Door header size calculator for exterior, interior and nonbearing walls, with header size, jack and king studs and cut length from IRC R602.7 by rough opening, snow and floor load.
Pick what sits on the wall above the opening, then the opening width.
Snow, Header Build and Bracing
Header Span Table for This Wall
| Header Size | Max Span | Jack Studs | Spans 38 in |
|---|---|---|---|
| 1-2×6 | 2 ft 11 in | 2 each end | No |
| 1-2×8 | 3 ft 8 in | 2 each end | Yes |
| 1-2×10 | 4 ft 5 in | 2 each end | Yes |
| 1-2×12 | 5 ft 1 in | 3 each end | Yes |
| 2-2×4 | 2 ft 11 in | 1 each end | No |
| 2-2×6 | 4 ft 4 in | 1 each end | Yes |
| 2-2×8 | 5 ft 5 in | 2 each end | Yes |
| 2-2×10 | 6 ft 5 in | 2 each end | Yes |
| 2-2×12 | 7 ft 8 in | 2 each end | Yes |
| 3-2×8 | 6 ft 10 in | 1 each end | Yes |
| 3-2×10 | 8 ft 1 in | 2 each end | Yes |
| 3-2×12 | 9 ft 6 in | 2 each end | Yes |
| 4-2×8 | 7 ft 10 in | 1 each end | Yes |
| 4-2×10 | 9 ft 4 in | 1 each end | Yes |
| 4-2×12 | 11 ft | 2 each end | Yes |
Header Size Chart by Opening
| Rough Opening | 2-Ply Pick | Jacks | Lightest Any Build | Jacks |
|---|---|---|---|---|
| 2 ft | 2-2×4 | 1 | 1-2×6 | 2 |
| 2 ft 6 in | 2-2×4 | 1 | 1-2×6 | 2 |
| 2 ft 10 in (32 in door) | 2-2×4 | 1 | 1-2×6 | 2 |
| 3 ft 2 in (36 in door) | 2-2×6 | 1 | 1-2×8 | 2 |
| 4 ft | 2-2×6 | 1 | 1-2×10 | 2 |
| 5 ft | 2-2×8 | 2 | 1-2×12 | 3 |
| 6 ft | 2-2×10 | 2 | 2-2×10 | 2 |
| 8 ft | Engineered | -- | 3-2×10 | 2 |
| 9 ft | Engineered | -- | 3-2×12 | 2 |
| 10 ft | Engineered | -- | 4-2×12 | 2 |
| 12 ft | Engineered | -- | Engineered | -- |
| 16 ft | Engineered | -- | Engineered | -- |
Header Framing Diagram
Step-by-Step Sizing
- Rough opening = door width 36 in + 2 in = 38 in (prehung door rule).
- Table R602.7(1), roof and ceiling, 30 psf snow column (ground snow 30 psf), building width 28 ft.
- Spans interpolated between the 24 and 36 ft columns (note c), rounded down to the inch; the larger jack count is kept.
- Header top braced by framing above, so tabulated spans apply (note f).
- Double-ply sizes checked: 2-2×4 spans 2 ft 11 in (too short), 2-2×6 spans 4 ft 4 in (fits).
- Cut length = 38 in + 2 × 1 jack × 1½ in = 41 in.
- King studs: Table R602.7.5 gives one per end for this span and wind column.
- Result: 2-2×6 Header.
Door Header Size Calculator Answers for Standard Doors
A standard 36 in exterior door under a roof-only load needs a double 2×6 header with one jack stud at each end. That answer comes from the 38 in rough opening, not the 36 in door slab, and that slip undersizes more door headers than any other input.
Every size below is read from IRC 2021 Tables R602.7(1) and R602.7(2), which the 2024 edition repeats unchanged, for a 28 ft wide house, 30 psf ground snow, a braced header top and No. 2 lumber. The 28 ft spans are interpolated between the 24 and 36 ft columns and rounded down, as note c allows.
