Duct Velocity Calculator

Updated

Duct Velocity Calculator for air speed from CFM and a round or rectangular duct size, airflow from a measured air speed, and the duct size for a target speed, with Manual D limits.

Airflow and Duct Size

Use the inside size of the duct, not the outside.

Duct Material and Run Length Galvanized Steel · 50 ft
Result Units FPM
Duct Velocity Result
733 FPM Duct Velocity
Velocity = airflow ÷ open area
3.73 m/s Same Speed
Feet per Second12.2 ft/s
Miles per Hour8.33 mph
The same air speed in the units air meters and metric drawings use, so you can compare a site reading with this design speed.
Above Recommended Speed
Recommended for This Run700 FPM
Maximum for This Run900 FPM
Residential duct limits for the run you picked. At or under the recommended speed it stays quiet; past the maximum it gets noisy.
78.5 sq in Open Area
Area in Square Feet0.545 sq ft
Area in Square Centimeters507 cm²
The open inside area the air moves through. Speed is airflow divided by this area, so a bigger size slows the air down and quiets it.
0.0855 in. w.c./100 ft
Over the Whole Run0.0427 in. w.c.
In Pascals per Meter0.698 Pa/m
Friction for clean galvanized sheet metal duct with standard air. Elbows, fittings and dampers add more loss on top of this.
8.34 Pa Velocity Pressure
Pitot Gauge Reading0.0335 in. w.c.
Air Mass Flow30 lb/min
The pressure the moving air carries, as a pitot tube reads it, at standard air. Mass flow is the weight of air the duct moves.
10.2 in Round at 700 FPM
Round at 900 FPM Max9.03 in
Smallest Square at 900 FPM8 in
Round and square sizes that carry this airflow at the recommended and maximum speeds, to help you pick a duct that stays in range.
Duct CFM and Friction ChartGalvanized Steel
Duct SizeArea (sq in)Airflow at 700 FPMAirflow at 900 FPMFriction at Max (in. w.c./100 ft)
4 in12.661.1 CFM78.5 CFM0.388
5 in19.695.4 CFM123 CFM0.294
6 in28.3137 CFM177 CFM0.234
7 in38.5187 CFM241 CFM0.193
8 in50.3244 CFM314 CFM0.164
9 in63.6309 CFM398 CFM0.142
10 in78.5382 CFM491 CFM0.124
12 in113550 CFM707 CFM0.0995
14 in154748 CFM962 CFM0.0824
16 in201977 CFM1,257 CFM0.07
18 in2541,237 CFM1,590 CFM0.0607
20 in3141,527 CFM1,963 CFM0.0534
22 in3801,848 CFM2,376 CFM0.0476
24 in4522,199 CFM2,827 CFM0.0428
26 in5312,581 CFM3,318 CFM0.0389
28 in6162,993 CFM3,848 CFM0.0355
30 in7073,436 CFM4,418 CFM0.0327
32 in8043,910 CFM5,027 CFM0.0303
34 in9084,414 CFM5,675 CFM0.0281
36 in1,0184,948 CFM6,362 CFM0.0263
Duct Velocity Chart by SectionSupply Trunk highlighted
Duct SectionRigid, RecommendedRigid, MaximumFlex, RecommendedFlex, Maximum
Supply Trunk700 FPM900 FPM600 FPM700 FPM
Supply Branch600 FPM900 FPM600 FPM700 FPM
Return Trunk600 FPM700 FPM600 FPM700 FPM
Return Branch400 FPM700 FPM400 FPM700 FPM
Supply Outlet Face700 FPM700 FPM700 FPM700 FPM
Return Grille Face500 FPM500 FPM500 FPM500 FPM
Filter Grille Face300 FPM300 FPM300 FPM300 FPM
Step-by-Step MathV = Q ÷ A
  1. Area = π × (10 in)² ÷ 4 = 78.54 sq in = 0.5454 sq ft.
  2. Velocity = 400 CFM ÷ 0.5454 sq ft = 733.4 FPM.
  3. Friction: air speed in the 10 in round = 733.4 FPM, Reynolds number = 8.56 × 10 × 733.4 = 62,778.
  4. Friction factor from the Colebrook equation = 0.02125; loss = 12 × f × 100 ÷ 10 × 0.075 × (733.4 ÷ 1097)² = 0.08548 in. w.c. per 100 ft.
  5. Velocity pressure = (733.4 ÷ 4005)² = 0.03353 in. w.c.
  6. Result: 733 FPM Duct Velocity.
Above the Recommended Speed
733 FPM is over the 700 FPM recommended but under the 900 FPM maximum for a rigid supply trunk. Expect more air noise; a round duct of 10.2 in slows it to 700 FPM.

