Snow Load Calculator for roof snow weight from depth and snow type, plus the ASCE 7 design snow load from ground snow load, pitch, exposure, warmth, risk category and roof surface.
Snow depth and type give the weight on your roof now; ground snow load sets what the roof is designed for.
Roof and Site Factors
Well insulated is R-30+ unvented or R-20+ vented. Factors follow the 2016 code edition.
Live Roof Snow Diagram
Snow Weight by Snow Type
Roof Snow Load by Pitch
Step-by-Step Snow Load Math
Depth, Density and Snow Load Calculator Weight
Ten inches of settled snow weighs 13.01 psf (0.623 kPa). On a 40 x 30 ft house with a 6/12 roof, that is 15,607 lb, or 61.9% of a roof designed for 21 psf of snow.
Snow type changes a snow load calculator answer more than depth does. The table puts each type on the same 1,200 sq ft of roof plan, 10 in deep measured straight down, against a 21 psf design snow load.
| Snow Type | Density | psf per Inch | Weight of 10 in on the Roof | Share of Design Load | Max Safe Depth |
|---|---|---|---|---|---|
| Fresh Snow | 60 kg/m³ (3.75 lb/cu ft) | 0.312 | 3,746 lb | 14.9% | 67.3 in |
| Damp Fresh Snow | 110 kg/m³ (6.87 lb/cu ft) | 0.572 | 6,867 lb | 27.3% | 36.7 in |
| Settled Snow | 250 kg/m³ (15.61 lb/cu ft) | 1.301 | 15,607 lb | 61.9% | 16.1 in |
| Wind-Packed Snow | 375 kg/m³ (23.41 lb/cu ft) | 1.951 | 23,410 lb | 92.9% | 10.8 in |
| Very Wet Snow | 750 kg/m³ (46.82 lb/cu ft) | 3.902 | 46,821 lb | 185.8% | 5.4 in |
| Ice | 917 kg/m³ (57.25 lb/cu ft) | 4.771 | 57,246 lb | 227.2% | 4.4 in |
In snow load calculator terms, the same 10 in that is harmless as fresh powder sits at 92.9% of the limit once it turns wind-packed. Rain soaking into settled snow can move a roof from the third row to the fifth in one storm.
Fresh snow density varies widely, which moves any snow load calculator estimate. The University of British Columbia's ATSC 113 notes put newly fallen snow at 30 to 300 kg/m³, with about 80 kg/m³ as the North American average.
Here w is the snow load in psf, ρ is the snow density in lb per cubic foot and d is the snow depth in inches. Dividing by 12 turns density per foot into load per inch of depth.
These snow load calculator depths are measured straight down, the way a yardstick goes into the snow. Measured square to the roof surface instead, the safe depth of settled snow on this 6/12 roof is 14.4 in rather than 16.1 in.
The difference is the slope. Depth square to a 6/12 roof is 0.894 times the vertical depth, so the same snow reads shallower and spreads over 1,342 sq ft of sloped surface instead of 1,200 sq ft of plan.
Ground Snow Load to Roof Design Load
In snow load calculator math, a 30 psf ground snow load becomes a 21 psf roof design load on a heated house with average exposure. The roof keeps 70% of the ground snow because wind and building heat clear some of it.
pf is the flat roof snow load, Ce the exposure factor, Ct the thermal factor, Is the importance factor and pg the ground snow load, all from ASCE 7-16 Chapter 7.
The snow load calculator table holds those factors at 1.0 on a 6/12 gable roof 30 ft wide, so only the ground snow load changes. The leeward column is the unbalanced case covered further down.
| Ground Snow Load | Roof Design Load | On 1,200 sq ft of Plan | Leeward Unbalanced Load |
|---|---|---|---|
| 10 psf (0.479 kPa) | 7.00 psf (0.335 kPa) | 8,400 lb | 10.00 psf |
| 20 psf (0.958 kPa) | 14.00 psf (0.670 kPa) | 16,800 lb | 20.00 psf |
| 30 psf (1.436 kPa) | 21.00 psf (1.005 kPa) | 25,200 lb | 30.00 psf |
| 40 psf (1.915 kPa) | 28.00 psf (1.341 kPa) | 33,600 lb | 40.00 psf |
| 50 psf (2.394 kPa) | 35.00 psf (1.676 kPa) | 42,000 lb | 50.00 psf |
| 70 psf (3.352 kPa) | 49.00 psf (2.346 kPa) | 58,800 lb | 70.00 psf |
| 100 psf (4.788 kPa) | 70.00 psf (3.352 kPa) | 84,000 lb | 100.00 psf |
Snow load calculator design weight uses the plan area under the roof, not the sloped surface, because code snow loads act on the horizontal projection. A 40 x 30 ft house carries 1,200 sq ft of plan at any pitch.
A ground snow load calculator answer comes from the building code map for your site, not from snow depth you measure. Your local building department publishes the ground snow load it enforces, and that figure starts every roof design.