| Door or Opening | Rough Opening | Exterior, Roof Only | Exterior, Roof + 1 Floor | Interior, 1 Floor | Interior, 2 Floors | Exterior King Studs |
|---|---|---|---|---|---|---|
| 24 in door | 26 in | 2-2×4, 1 jack | 2-2×4, 1 jack | 2-2×4, 1 jack | 2-2×6, 2 jacks | 1 |
| 28 in door | 30 in | 2-2×4, 1 jack | 2-2×6, 2 jacks | 2-2×4, 1 jack | 2-2×6, 2 jacks | 1 |
| 30 in door | 32 in | 2-2×4, 1 jack | 2-2×6, 2 jacks | 2-2×4, 1 jack | 2-2×6, 2 jacks | 1 |
| 32 in door | 34 in | 2-2×4, 1 jack | 2-2×6, 2 jacks | 2-2×6, 1 jack | 2-2×8, 2 jacks | 1 |
| 36 in door | 38 in | 2-2×6, 1 jack | 2-2×6, 2 jacks | 2-2×6, 1 jack | 2-2×8, 2 jacks | 1 |
| 4 ft opening | 48 in | 2-2×6, 1 jack | 2-2×8, 2 jacks | 2-2×6, 1 jack | 2-2×10, 2 jacks | 1 |
| 5 ft opening | 60 in | 2-2×8, 2 jacks | 2-2×10, 2 jacks | 2-2×8, 2 jacks | 3-2×10, 2 jacks | 2 |
| 6 ft opening | 72 in | 2-2×10, 2 jacks | 2-2×12, 2 jacks | 2-2×10, 2 jacks | 3-2×12, 2 jacks | 2 |
| 8 ft opening | 96 in | 3-2×10, 2 jacks | 3-2×12, 2 jacks | 3-2×12, 2 jacks | Engineered | 2 |
| 9 ft garage door | 108 in | 3-2×12, 2 jacks | 4-2×12, 2 jacks | 4-2×12, 2 jacks | Engineered | 3 |
| 16 ft garage door | 192 in | Engineered | Engineered | Engineered | Engineered | 4 |
The floor column assumes a center-bearing wall inside the house. A clear-span floor, where joists run from wall to wall, pushes a 36 in door from 2-2×6 to 2-2×8 once the house passes 28 ft wide.
For the 28 to 36 in doors in most homes, a typical door header is a double 2×4 or 2×6 under roof only and a double 2×6 or 2×8 under a floor. A door header size calculator mainly earns its keep on the openings past 4 ft.
From 5 ft up, some loads have no double 2× header that reaches, so a triple or quad build appears. A triple 2× with two ½ in spacers is 5½ in thick and fits a 2×6 wall; a quad is 6 in thick and stands ½ in proud of it.
King studs in each door header size calculator answer above follow Table R602.7.5 for wind under 140 mph in Exposure B or 130 mph in Exposure C. Where the design wind is 115 mph or less in Exposure B, openings up to 8 ft need only one king per end.
Rough Opening Before Any Header Size
For a prehung door, the rough opening is the door width plus 2 in, so a 32 in door frames to 34 in and a 36 in door to 38 in. Check the unit's install sheet, since some patio and fire-rated doors call for a different allowance.
That 38 in figure, not 36 in, is the width to carry into a door header size calculator for a 36 in prehung door. A 2 in error at this step is enough to push a header one size short.
Measure between the jack studs, not between the king studs. The king-to-king width also includes every jack, and sizing from it overstates the span by 3 in with one jack per end or 6 in with two.
The header itself is cut to the rough opening plus the thickness of the jacks it sits on at both ends, so its length grows with the jack count:
Here Lcut is the header length in inches, RO is the rough opening and nj is the jack count per end from the span table. Each jack is a 2× stud 1½ in thick, and the result is the length to cut once a door header size calculator has set the size and jack count.
For a 36 in exterior door with a 2-2×6 header and one jack per end, the cut is 38 + 3 = 41 in. Two 41 in pieces come out of one 8 ft 2×6 with 14 in left over, plus a 41 in strip of ½ in plywood or OSB for the spacer.
A 6 ft opening with a 2-2×10 and two jacks per end cuts to 72 + 6 = 78 in. Two of those need 156 in of 2×10, so one 14 ft board covers the header with a foot to spare. The Lumber Calculator and Board Foot Calculator carry those pieces into a full order.
Rule of Thumb vs IRC Span Tables
The d × 12 rule says a header of nominal depth d in inches spans d × 12 inches, so a 4×4 spans 4 ft and a 4×6 spans 6 ft. Against the IRC table, that rule undersizes almost every bearing door header.
