Duct size calculator for HVAC supply and return ducts, sizing round, rectangular and flex duct from CFM at a friction rate or a velocity, then checking speed and friction over TEL.
Residential ducts are usually sized at 0.08 to 0.10 in. w.c. per 100 ft.
Duct Role and Total Effective Length
Round vs Rectangle, to Scale
Duct Size Chart at 0.08 in. w.c./100 ft
| Round Size | Sheet Metal | Velocity | Flex Duct | Duct Board |
|---|---|---|---|---|
| 4 in | 33 CFM | 375 FPM | 28 CFM | 29 CFM |
| 5 in | 60 CFM | 439 FPM | 51 CFM | 54 CFM |
| 6 in | 98 CFM | 499 FPM | 83 CFM | 88 CFM |
| 7 in | 148 CFM | 555 FPM | 126 CFM | 132 CFM |
| 8 in | 212 CFM | 608 FPM | 180 CFM | 189 CFM |
| 9 in | 291 CFM | 659 FPM | 247 CFM | 259 CFM |
| 10 in | 386 CFM | 707 FPM | 327 CFM | 344 CFM |
| 12 in | 628 CFM | 799 FPM | 532 CFM | 558 CFM |
| 14 in | 947 CFM | 885 FPM | 801 CFM | 841 CFM |
| 16 in | 1,350 CFM | 967 FPM | 1,142 CFM | 1,198 CFM |
| 18 in | 1,847 CFM | 1,045 FPM | 1,560 CFM | 1,636 CFM |
| 20 in | 2,442 CFM | 1,119 FPM | 2,062 CFM | 2,162 CFM |
| 22 in | 3,144 CFM | 1,191 FPM | 2,653 CFM | 2,782 CFM |
| 24 in | 3,958 CFM | 1,260 FPM | 3,339 CFM | 3,500 CFM |
| 28 in | 5,950 CFM | 1,392 FPM | 5,016 CFM | 5,256 CFM |
| 32 in | 8,466 CFM | 1,516 FPM | 7,132 CFM | 7,472 CFM |
| 36 in | 11,550 CFM | 1,634 FPM | 9,725 CFM | 10,186 CFM |
Rectangles Equal to 11.8 in Round
| Height | Width | Velocity | Aspect Ratio |
|---|---|---|---|
| 4 in | 40 in | 540 FPM | 10 to 1 |
| 6 in | 22 in | 655 FPM | 3.7 to 1 |
| 8 in | 16 in | 675 FPM | 2 to 1 |
| 10 in | 12 in | 720 FPM | 1.2 to 1 |
| 12 in | 10 in | 720 FPM | 1.2 to 1 |
| 14 in | 10 in | 617 FPM | 1.4 to 1 |
| 16 in | 8 in | 675 FPM | 2 to 1 |
| 18 in | 8 in | 600 FPM | 2.3 to 1 |
| 20 in | 8 in | 540 FPM | 2.5 to 1 |
Step-by-Step Duct Sizing Math
Duct Size Calculator Results for 600 CFM
A 600 CFM sheet metal duct sized at 0.08 in. w.c. per 100 ft needs an 11.8 in inside diameter, which rounds up to a 12 in round duct. In that duct size calculator result, air moves at 764 FPM and the 12 in size runs at 0.074 in. w.c. per 100 ft.
The same 600 CFM, or 1,019 m³/h and 283 L/s, needs 299.7 mm exact, which lands on the 300 mm metric spiral size in a duct size calculator check. In rectangular sheet metal it needs 16 × 8 in, and in fully stretched flex it needs 14 in.
Every friction-based duct size calculator result comes from the Darcy equation solved backward. The diameter is varied until the friction for the chosen airflow matches the target rate.
Δp is friction in in. w.c. per 100 ft, f is the Colebrook friction factor, D is inside diameter in inches, Q is airflow in CFM and A is the duct area in sq ft. The 4005 term sets standard air at 0.075 lb/ft³, per the ASHRAE duct design chapter.
Rounding up always lowers both speed and friction in a duct size calculator answer. An exact 11.8 in duct would sit at 0.08 in. w.c. and about 790 FPM, while the 12 in standard size carries up to 628 CFM before it reaches the 0.08 limit.
Over a run with a total effective length of 150 ft, the 12 in duct uses 0.11 in. w.c. of the blower's pressure. Double the effective length to 300 ft and it uses 0.22 in. w.c., which is why long runs need a lower design friction rate.
CFM to Duct Size Chart at 0.06, 0.08 and 0.10
A 6 in round sheet metal duct carries 98 CFM at 0.08 in. w.c. per 100 ft, an 8 in duct carries 212 CFM, and a 12 in duct carries 628 CFM.
