Duct Volume Calculator

Updated

Duct Volume Calculator for the air in round, rectangular, square and flat oval ducts in cu ft, m³ or liters, with net area after liner, wrap surface and the CFM each size can move.

Duct Shape and Dimensions

Enter the inside duct size and straight run length to calculate internal volume.

Airflow & Liner Settings 400 CFM · 700 FPM · No Liner
Duct Volume Result
19.6 cu ft Internal Volume
Volume = cross-section area × duct length
0.556 m³ Same Volume
Volume in Liters556 L
Volume in US Gallons147 gal
Internal air capacity converted for purge testing, smoke volume, and fluid displacement.
0.785 sq ft Open Area
Opening in Square Inches113 sq in
Equivalent Square Size11 × 11 in
Net clear inside cross-section and the square duct size with equal friction loss.
78.5 sq ft Duct Surface
Surface in Square Meters7.3 m²
Perimeter Around Duct37.7 in
Lateral sheet metal and insulation wrap area along the straight run, excluding end caps.
509 FPM Air Velocity
Airflow at 700 FPM550 CFM
Air Transit Time2.95 sec
Air speed through this duct, the most air it moves at your max velocity, and one-pass time.
Standard Duct Size Volume Chart25 ft duct · 12 in highlighted
Duct SizeCross-SectionVolume per 1 ftVolume for 25 ft DuctAirflow at 700 FPMWrap Surface
6 in0.196 sq ft0.196 cu ft4.91 cu ft137 CFM39.3 sq ft
7 in0.267 sq ft0.267 cu ft6.68 cu ft187 CFM45.8 sq ft
8 in0.349 sq ft0.349 cu ft8.73 cu ft244 CFM52.4 sq ft
9 in0.442 sq ft0.442 cu ft11 cu ft309 CFM58.9 sq ft
10 in0.545 sq ft0.545 cu ft13.6 cu ft382 CFM65.4 sq ft
12 in0.785 sq ft0.785 cu ft19.6 cu ft550 CFM78.5 sq ft
14 in1.07 sq ft1.07 cu ft26.7 cu ft748 CFM91.6 sq ft
16 in1.4 sq ft1.4 cu ft34.9 cu ft977 CFM105 sq ft
18 in1.77 sq ft1.77 cu ft44.2 cu ft1,237 CFM118 sq ft
20 in2.18 sq ft2.18 cu ft54.5 cu ft1,527 CFM131 sq ft
22 in2.64 sq ft2.64 cu ft66 cu ft1,848 CFM144 sq ft
24 in3.14 sq ft3.14 cu ft78.5 cu ft2,199 CFM157 sq ft
Duct Volume by Run Length25 ft highlighted
Duct LengthVolume (cu ft)Volume (m³)Liters (L)Surface Area
10 ft7.85 cu ft0.222 m³222 L31.4 sq ft
25 ft19.6 cu ft0.556 m³556 L78.5 sq ft
50 ft39.3 cu ft1.11 m³1,112 L157 sq ft
75 ft58.9 cu ft1.67 m³1,668 L236 sq ft
100 ft78.5 cu ft2.22 m³2,224 L314 sq ft
150 ft118 cu ft3.34 m³3,336 L471 sq ft
200 ft157 cu ft4.45 m³4,448 L628 sq ft
Step-by-Step MathVolume = area × length
  1. Inside cross-section area = π × (12 in)² ÷ 4 = 113.1 sq in = 0.7854 sq ft.
  2. Duct volume = 0.7854 sq ft × 25 ft = 19.63 cu ft.
  3. Lateral surface area = π × 1 ft × 25 ft = 78.54 sq ft.
  4. Air velocity = 400 CFM ÷ 0.7854 sq ft = 509.3 FPM (2.945 sec to pass through).
  5. Result: 19.6 cu ft Internal Volume.
Within Your Max Velocity
At 400 CFM, air moves at 509 FPM here, at or under your 700 FPM limit, and replaces the 19.6 cu ft inside this duct every 2.95 sec.

Duct Volume Calculator Formulas by Shape

Duct volume equals the inside cross-section area times the straight length. A 12 in round duct 25 ft long holds 19.6 cu ft of air, which is 0.556 m³ or 556 liters.

V is the volume, A is the inside area in sq ft (or m²) and L is the run length in ft (or m). Divide an area in square inches by 144 before you multiply, or every duct volume calculator result comes out 144 times too big.

D is the inside diameter. For a metric duct volume calculator estimate, a 300 mm round duct has 0.0707 m² of open area, so a 30 m run holds 2.12 m³, or 2,121 liters of air.

W and H are the inside width and height. A square duct uses the same rule with both sides equal. In duct volume calculator math, a 10 × 10 in duct counts as 100 sq in, or 0.694 sq ft.