FPM Math Behind a Duct Velocity Calculator

Air velocity in a duct equals airflow divided by the inside cross-section area. With airflow in CFM and area in square feet, the speed comes out in feet per minute, or FPM.

V is velocity in FPM, Q is airflow in CFM and A is the inside area in sq ft. A round duct has A = π × D² ÷ 576 with D in inches, and a rectangular duct has A = W × H ÷ 144.

A 10 inch round duct has 78.5 sq in, or 0.545 sq ft, of open area. At 400 CFM, 400 ÷ 0.545 = 733 FPM, or 3.73 m/s, the figure to expect from any duct velocity calculator for that duct.

For a duct velocity calculator metric or SI check, keep airflow in m³/s and area in m². Air at 0.2 m³/s, or 720 m³/h, in a 250 mm duct with 0.0491 m² of area moves at 4.07 m/s, which is 802 FPM.

In metric work, liters per second must become m³/s before dividing by m². Skipping that step gives a speed 1,000 times too low, a slip that shows up in published duct velocity formula examples.

The CFM formula is the same equation turned around, Q = V × A. An 8 inch duct at 700 FPM carries 700 × 0.349 = 244 CFM, which is how the CFM of a duct is worked out from a measured speed.

Room-side airflow, from room size and air changes per hour, comes from the CFM Calculator, and that CFM figure is what feeds each duct velocity calculator check.

Recommended FPM by Duct Section

A residential supply trunk in rigid metal should run at 700 FPM or less, with 900 FPM as the maximum. Branches, returns and flex duct run slower, following the ACCA Manual D residential duct design limits.

An HVAC duct velocity calculator result only means something once it sits beside the limit for its own section of duct, listed below for rigid metal and flex.

Duct SectionRigid, RecommendedRigid, MaximumFlex, RecommendedFlex, Maximum
Supply trunk700 FPM900 FPM600 FPM700 FPM
Supply branch600 FPM900 FPM600 FPM700 FPM
Return trunk600 FPM700 FPM600 FPM700 FPM
Return branch400 FPM700 FPM400 FPM700 FPM
Supply outlet face700 FPM700 FPM700 FPM700 FPM
Return grille face500 FPM500 FPM500 FPM500 FPM
Filter grille face300 FPM300 FPM300 FPM300 FPM

The same duct velocity calculator result can pass in one material and fail in another. A 10 inch trunk at 400 CFM runs at 733 FPM, above the 700 FPM rigid recommendation but under its 900 FPM maximum, while in flex it sits past the 700 FPM maximum.

A duct velocity calculator reading above the recommended speed means audible air rush at registers. Above the maximum, noise and friction both climb, because duct friction rises with roughly the square of air speed.

A very low duct velocity calculator result costs duct material and space rather than comfort inside the duct.

At the outlet it matters more, since supply registers are sized for 500 to 800 FPM face velocity and slower air throws a shorter distance into the room.

CFM Each Round Duct Carries at 700 and 900 FPM

A 6 inch round duct carries 137 CFM at 700 FPM and 177 CFM at 900 FPM. The chart below runs the same duct velocity calculator math for common round sizes, with friction for clean galvanized steel at 700 FPM.