Each row lists the duct size calculator capacity, meaning the most airflow a standard size carries at each common design friction rate.
| Round Duct | CFM at 0.06 | CFM at 0.08 | CFM at 0.10 | Velocity at 0.08 |
|---|---|---|---|---|
| 4 in | 28 | 33 | 37 | 375 FPM |
| 5 in | 51 | 60 | 68 | 439 FPM |
| 6 in | 83 | 98 | 111 | 499 FPM |
| 7 in | 126 | 148 | 168 | 555 FPM |
| 8 in | 181 | 212 | 240 | 608 FPM |
| 9 in | 248 | 291 | 329 | 659 FPM |
| 10 in | 329 | 386 | 436 | 707 FPM |
| 12 in | 536 | 628 | 709 | 799 FPM |
| 14 in | 810 | 947 | 1,068 | 885 FPM |
| 16 in | 1,155 | 1,350 | 1,523 | 967 FPM |
| 18 in | 1,581 | 1,847 | 2,082 | 1,045 FPM |
| 20 in | 2,091 | 2,442 | 2,753 | 1,119 FPM |
| 24 in | 3,392 | 3,958 | 4,460 | 1,260 FPM |
Read the chart from airflow to size by taking the first row whose CFM meets the need. A room branch of 120 CFM needs a 7 in duct at 0.08, and a 180 CFM branch needs 8 in, at 449 and 516 FPM.
Friction rate moves the answer more than most duct size charts admit. At 0.10, 400 CFM fits a 10 in duct at 733 FPM, but at 0.08 it needs 12 in. A 1,000 CFM trunk drops from 16 in to 14 in when the design rate rises from 0.08 to 0.10.
Duct size calculator figures based on cfm here assume sheet metal, standard air and straight duct. Tonnage converts at 400 CFM per ton, so the system totals for common equipment fall out directly.
| System | Airflow | Exact Diameter at 0.08 | Standard Round | Trunk Velocity |
|---|---|---|---|---|
| 1.5 ton | 600 CFM | 11.8 in | 12 in | 764 FPM |
| 2 ton | 800 CFM | 13.1 in | 14 in | 748 FPM |
| 2.5 ton | 1,000 CFM | 14.3 in | 16 in | 716 FPM |
| 3 ton | 1,200 CFM | 15.3 in | 16 in | 859 FPM |
| 4 ton | 1,600 CFM | 17.1 in | 18 in | 905 FPM |
| 5 ton | 2,000 CFM | 18.5 in | 20 in | 917 FPM |
Size the system airflow first with the AC Tonnage Calculator, then split it among rooms before any branch duct size calculator run. A single trunk size only covers the first run off the plenum.
Velocity Limits Overrule Friction on Big Trunks
ACCA Manual D caps residential supply trunks and branches at 900 FPM in rigid duct and 700 FPM in flex, and return ducts at 700 FPM. A duct size calculator answer based on 0.08 friction breaks the 900 FPM cap on 4 and 5 ton trunks.
| Duct | Supply Recommended | Supply Maximum | Return Recommended | Return Maximum |
|---|---|---|---|---|
| Trunk, rigid | 700 FPM | 900 FPM | 600 FPM | 700 FPM |
| Trunk, flex | 600 FPM | 700 FPM | 600 FPM | 700 FPM |
| Branch, rigid | 600 FPM | 900 FPM | 400 FPM | 700 FPM |
| Branch, flex | 600 FPM | 700 FPM | 400 FPM | 700 FPM |
The figures are Manual D Table 3-1 as reproduced in an AHRI Manual D checklist, which also lists 700 FPM for supply outlet faces, 500 FPM for return grilles and 300 FPM for filter grilles.
A 4 ton trunk at 1,600 CFM sized by friction lands on 18 in at 905 FPM, just over the cap. Holding 900 FPM needs an 18.1 in exact diameter, so the trunk goes to 20 in. A 5 ton trunk at 2,000 CFM moves from 20 in to 22 in for the same reason.
Below about 1,600 CFM, friction governs and velocity checks pass. Above it, size the trunk by velocity first, then confirm friction stays under the design rate in the duct size calculator check, since the larger duct always runs at lower friction.
Velocity sizing alone uses the area equation, D = 13.54 × √(CFM ÷ FPM). For 600 CFM, 900 FPM gives 11.1 in and a 12 in duct, while 600 FPM gives 13.5 in and a 14 in duct at 561 FPM, quieter but one size larger.
The Duct Velocity Calculator checks an existing size against these limits. One velocity does not suit the whole system, since branches near bedrooms run slower than a trunk in an attic or basement.
Available Static Pressure Sets the Friction Rate
Manual D sets the design friction rate from the blower pressure left after equipment losses, spread over the longest run.
With 0.20 in. w.c. available across 200 ft of total effective length, the rate is 0.10 in. w.c. per 100 ft, the starting input for every duct size calculator run.