It is the shortcut behind many quick door header size calculator answers online. The rule ignores snow, floors above and building width, which are the three things the code table is built on. The comparison below uses a 28 ft wide house at 30 psf snow with a braced header top.
| Rough Opening | d × 12 Size | Code Span of That Size, Roof Only | Code Size, Roof Only | Code Size, Roof + 1 Floor |
|---|---|---|---|---|
| 36 in | 4×4 (2-2×4) | 2 ft 11 in, fails | 2-2×6 | 2-2×6 |
| 48 in | 4×4 (2-2×4) | 2 ft 11 in, fails | 2-2×6 | 2-2×8 |
| 60 in | 4×6 (2-2×6) | 4 ft 4 in, fails | 2-2×8 | 2-2×10 |
| 72 in | 4×6 (2-2×6) | 4 ft 4 in, fails | 2-2×10 | 2-2×12 |
| 96 in | 4×8 (2-2×8) | 5 ft 5 in, fails | 3-2×10 | 3-2×12 |
| 120 in | 4×10 (2-2×10) | 6 ft 5 in, fails | 4-2×12 | Engineered |
| 144 in | 4×12 (2-2×12) | 7 ft 8 in, fails | Engineered | Engineered |
The only case where the rule held was a 36 in opening in a 24 ft wide house carrying roof only, where a 2-2×4 reaches 3 ft 1 in. Add a floor or widen the house and the same header falls short.
So a 4×6 header spans 6 ft only by the rule. Under the IRC, a 2-2×6 in a 28 ft house reaches 4 ft 4 in under roof alone and 3 ft 7 in with one floor above. Any door header size calculator built on d × 12 alone will hand back a header the inspector can reject.
Header Span Size Chart by Load
For a door header size calculator check by hand, read across a row to see how far one header reaches as the load grows. Spans are for a 28 ft wide house with a braced top, with the jack count per end in brackets.
| Header | Roof Only, 30 psf | Roof Only, 70 psf | Roof + 1 Floor, Center Bearing | Roof + 1 Floor, Clear Span | Interior, 1 Floor | Interior, 2 Floors |
|---|---|---|---|---|---|---|
| 2-2×4 | 2 ft 11 in (1) | 2 ft 2 in (1) | 2 ft 4 in (1) | 2 ft 1 in (1) | 2 ft 8 in (1) | 1 ft 9 in (1) |
| 2-2×6 | 4 ft 4 in (1) | 3 ft 3 in (2) | 3 ft 7 in (2) | 3 ft 2 in (2) | 4 ft 0 in (1) | 2 ft 9 in (2) |
| 2-2×8 | 5 ft 5 in (2) | 4 ft 2 in (2) | 4 ft 7 in (2) | 4 ft 0 in (2) | 5 ft 1 in (2) | 3 ft 5 in (2) |
| 2-2×10 | 6 ft 5 in (2) | 4 ft 11 in (2) | 5 ft 4 in (2) | 4 ft 8 in (2) | 6 ft 1 in (2) | 4 ft 1 in (2) |
| 2-2×12 | 7 ft 8 in (2) | 5 ft 10 in (3) | 6 ft 4 in (2) | 5 ft 7 in (3) | 7 ft 1 in (2) | 4 ft 10 in (3) |
| 3-2×8 | 6 ft 10 in (1) | 5 ft 2 in (2) | 5 ft 8 in (2) | 4 ft 11 in (2) | 6 ft 5 in (1) | 4 ft 4 in (2) |
| 3-2×10 | 8 ft 1 in (2) | 6 ft 2 in (2) | 6 ft 9 in (2) | 5 ft 11 in (2) | 7 ft 7 in (2) | 5 ft 2 in (2) |
| 3-2×12 | 9 ft 6 in (2) | 7 ft 4 in (2) | 8 ft 0 in (2) | 7 ft 0 in (2) | 8 ft 11 in (2) | 6 ft 0 in (2) |
| 4-2×12 | 11 ft 0 in (2) | 8 ft 5 in (2) | 9 ft 2 in (2) | 8 ft 0 in (2) | 10 ft 4 in (2) | 7 ft 0 in (2) |
Before trusting a 2×8 from any door header size calculator, confirm it is doubled for a 2×4 wall. Built that way, and a 2-2×8 reaches 5 ft 5 in under roof only. The same pair drops to 3 ft 5 in in an interior wall under two floors, which still clears a 36 in door.