Round DuctInside AreaCFM at 600 FPMCFM at 700 FPMCFM at 900 FPMFriction at 700 FPM
4 in12.6 sq in52.461.178.50.246 in. w.c./100 ft
5 in19.6 sq in81.895.41230.186 in. w.c./100 ft
6 in28.3 sq in1181371770.148 in. w.c./100 ft
7 in38.5 sq in1601872410.122 in. w.c./100 ft
8 in50.3 sq in2092443140.103 in. w.c./100 ft
9 in63.6 sq in2653093980.0894 in. w.c./100 ft
10 in78.5 sq in3273824910.0785 in. w.c./100 ft
12 in113 sq in4715507070.0627 in. w.c./100 ft
14 in154 sq in6417489620.0519 in. w.c./100 ft
16 in201 sq in8389771,2570.0441 in. w.c./100 ft
18 in254 sq in1,0601,2371,5900.0382 in. w.c./100 ft
20 in314 sq in1,3091,5271,9630.0336 in. w.c./100 ft

Friction per foot drops as ducts grow, even at the same speed. A 4 inch duct at 700 FPM loses 0.246 in. w.c. per 100 ft, more than seven times the 0.0336 of a 20 inch duct moving air just as fast.

Small branch runs therefore use up more of the blower's pressure per foot than the trunk does. Keep long branches one size up when a duct velocity calculator result lands near the branch maximum.

Return ducts use the same duct velocity calculator math with the slower return limits, and the Return Air Duct Size Calculator sizes the return side from total system airflow.

Sizing a Duct for 400 or 1,000 CFM

400 CFM needs a 10.2 inch round duct to stay at 700 FPM, so the next stock size up is a 12 inch duct running at 509 FPM. 1,000 CFM needs 16.2 inches at 700 FPM, which rounds up to an 18 inch duct at 566 FPM.

AirflowDiameter at 600 FPMDiameter at 700 FPMDiameter at 900 FPMNext Size Up From 700 FPMSpeed in That SizeFriction in That Size
100 CFM5.53 in5.12 in4.51 in6 in509 FPM0.0831 in. w.c./100 ft
150 CFM6.77 in6.27 in5.53 in7 in561 FPM0.0817 in. w.c./100 ft
200 CFM7.82 in7.24 in6.38 in8 in573 FPM0.0718 in. w.c./100 ft
400 CFM11.1 in10.2 in9.03 in12 in509 FPM0.0351 in. w.c./100 ft
600 CFM13.5 in12.5 in11.1 in14 in561 FPM0.0347 in. w.c./100 ft
800 CFM15.6 in14.5 in12.8 in16 in573 FPM0.0306 in. w.c./100 ft
1,000 CFM17.5 in16.2 in14.3 in18 in566 FPM0.0259 in. w.c./100 ft
1,200 CFM19.1 in17.7 in15.6 in18 in679 FPM0.0361 in. w.c./100 ft
1,600 CFM22.1 in20.5 in18.1 in22 in606 FPM0.023 in. w.c./100 ft

The size steps above run in whole inches to 10 inches, then in even sizes. That gap turns a 10.2 inch duct velocity calculator answer for 400 CFM into either a 10 inch duct at 733 FPM or a 12 inch duct at 509 FPM.

For a 400 CFM supply trunk, a 733 FPM duct velocity calculator result in the 10 inch size is still legal in rigid metal, under the 900 FPM maximum. The 12 inch size costs more metal but cuts friction from 0.0855 to 0.0351 in. w.c. per 100 ft.

A rectangular duct velocity calculator works the same way, with the needed area divided by the width on hand. 400 CFM at 700 FPM needs 82.3 sq in, so an 8 inch deep joist bay needs about 10.3 inches of inside width.

At the usual 400 CFM per ton, 1,000 CFM is the airflow of a 2.5 ton system, and the AC Tonnage Calculator sets that tonnage from the house load.

Rectangular Ducts Lose More at the Same Area

A 10 × 10 inch duct carries 486 CFM at 700 FPM and 625 CFM at 900 FPM. Area alone sets the speed, but shape changes the friction, so rectangular duct velocity calculator sizing goes through an equivalent round diameter.

The sides a and b are inside dimensions in inches. De is the round duct with the same friction at the same airflow, the equal-friction relation given in the ASHRAE Handbook of Fundamentals.