In the flat oval formula, a is the major width and b is the minor height. Flat oval duct is two half-circles joined by flat sides, so it holds more air than an ellipse of the same width and height.

That difference matters. An 18 × 8 in flat oval has 130.3 sq in of open area and holds 22.6 cu ft over 25 ft. The ellipse formula gives only 113.1 sq in, which undercounts a duct volume calculator total by 13%.

Cubic Feet in a Round Duct

Each foot of round duct holds its own area in cubic feet, the base of every duct volume calculator total. An 8 in duct holds 0.349 cu ft per foot, a 12 in duct holds 0.785 cu ft per foot, and a 24 in duct holds 3.14 cu ft per foot.

Volume grows with the square of the diameter, so the duct volume calculator result for 24 in duct is four times the 12 in figure per foot, not twice.

The table below sets out the duct volume calculator figures for common round sizes in both unit systems, from 4 in bath branches up to 24 in trunks.

Round ductOpen areaCu ft per ftLiters per mUS gal per ft25 ft run100 ft run
4 in (102 mm)12.6 sq in0.0878.1 L0.652.18 cu ft8.7 cu ft
5 in (127 mm)19.6 sq in0.13612.7 L1.023.41 cu ft13.6 cu ft
6 in (152 mm)28.3 sq in0.19618.2 L1.474.91 cu ft19.6 cu ft
7 in (178 mm)38.5 sq in0.26724.8 L2.006.68 cu ft26.7 cu ft
8 in (203 mm)50.3 sq in0.34932.4 L2.618.73 cu ft34.9 cu ft
9 in (229 mm)63.6 sq in0.44241.0 L3.3111.0 cu ft44.2 cu ft
10 in (254 mm)78.5 sq in0.54550.7 L4.0813.6 cu ft54.5 cu ft
12 in (305 mm)113.1 sq in0.78573.0 L5.8819.6 cu ft78.5 cu ft
14 in (356 mm)153.9 sq in1.0799.3 L8.0026.7 cu ft107 cu ft
16 in (406 mm)201.1 sq in1.40129.7 L10.434.9 cu ft140 cu ft
18 in (457 mm)254.5 sq in1.77164.2 L13.244.2 cu ft177 cu ft
20 in (508 mm)314.2 sq in2.18202.7 L16.354.5 cu ft218 cu ft
24 in (610 mm)452.4 sq in3.14291.9 L23.578.5 cu ft314 cu ft

A full ductwork volume calculator total is the sum of every run. A 50 ft, 16 in trunk feeding six 6 in branches of 15 ft each holds 69.8 + 17.7 = 87.5 cu ft, or about 2,477 liters.

The metric column assumes the inch size. Metric spiral duct sold in 100, 125, 160, 200, 250 and 315 mm sizes holds slightly different amounts, so run a duct volume calculator check with the real millimeter diameter.

Rectangular Duct Volume and Equivalent Diameter

A rectangular duct holds width × height × length of air, and that duct volume calculator figure hides how it moves air. An 8 × 8 in duct has the same 64 sq in as a 9 in round, yet flows like an 8.75 in round.

The extra perimeter of a rectangle adds friction. ASHRAE's Handbook of Fundamentals, Duct Design chapter, gives the Huebscher equation for the round size with equal friction at equal airflow.

De is the equivalent round diameter, and a and b are the two inside sides in the same unit. For flat oval duct, ASHRAE uses De = 1.55 A0.625 ÷ P0.25, with A the open area and P the perimeter.

Rectangular ductOpen areaCu ft per ftLiters per mRound of same areaEqual-friction round
8 × 8 in64 sq in0.44441.3 L9.0 in8.75 in
12 × 6 in72 sq in0.50046.5 L9.6 in9.14 in
10 × 8 in80 sq in0.55651.6 L10.1 in9.76 in
12 × 8 in96 sq in0.66761.9 L11.1 in10.7 in
16 × 8 in128 sq in0.88982.6 L12.8 in12.2 in
16 × 10 in160 sq in1.11103.2 L14.3 in13.7 in
20 × 10 in200 sq in1.39129.0 L16.0 in15.2 in
24 × 12 in288 sq in2.00185.8 L19.1 in18.3 in
30 × 10 in300 sq in2.08193.5 L19.5 in18.3 in

The last two rows show the aspect ratio cost. A 30 × 10 in duct holds 4% more air per foot than a 24 × 12 in duct, yet both flow like an 18.3 in round. Flat ducts buy volume, not airflow.

For a rectangular duct size calculator answer, size the round duct first, then choose a rectangle whose equal-friction round matches it. Matching open area alone leaves the rectangle's equal-friction diameter 3-7% below the round it replaces.