All four lumber groups in the table, Douglas fir-larch, hem-fir, Southern pine and spruce-pine-fir, share one set of spans per note b, so species does not change a door header size calculator answer among those four. A grade below No. 2 is outside the table and needs a designed header.
Exterior Door Header Size Chart for a 36 in Door
Snow load and building width move a 36 in exterior door header more than most framers expect. The 38 in rough opening below runs through all five exterior load rows of Table R602.7(1), each as a double 2× header.
| Ground Snow | Building Width | Roof Only | +1 Floor, Center Bearing | +1 Floor, Clear Span | +2 Floors, Center Bearing | +2 Floors, Clear Span |
|---|---|---|---|---|---|---|
| 30 psf | 24 ft | 2-2×6, 1 jack | 2-2×6, 1 jack | 2-2×6, 2 jacks | 2-2×6, 2 jacks | 2-2×8, 2 jacks |
| 30 psf | 36 ft | 2-2×6, 1 jack | 2-2×6, 2 jacks | 2-2×8, 2 jacks | 2-2×8, 2 jacks | 2-2×10, 3 jacks |
| 50 psf | 24 ft | 2-2×6, 1 jack | 2-2×6, 2 jacks | 2-2×6, 2 jacks | 2-2×8, 2 jacks | 2-2×8, 2 jacks |
| 50 psf | 36 ft | 2-2×6, 2 jacks | 2-2×8, 2 jacks | 2-2×8, 2 jacks | 2-2×8, 2 jacks | 2-2×10, 3 jacks |
| 70 psf | 24 ft | 2-2×6, 2 jacks | 2-2×6, 2 jacks | 2-2×8, 2 jacks | 2-2×8, 2 jacks | 2-2×8, 2 jacks |
| 70 psf | 36 ft | 2-2×8, 2 jacks | 2-2×8, 2 jacks | 2-2×8, 2 jacks | 2-2×10, 3 jacks | 2-2×10, 3 jacks |
Building width is measured perpendicular to the ridge, per note c. On a gable house that is the eave-to-eave depth, which sets how much roof bears on the long walls where most entry doors sit. That eave-to-eave figure is the width a door header size calculator needs for those walls.
Treat snow load and building width as measured inputs, not guesses, for any exterior door header size calculator lookup.
Snow columns are not interpolated. A 40 psf site reads the 50 psf column, and a site under 30 psf may use the 30 psf column only when the roof live load is 20 psf or less, per note e.
Your local ground snow load comes from the building department or the ground snow map in IRC Section R301.2. In a load bearing wall, a door header size calculator result is only as good as that number and the floor count above it.
Interior Door Header Size in Bearing Walls
An interior door header size calculator lookup starts with the floor count above, not the snow load.
An interior bearing wall carries floors, not roof snow, so its header is read from Table R602.7(2) by the number of floors above. A standard 32 in interior door under one floor needs a 2-2×6 with one jack; under two floors it needs a 2-2×8 with two.
The span chart above shows the full interior range. Under one floor a 2-2×10 reaches 6 ft 1 in at 28 ft width, while under two floors no double header clears a 5 ft opening and a 3-2×10 in a 2×6 wall takes over.
Inside the house, each header end gets one full-height stud end-nailed to it, per R602.7.5. The king stud table with its wind columns applies only to exterior walls, so an interior door header size calculator answer calls for one king per end.
The floor framing that loads the wall also sets which row to read. The Floor Joist Calculator shows joist direction and span, which tells you whether a hallway wall needs a door header size calculator check at all.
Jack Studs and King Studs for Each Header
A door header needs the jack count printed beside its span in the NJ column, which runs from one to four per end in the IRC tables. Heavier loads and longer spans raise the count because each added jack gives the header end more bearing area.
Count jacks before cutting. With two jacks per end in a door header size calculator result, the header grows 6 in longer and the opening takes two more studs.
Where the table calls for one jack, note d allows an approved framing anchor on the full-height stud in its place. That swap moves the king count to the wind-under-140 mph column, per note b of Table R602.7.5.
| Maximum Header Span | Under 140 mph B or 130 mph C | 115 mph or Less, Exposure B |
|---|---|---|
| 4 ft | 1 | 1 |
| 6 ft | 2 | 1 |
| 8 ft | 2 | 1 |
| 10 ft | 3 | 2 |
| 12 ft | 3 | 2 |
| 14 ft | 3 | 2 |
| 16 ft | 4 | 2 |
| 18 ft | 4 | 2 |
For a door header size calculator king count, the design wind speed and exposure category on your permit set the column to read.