Rectangular DuctInside AreaSpeed at 600 CFMEquivalent RoundFriction at 600 CFM
10 × 10 in100 sq in864 FPM10.9 in0.116 in. w.c./100 ft
12.5 × 8 in100 sq in864 FPM10.9 in0.12 in. w.c./100 ft
20 × 5 in100 sq in864 FPM10.3 in0.153 in. w.c./100 ft
25 × 4 in100 sq in864 FPM9.96 in0.184 in. w.c./100 ft

All four ducts move 600 CFM at the same 864 FPM, yet the flat 25 × 4 loses 59% more pressure per 100 ft than the square 10 × 10. A rectangular duct friction calculator check matters most for thin ducts squeezed into joist bays.

A 10 × 10 duct does not equal a 10 inch round in duct velocity calculator friction math. Its equivalent round is 10.9 inches, so at equal friction it carries a little more air than a 10 inch round, not the same.

Friction Loss and Flex Duct Compression

400 CFM through 50 ft of 10 inch galvanized duct loses 0.0427 in. w.c. Fully stretched flex of the same size loses 0.0613 to 0.0953 in. w.c., using the ASHRAE roughness range of 0.0035 to 0.015 ft for flex.

The loss Δp is in in. w.c., f is the Darcy friction factor from the Colebrook equation, L is length in ft, D is diameter in inches, ρ is air density at 0.075 lb/ft³ and V is velocity in FPM.

Duct at 400 CFMAir SpeedGalvanized SteelFlex, Fully Stretched
8 in round1,146 FPM0.256 in. w.c./100 ft0.392 to 0.631 in. w.c./100 ft
10 in round733 FPM0.0855 in. w.c./100 ft0.123 to 0.191 in. w.c./100 ft

Those duct velocity calculator flex figures assume the duct is pulled tight. Researchers at Lawrence Berkeley National Laboratory measured how much compression raises that loss, size by size.

K is the multiplier on stretched-flex friction, rc is compression as a fraction of the fully stretched length, and a is the lab factor for the duct size. In duct velocity calculator math, sizes between 6, 8 and 10 inches take a factor in between.

Flex SizeLab Factor a10% Compressed15% Compressed20% Compressed30% Compressed
6 in25.35×3.54×4.8×6.07×8.61
8 in21.61×3.16×4.24×5.32×7.48
10 in16.18×2.62×3.43×4.24×5.85

Small flex suffers most. At 30% compression a 6 inch run loses 8.61 times its stretched friction, while a 10 inch run loses 5.85 times. The size-blind ASHRAE factor of 1 + 9.86 × rc gives only 3.96 at 30%.

The lab study found that ASHRAE factor reads about 35% low on average. Below 6 inches or above 10 inches, the nearest tested factor is the best duct velocity calculator estimate available, since the study covered only those three sizes.

At 30% compression, the 50 ft run of 10 inch flex at 400 CFM loses 0.359 to 0.558 in. w.c., 8.4 to 13 times the 0.0427 in. w.c. of galvanized steel. Sagging between hangers adds loss on top of any duct velocity calculator compression figure.

Velocity Pressure and Pitot Readings

Air at 700 FPM carries 0.0305 in. w.c. of velocity pressure, or 7.6 Pa, at standard air density. Velocity pressure is what a pitot tube reads, and air speed follows from it.

VP is velocity pressure in in. w.c. and V is velocity in FPM, for standard air at 0.075 lb/ft³. A pitot reading of 0.05 in. w.c. means 896 FPM, and a reading of 0.03 in. w.c. means 694 FPM.

Air SpeedVelocity PressureVelocity Pressure in Pa
300 FPM0.00561 in. w.c.1.4 Pa
500 FPM0.0156 in. w.c.3.88 Pa
600 FPM0.0224 in. w.c.5.58 Pa
700 FPM0.0305 in. w.c.7.6 Pa
900 FPM0.0505 in. w.c.12.6 Pa
1,000 FPM0.0623 in. w.c.15.5 Pa
1,200 FPM0.0898 in. w.c.22.3 Pa
1,500 FPM0.14 in. w.c.34.9 Pa

To check duct velocity on site against a duct velocity calculator design figure, take a traverse of several readings across the opening.