FR is the design friction rate in in. w.c. per 100 ft, ASP is the available static pressure left for ducts in in. w.c., and TEL is the total effective length of the longest supply plus return run in feet, fittings included.
The AHRI worked example starts from a blower rated 0.70 in. w.c. at 1,200 CFM. A 0.23 coil, 0.18 filter, 0.03 supply outlet, 0.03 return grille and 0.03 dampers use 0.50, leaving 0.20 in. w.c. for the ducts.
| Available Static | TEL | Friction Rate | 600 CFM Exact | 600 CFM Round |
|---|---|---|---|---|
| 0.10 in. w.c. | 150 ft | 0.067 | 12.25 in | 14 in |
| 0.10 in. w.c. | 300 ft | 0.033 | 14.12 in | 16 in |
| 0.15 in. w.c. | 200 ft | 0.075 | 11.96 in | 12 in |
| 0.20 in. w.c. | 200 ft | 0.100 | 11.27 in | 12 in |
| 0.20 in. w.c. | 300 ft | 0.067 | 12.25 in | 14 in |
| 0.25 in. w.c. | 150 ft | 0.167 | 10.16 in | 12 in |
The common 0.08 to 0.10 rule only holds when the equipment leaves about 0.16 to 0.20 in. w.c. for 200 ft of effective length. A high-drop filter or a long attic run pushes the true rate to 0.067 or lower, and the 600 CFM trunk grows to 14 in.
A 0.25 in. w.c. budget on a short 150 ft system allows 0.167, yet 600 CFM still lands on 12 in, because a 10 in duct would need 0.18 and run at 1,100 FPM.
Use the Static Pressure Calculator to total the equipment drops before any duct size calculator run.
Rectangular Sizes Equal to a 12 in Round
A 16 × 8 in rectangle carries 600 CFM at or below the friction of the 11.8 in round, and so do 22 × 6, 12 × 10 and 40 × 4 in, each rounded up to whole inches. The flatter the shape, the more sheet metal it takes to move the same air.
De is the equivalent round diameter in inches, and W and H are the inside width and height. Equal De means equal friction and equal airflow, per the Huebscher equation used in the ASHRAE duct design chapter, not equal area.
| Height | Width | Aspect Ratio | Velocity at 600 CFM | Perimeter |
|---|---|---|---|---|
| 4 in | 40 in | 10 to 1 | 540 FPM | 88 in |
| 6 in | 22 in | 3.7 to 1 | 655 FPM | 56 in |
| 8 in | 16 in | 2 to 1 | 675 FPM | 48 in |
| 10 in | 12 in | 1.2 to 1 | 720 FPM | 44 in |
A 12 in round has a 37.7 in circumference against 48 in for the 16 × 8 and 88 in for the 40 × 4. That flat 40 × 4 needs 2.3 times the metal of the round, adds the most surface for heat gain and leakage, and still only matches its friction.
Equal friction does not mean equal area. The 16 × 8 in has 128 sq in against 113.1 sq in for the 12 in round, so a rectangular duct size calculator answer always carries more area than the round it replaces.
Converting by area picks the wrong round. A 22 × 6 in duct has the area of a 13 in circle, which rounds to 14 in, yet its friction matches an 11.9 in round, so a 12 in round carries the same air.
Sheet Metal, Duct Board and Flex Need Different Sizes
At 0.08 in. w.c. per 100 ft, 600 CFM needs 12 in sheet metal but 14 in duct board or fully stretched flex. Rougher inside surfaces add friction, so the same airflow needs more diameter in a duct size calculator result.
| Round Size | Sheet Metal CFM | Duct Board CFM | Flex, Fully Stretched CFM |
|---|---|---|---|
| 6 in | 98 | 88 | 83 |
| 7 in | 148 | 132 | 126 |
| 8 in | 212 | 189 | 180 |
| 10 in | 386 | 344 | 327 |
| 12 in | 628 | 558 | 532 |
| 14 in | 947 | 841 | 801 |
| 16 in | 1,350 | 1,198 | 1,142 |
These duct size calculator values use absolute roughness of 0.0003 ft for sheet metal, 0.0019 ft for duct board and 0.003 ft for flex.
The flex value is the medium rough category for fully extended nonmetallic flex in the ASHRAE Handbook, Fundamentals duct roughness table.
For duct board, a NAIMA white paper by IBACOS found 30% to 38% more pressure drop than sheet metal in an 8 × 10 in duct from 500 to 1,000 FPM. The 0.0019 ft value gives 22% to 30% over the same range.
Installed flex rarely stays stretched. Lawrence Berkeley National Laboratory tests found about 15% compression raised the pressure drop of 8 in flex about 4.2 times, which cuts its duct size calculator capacity at 0.08 from 180 CFM to about 85 CFM.
That gap is why flex branches are drawn one size up and pulled tight. A 300 CFM branch needs 10 in flex fully stretched, and a sagging run of the same size can deliver about half of it.