Spans between the rows take the larger row, so a 5 ft opening in a normal-wind zone gets two kings per end.
A site above 140 mph in Exposure B, or above 130 mph in C, sits outside this table. The header size still comes from Table R602.7(1), but the king studs and header connections need a wind design.
Table R602.3(1) sets the nailing. Each full-height stud is end-nailed to the header with 3-16d common or 4-16d box nails, and the plies of a built-up header are face-nailed with 16d common at 16 in on center along each edge.
The kings and jacks add to the stud count for the wall. The Framing Calculator counts studs and plates for the run around each opening.
Built-Up Plies and Single-Member Headers
A door header in a 2×4 wall takes two 2× boards with a ½ in spacer, which makes 3½ in and matches the stud depth. A 2×6 wall takes three boards and two ½ in spacers for 5½ in.
That answers how many 2×4 or 2×6 go in a door header: two boards in a 2×4 wall, three in a 2×6 wall, all the same depth. The board depth, 2×4 up through 2×12, is what the span table sets.
In a 2×6 wall, the triple rows are the ones to read in a door header size calculator lookup, since three plies fill the wall depth without foam or furring.
IRC 2021 also lists single-ply headers. Under R602.7.1, a single header needs a flat 2× plate as wide as the studs on its top and bottom, face-nailed with 10d box nails at 12 in on center. A single-ply door header size calculator result is only code-legal with those flat plates in place.
For a 36 in door in a 28 ft house under roof only, a single 1-2×8 works but needs two jacks per end. A 2-2×6 needs one. The single board leaves the space behind it open for insulation, while the double saves a jack and takes less height above the door.
Under one floor, the single-ply choice for the same door grows to a 1-2×10 with three jacks per end. At that point most framers go back to the double 2×6 and its two jacks.
Cripple Studs Above the Header Change the Span
When short cripple studs sit on the header instead of floor or ceiling framing bearing on it directly, the header top is not braced. Note f then multiplies every 2×8, 2×10 and 2×12 span by 0.70, so a door header size calculator lookup for that wall has to use the reduced span.
The cut is steep. In a 28 ft house under roof only, a 2-2×8 drops from 5 ft 5 in to 3 ft 9 in, and a 2-2×10 from 6 ft 5 in to 4 ft 5 in.
In door header size calculator terms, a 5 ft opening that takes a 2-2×8 with a braced top needs a 2-2×12 with cripples above it. A 6 ft opening, a 2-2×10 when braced, needs a triple 3-2×12 once cripples bear on it.
The 0.70 factor skips 2×4 and 2×6 headers, so a 36 in door with a 2-2×6 keeps its 4 ft 4 in span either way. Tall walls and wide openings are where cripples, and the 0.70 cut, change a door header size calculator answer most.
Garage and Patio Door Header Size
Every 16 ft garage door header size calculator lookup against the IRC ends at an engineered beam, because the longest sawn header in Table R602.7(1) is a 4-2×12 at 15 ft 3 in. That figure is for a 12 ft wide building with roof only; at 28 ft wide it drops to 11 ft 0 in.
Overhead doors are framed to at least the door's own width, so any garage door header size calculator answer for a two-car opening points to LVL, PSL or glulam. Size those from the maker's published header tables or have a design professional do it.
A 9 ft single garage door is the widest common door that a door header size calculator can still answer with sawn lumber. In a 28 ft wide garage carrying roof only at 30 psf, a 3-2×12 with two jacks per end spans it; a 4-2×12 takes over at 50 psf.
A patio door header size chart reads the same as any door chart, since only the rough opening changes. A 6 ft patio door opening of 72 to 74 in takes a 2-2×10 with two jacks in a 28 ft house under roof only. An 8 ft opening of 96 in needs a triple 3-2×10 under roof alone, which is a 2×6 wall detail.
For any opening past the sawn tables, where no door header size calculator lookup in the IRC finds a fit, the Wood Beam Span Calculator shows how depth and load trade off before you price an engineered beam. The Lumber Weight Calculator gives the lift weight of a long built-up header.