Liner Thickness and Net Duct Volume

Internal duct liner sits inside the sheet metal, so a duct volume calculator estimate for lined duct must use the airway. A 1 in liner cuts a 12 in round duct's open area from 113.1 to 78.5 sq in, a 31% loss of air volume.

The liner comes off both sides, so the net size is the sheet metal size minus twice the liner. A 16 × 10 in lined duct with 1 in liner has a 14 × 8 in airway, and its 25 ft duct volume calculator total drops from 27.8 to 19.4 cu ft.

Liner thickness12 in round open areaArea lost25 ft volumeVelocity at 400 CFM16 × 10 in open area25 ft volume
None113.1 sq in0%19.6 cu ft509 FPM160 sq in27.8 cu ft
0.5 in (13 mm)95.0 sq in16%16.5 cu ft606 FPM135 sq in23.4 cu ft
1 in (25 mm)78.5 sq in31%13.6 cu ft733 FPM112 sq in19.4 cu ft
1.5 in (38 mm)63.6 sq in44%11.0 cu ft905 FPM91 sq in15.8 cu ft
2 in (51 mm)50.3 sq in56%8.7 cu ft1,146 FPM72 sq in12.5 cu ft

The velocity column is the trap. A 12 in duct that is fine at 509 FPM bare climbs past the 900 FPM supply limit once it gets 1.5 in of liner.

Grow the sheet metal by twice the liner thickness to keep the airway and the duct volume calculator figure you sized, rather than trusting the outside dimensions on the drawing.

CFM to Duct Size at Manual D Velocities

Duct size works backward from the same open area used for duct volume, dividing airflow by velocity. 400 CFM at 700 FPM needs 0.571 sq ft of open area, which is a 10.2 in round, so the next stocked size is 12 in.

A is the open area in sq ft, Q is the airflow in CFM and V is the air velocity in FPM. In metric, use m³/s and m/s to get m², or L/s divided by m/s and then by 1,000.

D is the round diameter for that area. Multiply by 12 to turn feet into inches. This is the duct size calculation formula behind every HVAC duct size CFM calculator that sizes by velocity.

The velocity limit comes from ACCA. The ACCA Manual D checklist (Table 3-1) recommends 700 FPM for rigid supply trunks and 600 FPM for rigid return trunks, with maximums of 900 and 700 FPM.

Branch ducts run slower. Manual D recommends 600 FPM for rigid supply branches and 400 FPM for return branches. Flex duct maximums drop to 700 FPM on both supply and return. The full standard is ANSI/ACCA Manual D.

Stock sizes change the answer. Building scientist Dr. Allison Bailes of Energy Vanguard notes round duct comes in 1 in steps from 4 to 10 in, then every 2 in. A 17 in or 23 in result has to go up to 18 or 24 in.

AirflowExact size at 600 FPMStock sizeExact size at 700 FPMStock sizeExact size at 900 FPMStock size
100 CFM (47 L/s)5.53 in6 in5.12 in6 in4.51 in5 in
150 CFM (71 L/s)6.77 in7 in6.27 in7 in5.53 in6 in
250 CFM (118 L/s)8.74 in9 in8.09 in9 in7.14 in8 in
400 CFM (189 L/s)11.06 in12 in10.24 in12 in9.03 in10 in
600 CFM (283 L/s)13.54 in14 in12.54 in14 in11.06 in12 in
800 CFM (378 L/s)15.64 in16 in14.48 in16 in12.77 in14 in
1,200 CFM (566 L/s)19.15 in20 in17.73 in18 in15.64 in16 in
1,600 CFM (755 L/s)22.11 in24 in20.47 in22 in18.05 in20 in
2,000 CFM (944 L/s)24.72 in26 in22.89 in24 in20.19 in22 in

Velocity sets the smallest size, not always the final one. The same ACCA checklist sizes a 150 CFM bedroom with an 8 in duct, which runs at only 430 FPM, because the friction rate called for it.

A friction-rate size is often one step larger than the velocity size in the table. Check air speed in a chosen size with the Duct Velocity Calculator.

Return ducts need the slower 600-700 FPM column. The Return Air Duct Size Calculator works from system airflow, and the CFM Calculator finds the airflow a room or fan needs before any duct gets sized.

Surface Area for Wrap and Sheet Metal

Duct surface area is the perimeter times the run length. A 12 in round duct has a 37.7 in perimeter, so 25 ft of it needs 78.5 sq ft of sheet metal or insulation wrap, ends not included.

S is the lateral surface in sq ft, P is the outside perimeter in ft and L is the length in ft. Use the sheet metal size here, not the lined airway used for a duct volume calculator figure, since wrap goes outside the metal.

Round duct wraps the most air in the least metal. Holding the 113 sq in area of a 12 in round fixed, so every duct volume calculator total stays equal, the shape alone changes the wrap a 100 ft run takes.