Average the speeds rather than trusting one point. Air near the walls moves slower than in the middle, so one centerline reading overstates the flow.

Residential speeds give tiny pressures, under 0.07 in. w.c. at 1,000 FPM, so a pitot traverse needs a gauge that reads to 0.001 in. w.c. A vane or hot-wire anemometer reads speed directly and is easier at registers.

Grille and Filter Face Speeds

A filter grille should pass air at 300 FPM or less and a plain return grille at 500 FPM or less. Those are the ACCA limits cited in the Hart and Cooley engineering data guide, which puts supply outlets at 500 to 800 FPM.

AirflowSupply Outlet at 700 FPMReturn Grille at 500 FPMFilter Grille at 300 FPM
100 CFM20.6 sq in28.8 sq in48 sq in
200 CFM41.1 sq in57.6 sq in96 sq in
400 CFM82.3 sq in115 sq in192 sq in
600 CFM123 sq in173 sq in288 sq in
800 CFM165 sq in230 sq in384 sq in
1,000 CFM206 sq in288 sq in480 sq in
1,200 CFM247 sq in346 sq in576 sq in

Face areas in a duct velocity calculator grille check are effective areas, the maker's Ak value times 144, not the nominal size on the box.

A 20 × 20 filter grille is 400 sq in nominal, so its true limit at 300 FPM sits below the 833 CFM the nominal size suggests.

A filter face over 300 FPM gets noisy and catches less dust. Sizing one central filter grille for 1,200 CFM takes 576 sq in of effective face, which often means two grilles instead of one.

Air Speed, Airflow and Metric Units

Metric drawings, air meters and fan labels state the same speeds and flows in other units. Every factor below follows from 1 ft = 0.3048 m, so 1 FPM is exactly 0.00508 m/s.

A duct velocity calculator metric result and an imperial one describe the same duct, so the factors below move a reading between site meters and drawings.

What is 1 CFM equal to?

One CFM equals 1.70 m³/h, 0.472 L/s and 0.000472 m³/s. For speed, 1 m/s equals 196.9 FPM, 1 ft/s equals 60 FPM and 1 mph equals 88 FPM, so 733 FPM is 3.73 m/s or 8.33 mph.

Is duct velocity the same as airflow?

Velocity is the speed of the air in FPM or m/s, while airflow is the volume it moves in CFM or m³/h. The same 400 CFM travels at 733 FPM in a 10 inch duct and at 1,146 FPM in an 8 inch duct.

Does smaller duct size increase velocity?

At a fixed airflow, a smaller duct raises the speed in proportion to the lost area. Dropping 400 CFM from a 10 inch to an 8 inch round lifts the speed from 733 to 1,146 FPM, past the 900 FPM trunk maximum.

Friction rises faster than speed, from 0.0855 to 0.256 in. w.c. per 100 ft in that swap, three times the loss. That is the noise and blower strain people describe when duct velocity is too high.

How do you calculate air velocity in a 12 inch duct?

A 12 inch round duct has 113 sq in, or 0.785 sq ft, of inside area. At 1,000 CFM the air moves at 1,000 ÷ 0.785 = 1,273 FPM, well over the 900 FPM maximum for a residential supply trunk.

Turned around, a 12 inch duct carries 550 CFM at the 700 FPM trunk recommendation and 707 CFM at the 900 FPM maximum, the range a duct velocity calculator check should land in for a 12 inch trunk.

What is a Ductulator?

A Ductulator is a slide-rule duct sizer that links airflow, duct size, velocity and friction rate on one dial. It reads the same relationships as a duct velocity calculator, such as 244 CFM in an 8 inch duct at 700 FPM.

The slide rule assumes clean metal duct, so its friction rates read low for flex. A duct velocity calculator SI or metric version follows the same math, only with m³/s, m² and m/s in place of CFM, sq ft and FPM.