Nonbearing Walls and the Flat 2×4 Header
A wall that carries no roof, ceiling or floor needs no load-bearing header, per IRC R602.7.4. One flat 2×4 can head an opening up to 8 ft wide when the nailing surface above it sits within 24 in.
No cripples or blocking are needed over that flat 2×4. The difference between a load-bearing and non-load-bearing header is that the first is sized from a span table and sits on jacks, while the second only gives drywall and trim a nailing edge.
The 24 in gap is where wall height matters. With an 80 in prehung door framed about 82½ in tall, a flat 2×4 leaves about 8⅝ in to the top plate on an 8 ft wall with 92⅝ in studs and about 20⅝ in on a 9 ft wall with 104⅝ in studs.
On a 10 ft wall with 116⅝ in studs, the gap grows to about 32⅝ in. The flat 2×4 allowance no longer applies, so the head needs cripples, blocking or an on-edge header your inspector accepts, even though no door header size calculator span check applies.
Before running a door header size calculator on a partition, confirm whether anything bears on it from the attic or the floor above.
A wall is nonbearing only when nothing rests on it. Joists, rafters, a beam or a girder truss bearing on the top plate make it a bearing wall, and the JLC guide to exterior wall headers walks through the same nonbearing rule and the bracing note.
Approval, LVL and Lintel Answers
These answers use the same IRC tables as every door header size calculator figure above, with a 28 ft wide house at 30 psf snow unless stated otherwise.
Is a door header size calculator a structural approval?
No calculator result is an approval. The IRC span tables are a prescriptive path that a building official accepts for one- and two-family homes inside their limits, which means No. 2 lumber, uniform loads, the listed snow loads and building widths up to 36 ft.
A point load from a girder or post above the opening, a wider building, or snow above 70 psf all fall outside those tables.
A permit and inspection are still how the header gets approved, and local amendments can change the tables. A door header size calculator answer outside those limits needs a design.
How do I use a door header size calculator?
Gather the facts first. You need the rough opening, whether the wall bears load, what sits above it (roof only, one floor or two), the ground snow load from your building department and the building width measured across the ridge.
Then read the result against the job. Confirm the jack count, add it to the cut length, check that the plies match your wall thickness and see whether cripples will bear on the header, since that cuts 2×8 to 2×12 spans by 30%.
How do I choose a door header?
Start with the smallest header that spans the opening at your load, then weigh fit. A 36 in door under roof only can take a 2-2×6 with one jack or a 1-2×8 with two, and both are legal in a 28 ft house.
The double fits a 2×4 wall and sits lower above the door. The single leaves room for insulation but adds a jack per end. Past the sawn tables, the choice becomes an LVL or other engineered header.
Can you use a 2×4 for a door header?
A double 2×4 is the smallest bearing size in any IRC-based door header size calculator table and a legal header for small doors. In a 28 ft house under roof only it spans 2 ft 11 in, enough for a 30 or 32 in door, but under two floors it reaches only 1 ft 9 in.
In a nonbearing wall, a single flat 2×4 heads an opening up to 8 ft wide, provided the framing above is within 24 in.
What is the difference between a header and a lintel?
A header is the horizontal member over an opening in a wood-framed wall, carried by jack studs. A lintel does the same job over an opening in masonry or concrete, usually as a steel angle or a reinforced concrete or masonry beam.
Brick veneer over a wood-framed opening often has both: a wood header for the framing and a steel angle lintel for the brick. For a door header size calculator, only the wood header counts, since the lintel is sized for the veneer.
Can I use LVL lumber for any door header?
LVL can head any door opening, but the IRC sawn-lumber tables do not cover it. An LVL header is sized from the manufacturer's tables, not an IRC-based door header size calculator, for the same load, span and bearing, and those tables also set the bearing length at each end.
LVL makes sense where sawn lumber runs out, such as a 16 ft garage door or a 6 ft opening under two floors, or where a deep built-up header will not fit the head height.
Does the 2024 IRC change door header sizes?
The spans and jack counts in IRC 2024 Table R602.7(1), R602.7(2) and R602.7.5 match the 2021 edition row for row, and notes c through f and Section R602.7.4 read the same. A door header size calculator built on the 2021 values gives the same header for a 2024 permit.
Your jurisdiction may still be on an older edition or carry local changes. The Fine Homebuilding header guide notes the exterior table moved into Chapter 6 in 2015, so older code books list header spans in Chapter 5.