 in².

Cable OD1/2 in EMT3/4 in EMT1 in EMT1-1/4 in EMT1-1/2 in EMT2 in EMT
0.20 in (5.1 mm)4611192642
0.25 in (6.4 mm)247121627
0.30 in (7.6 mm)13581119

Note 7 makes small cable counts uneven. For a 0.20 in cable, 0.122 ÷ 0.0314 is 3.88 in 1/2 in EMT, which rounds up to 4. In 3/4 in it is 6.78, which rounds down to 6.

The same Note 9 method covers a fire alarm conduit fill calculator count and a Cat 6 or Cat 6A run. Cat 6 and Cat 6A ODs vary by brand and jacket rating, so use the figure for the exact cable on the reel.

For a low voltage conduit fill calculator job with mixed cables, add each cable's circle area and hold the total to 40%. Cable OD is all a conduit fill calculator by diameter needs, since Note 9 ignores the conductors inside.

A single large cable can fill 53%. The biggest single cable allowed is 0.453 in OD in 1/2 in EMT, 0.600 in in 3/4 in and 0.764 in in 1 in EMT.

Jam Ratio and the 360 Degree Bend Limit

Three single conductors can jam at a bend when 1.05 times the conduit ID divided by the wire OD falls between 2.8 and 3.2. A conduit fill calculator pass is not a pull check: three 8 AWG in 1/2 in EMT sit at 36.12% fill and a 3.02 jam ratio.

D is the conduit's inside diameter and d is one conductor's outside diameter. The 1.05 factor allows for the oval shape of the raceway at bends, as John DeDad explains in EC&M's cable pulling calculations.

Three THHNEMT sizeFillJam ratioJam ratio one size up
8 AWG1/2 in36.12%3.024.01
3 AWG1 in33.78%3.134.12
2 AWG1 in40.21%2.873.77
1/0 AWG1-1/4 in37.20%2.983.48
3/0 AWG1-1/2 in39.47%2.893.72
250 kcmil2 in35.49%3.054.03
500 kcmil2-1/2 in36.22%3.023.71

Three 2 AWG in 1 in EMT is the worst case on the list. It reaches 40.21% and passes only through the Note 7 round-up, then lands at a jam ratio of 2.87. One size up clears both problems.

The ratio matters most for exactly three wires. NEC Chapter 9 Informational Note 2 says jamming can still occur with four or more, but the chance is very low.

Bends add a separate limit that no conduit fill calculator percentage reflects. EMT, rigid and PVC rules (358.26, 344.26 and 352.26) allow no more than 360° between pull points.

Two 90° bends, two 30° offsets and a 45° three-bend saddle add up to 390°, so that run needs a pull point partway along.

Offsets count both bends and saddles count every bend. The Offset Bend Calculator and Saddle Bend Calculator give each angle. Past 360°, a box sized with the Pull Box Sizing Calculator resets the count.

Derating After Three Current-Carrying Wires

A conduit fill calculator result tells you what fits, not what the wires can carry. Under NEC 310.15(C)(1), four to six current-carrying wires drop to 80% ampacity, seven to nine to 70%, and ten to twenty to 50%.

EMT sizeMost 12 AWG THHNAdjustment12 AWG ampacity (30 A base)Fine for 20 A breakers?
1/2 in970%21 AYes
3/4 in1650%15 ANo
1 in2645%13.5 ANo
1-1/4 in4535%10.5 ANo

Sixteen 12 AWG in 3/4 in EMT is a legal conduit fill calculator answer but useless on 20 A circuits. Past nine current-carrying 12 AWG wires, step up to 10 AWG, which drops from 40 A to 20 A at the 50% factor.

The base figures are the 90 °C THHN column of Table 310.16, and the result still can't exceed the terminal rating. The Wire Ampacity Calculator runs the full temperature and bundling correction.

Grounds never count as current-carrying. Under 310.15(E), a neutral that carries only the unbalanced current of its own circuit doesn't count either, so a 120/240 V multiwire circuit adds two, not three.

Answers on NEC Fill, Percentage and Sizing

Areas below are in square inches. Multiply by 645.16 for square millimeters, and note that metric wire sizes such as 2.5 mm² describe copper only. Convert with the AWG to mm² Calculator, then use the insulated area for fill.

Is this online Conduit Fill calculator compatible with the NEC?

A conduit fill calculator result is NEC-compatible when it uses Chapter 9 Table 1 fill limits, Table 4 conduit areas, Table 5 and Table 8 wire areas, and Notes 4, 7 and 9. Every table above uses those sources, with grounds sized from Table 250.122.

The edition your jurisdiction adopted and the local inspector have the final say. The code text itself is published by the NFPA as NFPA 70, the National Electrical Code.

How do I calculate Conduit Fill?

Add the area of every wire, ground included, and divide by the conduit's total inside area, the hand version of any conduit fill calculator result. Three 10 AWG THHN plus a 10 AWG ground total 4 × 0.0211 = 0.0844 in² (54.5 mm²).

In 3/4 in EMT, with 0.533 in² (344 mm²) inside, the fill is 0.0844 ÷ 0.533 × 100 = 15.83%. The limit for four wires is 40%, or 0.213 in², so 0.1286 in² of room is left.

What is a Conduit Fill percentage?

It is the share of the conduit's inside cross-section taken by wire insulation and copper. A 15.83% result means 15.83% of the bore is wire and 84.17% is air.

The code ceiling is 53%, 31% or 40% by wire count, and 60% for nipples. A conduit fill calculator percentage near the ceiling is legal, but expect a hard pull and more heat in the bundle.

How do I choose a conduit size?

Conduit sizing runs the conduit fill calculator math backward. Divide the total wire area by 0.40 for three or more wires, then take the first Table 4 trade size whose total area is at least that number.

For the 0.3345 in² mixed run above, that is 0.836 in², so 1 in EMT at 0.864 in² is the first size that works.

Then check the pull. If three equal wires land at a jam ratio of 2.8 to 3.2, or the run tops 360° of bends, go up one size. The Box Fill Calculator covers the boxes at each end, which follow their own volume rules.