Shape with 113 sq in of open areaSizePerimeterSurface per 100 ftExtra wrap vs round
Round12 in37.7 in314 sq ft0%
Square10.6 × 10.6 in42.5 in355 sq ft12.8%
Rectangle, 2:115.0 × 7.5 in45.1 in376 sq ft19.7%

That extra 20% shows up three times on a flat duct run. You buy more metal, more wrap and lose more heat through the larger skin. The R-Value Calculator totals the insulation layers you plan to wrap with.

Duct weight in kilograms starts from this surface figure in m². Sheet weight per square foot depends on the gauge, and the Duct Weight Calculator turns duct size and gauge into pounds or kilograms.

Air Turnover Time in a Duct Run

One pass of air takes the duct volume calculator total divided by the airflow. A 12 in round duct 25 ft long holds 19.6 cu ft, so 400 CFM replaces all of it every 2.95 seconds at 509 FPM.

t is the time in seconds, V is the duct volume calculator total in cu ft and Q is the airflow in CFM. The same result comes from run length divided by air speed in feet per second.

The time matters when a duct must be flushed or dosed. Fogging sanitizer, smoke testing for leaks and purging before a test all scale with the duct volume calculator figure, not with floor area.

RunAirflowAir volumeAir velocityOne full pass
6 in round, 15 ft branch100 CFM2.95 cu ft509 FPM1.77 sec
8 in round, 20 ft branch150 CFM6.98 cu ft430 FPM2.79 sec
12 in round, 25 ft400 CFM19.6 cu ft509 FPM2.95 sec
16 × 8 in, 50 ft trunk800 CFM44.4 cu ft900 FPM3.33 sec
16 in round, 50 ft trunk1,000 CFM69.8 cu ft716 FPM4.19 sec

Ducts empty in seconds while rooms take minutes. For how often a room's own air turns over, use the Air Changes per Hour Calculator with the room size and supply CFM.

Sizing Answers for Common CFM Loads

Each answer below uses inside dimensions with no liner, the Manual D velocities from the sizing table and the same duct volume calculator math as the tables above.

How much CFM is in a 10x10 duct?

A 10 × 10 in duct carries 486 CFM at 700 FPM. Its open area is 100 sq in, or 0.694 sq ft, so it moves 417 CFM at 600 FPM and 625 CFM at the 900 FPM supply maximum.

At a set friction rate it behaves like a 10.9 in round duct, not an 11.3 in round of the same area. As a duct volume calculator figure, each foot of it holds 0.694 cu ft, or 64.5 liters per meter.

How do I calculate the CFM of a duct?

Multiply the open area in square feet, the same area used in a duct volume calculator, by the air velocity in FPM. An 8 in round duct has 0.349 sq ft of area, so at 700 FPM it carries 244 CFM.

At 700 FPM, a 6 in duct carries 137 CFM, a 10 in duct 382 CFM, a 12 in duct 550 CFM and a 16 in duct 977 CFM. For a real duct, measure the velocity with an anemometer at several points across the opening and average them first.

What size duct for 12x12 room?

A 12 × 12 room usually takes one 6 to 8 in round supply. The size depends on the room's airflow, which comes from a Manual J load, not from its 144 sq ft of floor.

A room needing 100 CFM gets a 6 in duct at 509 FPM. A room needing 150 CFM gets a 7 in duct at 561 FPM, and the ACCA example above uses an 8 in for 150 CFM when friction governs. The AC Tonnage Calculator sizes the cooling load first.

What is the area of a 10 inch duct?

A 10 in round duct has 78.54 sq in of open area, which is 0.545 sq ft or 0.0507 m². That comes from π × 10² ÷ 4.

The same number is its duct volume calculator figure per foot, 0.545 cu ft, or 50.7 liters per meter. At 700 FPM it carries 382 CFM, and with 1 in of liner its airway shrinks to 8 in and 50.3 sq in.

What size duct for 1000 CFM?

1,000 CFM needs a 16 in round duct for supply and an 18 in round for return. At 700 FPM the exact size is 16.2 in, and the next stock size up is 18 in at 566 FPM.

A 16 in duct carries it at 716 FPM, which is under the 900 FPM supply maximum but over the 700 FPM return limit. In rectangular duct, 20 × 10 in moves 1,000 CFM at 720 FPM and 16 × 10 in hits exactly 900 FPM.

What size duct is needed for 250 CFM?

250 CFM needs an 8 in round supply duct or a 9 in round return. An 8 in duct runs at 716 FPM, inside the 900 FPM supply limit but over the 700 FPM return limit.

At 700 FPM the exact size is 8.09 in, so a 9 in duct at 566 FPM is the size that meets the velocity on both sides. A 12 × 6 in rectangle carries 250 CFM at 500 FPM.