Return Ducts, Room CFM and Manual D Clarified
Duct size calculator answers below use sheet metal at 0.08 in. w.c. per 100 ft and standard air unless another material or rate is named.
What duct size do I need for a given CFM?
Match the airflow to the first round size that carries it at your design friction rate in a duct size calculator based on cfm. At 0.08, 100 CFM needs 7 in, 200 CFM needs 8 in, 400 CFM needs 12 in, 800 CFM needs 14 in and 1,200 CFM needs 16 in.
For 600 CFM duct size, the answer is 12 in round, 16 × 8 in rectangular or 14 in flex. Check velocity afterward, since trunks of about 1,600 CFM and up hit the 900 FPM cap before they reach the friction limit.
What friction rate should I use for a residential HVAC system?
Use the rate your blower can afford, found as available static pressure × 100 ÷ total effective length. Most residential designs land between 0.06 and 0.10 in. w.c. per 100 ft, with 0.08 a common starting point.
Friction rate is the pressure lost per 100 ft of straight duct and the main duct size calculator input. It is a budget, not a target, so a system with 0.15 in. w.c. available and 250 ft of effective length should be sized at 0.06.
How do I choose between sizing by friction rate or by velocity?
Size by friction rate first, then check velocity against Manual D limits and upsize when it fails. Friction sizing protects the blower's pressure budget, and velocity sizing protects against noise.
Use velocity alone only for short runs where friction is trivial, such as a plenum takeoff, or for noise-sensitive rooms, where 600 FPM instead of 900 FPM adds one size.
How do I size a return air duct?
Size returns to lower velocity than supplies, with Manual D recommending 600 FPM in trunks and 400 FPM in branches. A 600 CFM return at 600 FPM needs 13.5 in, so a 14 in duct, one size above the 12 in supply.
The return carries the full system airflow back through a filter, so its grille face also needs to stay near 300 FPM at a filter grille. The Return Air Duct Size Calculator covers the return path and grille sizing.
How do I calculate Total Equivalent Length (TEL)?
Add the straight length of the longest supply run and the longest return run, then add the equivalent length of every fitting along them from the Manual D fitting tables. Elbows and takeoffs often add more feet than the straight duct itself.
TEL matters because it sets the friction budget for every duct size calculator result. A 600 CFM run in 12 in duct uses 0.11 in. w.c. over 150 ft of TEL but 0.22 over 300 ft, which can exceed what the blower has left.
What is Manual D in HVAC?
ACCA Manual D is the ANSI-recognized procedure for residential duct design. It sets the friction rate from available static pressure and TEL, sizes each run from room airflow, and limits velocities by duct type.
Manual J comes first and gives each room's heating and cooling load, and Manual S selects the equipment. Without Manual J room loads, any duct size calculator result rests on guessed airflow and every downstream number inherits the guess.
How do I calculate duct size based on room square footage?
Square footage alone does not set a duct size calculator answer, since room airflow comes from the room's share of the load. A room carrying 10% of a 3 ton, 1,200 CFM load needs 120 CFM and a 7 in branch at 0.08.
Rooms of equal size can carry very different loads from windows, exposure and floor level. Get room CFM from a load calculation or the CFM Calculator, then size the branch from that airflow.
What happens if HVAC ducts are too small?
Velocity, noise and static pressure all climb. Pushing 600 CFM through a 10 in duct instead of 12 in raises velocity from 764 to 1,100 FPM and friction from 0.074 to 0.18 in. w.c. per 100 ft.
The blower then moves less air than designed or, on variable-speed motors, draws more power to hold it, which raises energy use, lowers capacity and can freeze an evaporator coil in cooling.
What is the difference between a ductulator and a duct calculator?
A ductulator is a slide rule printed with a friction chart for one roughness and standard air. A duct sizer in software solves the same Darcy and Colebrook math directly, so it can switch materials and units without separate charts.
Both should agree for sheet metal at standard air. A 12 in round reads about 628 CFM at 0.08 by either duct size calculator method, and differences of a few percent come from rounding on the printed scale.
How accurate are duct sizing calculator results?
The straight duct math matches the ASHRAE friction equations, so results are as good as the inputs. The largest errors come from guessed airflow, missing fittings in TEL and flex that is not fully stretched.
Rounding up to the next standard size adds margin to any duct size calculator result. The 600 CFM duct needs 11.8 in exact, and the 12 in standard size runs at 0.074 instead of 0.08 in. w.c., about 8% below the design rate.
What is static pressure in HVAC systems?
Static pressure is the resistance the blower pushes against, measured in inches of water column or pascals, where 1 in. w.c. equals 248.84 Pa.
Most residential blowers are rated for 0.50 in. w.c. total, and the ducts get what is left after the coil, filter, grilles and dampers, which sets the duct size calculator friction rate.