Exposure, Heat and Risk Factors
At the same 30 psf ground snow load, the 6/12 snow load calculator result ranges from 17.85 psf on a heated greenhouse to 27.30 psf on a freezer building. Exposure and heat move the result by more than half.
| Site and Building | Exposure Ce | Thermal Ct | Roof Design Load |
|---|---|---|---|
| Open terrain, fully exposed, heated | 0.9 | 1.0 | 18.90 psf |
| Suburban, partially exposed, heated | 1.0 | 1.0 | 21.00 psf |
| Suburban, partially exposed, cold vented roof | 1.0 | 1.1 | 23.10 psf |
| Suburban, sheltered by trees, heated | 1.2 | 1.0 | 25.20 psf |
| Suburban, partially exposed, unheated | 1.0 | 1.2 | 25.20 psf |
| Shoreline, fully exposed, unheated | 0.8 | 1.2 | 20.16 psf |
| Suburban, partially exposed, freezer | 1.0 | 1.3 | 27.30 psf |
| Suburban, partially exposed, heated greenhouse | 1.0 | 0.85 | 17.85 psf |
A sheltered roof holds more snow because trees and buildings stop wind from scouring it. A shoreline roof with no shelter is the reverse, which is why the unheated shoreline roof still comes in under the heated suburban one.
Risk category scales the whole snow load calculator result in ASCE 7-16. The same roof is 16.80 psf for a barn or shed, 21.00 psf for a house, 23.10 psf for a school and 25.20 psf for a hospital or fire station.
A cold vented roof has more than R-25 between the vented attic and the heated rooms below, so little building heat reaches the snow. That keeps more snow on the roof, which is why its Ct of 1.1 raises the load.
Steep and Slippery Roofs Shed Load
A 12/12 roof over a heated house keeps 62.5% of the flat roof snow load, while a slippery metal roof at the same pitch keeps 38.5%. Below 30° on a rough, heated roof, the slope factor stays at 1.0.
Cs is the slope factor, θ the roof angle in degrees and a the angle where shedding starts, from 5° to 45° by roof warmth and surface. Cs is 1.0 at or below a and 0 at 70° and steeper.
| Pitch | Angle | Heated, Rough | Heated, Slippery | Cold Vented, Rough | Cold Vented, Slippery | Unheated, Slippery |
|---|---|---|---|---|---|---|
| 4/12 | 18.43° | 1.000 | 0.793 | 1.000 | 0.859 | 0.938 |
| 6/12 | 26.57° | 1.000 | 0.668 | 1.000 | 0.724 | 0.790 |
| 8/12 | 33.69° | 0.908 | 0.559 | 1.000 | 0.605 | 0.660 |
| 10/12 | 39.81° | 0.755 | 0.465 | 0.929 | 0.503 | 0.549 |
| 12/12 | 45.00° | 0.625 | 0.385 | 0.769 | 0.417 | 0.455 |
| 16/12 | 53.13° | 0.422 | 0.260 | 0.519 | 0.281 | 0.307 |
| 24/12 | 63.43° | 0.164 | 0.101 | 0.202 | 0.109 | 0.119 |
Slippery counts only for metal, glass or similar surfaces with nothing stopping the snow. Snow guards, ridge vents or a parapet at the eave turn it back into a rough roof, and a heated roof needs R-30 unvented or R-20 vented to count as slippery.
On a 30 psf site, that difference matters for every rafter snow load calculator check. A heated 6/12 shingle roof carries 21.00 psf, while the same roof in unobstructed standing seam metal carries 14.03 psf, a third less.
The Roof Pitch Calculator turns a measured rise and run into the roof angle these slope factors need. A 7/12 roof is 30.26°, just past the 30° break for heated rough roofs.
Low-Slope Minimums and Rain-on-Snow
Any hip or gable roof under 15° must carry at least the ground snow load up to 20 psf, times the importance factor. On a 25 psf site that minimum is 20 psf, above the 17.50 psf the formula gives.
Light-snow sites add a 5 psf rain-on-snow surcharge when the ground snow load is 20 psf or less and the roof angle is under W/50. Here W is the horizontal eave-to-ridge distance in feet, so very flat, wide roofs are the ones that qualify.
| Ground Snow Load | Roof | Formula Load | Rain-on-Snow | Minimum | Design Load |
|---|---|---|---|---|---|
| 10 psf | Flat, 30 ft wide | 7.00 psf | 5 psf | 10.00 psf | 12.00 psf |
| 10 psf | 2/12, 30 ft wide | 7.00 psf | None | 10.00 psf | 10.00 psf |
| 15 psf | 1/4:12, 200 ft wide | 10.50 psf | 5 psf | 15.00 psf | 15.50 psf |
| 20 psf | Flat, 30 ft wide | 14.00 psf | 5 psf | 20.00 psf | 20.00 psf |
| 25 psf | 2/12, 30 ft wide | 17.50 psf | None | 20.00 psf | 20.00 psf |
| 40 psf | Flat, 30 ft wide | 28.00 psf | None | 20.00 psf | 28.00 psf |
In a snow load calculator total, the surcharge goes on the formula load, never on the minimum, and the larger of the two governs. On a flat 20 psf site, 14 + 5 is 19 psf, so the 20 psf minimum still wins.
A 200 ft wide warehouse has 100 ft from eave to ridge, so its cutoff is 2°. A 1/4:12 roof at 1.19° falls under it and takes the 5 psf surcharge, while a 30 ft wide house only qualifies when dead flat.
Unbalanced Snow on Gable Roofs
Wind can strip one side of a 30 ft wide 6/12 gable roof and load the other side to 30 psf, the full ground snow load, against a 21 psf balanced load. Rafters need checking for both cases.
For hip and gable roofs 20 ft or less from eave to ridge with ridge-to-eave rafters, ASCE 7-16 places the full Is times pg on the leeward side and nothing on the windward side. Roofs flatter than 1/2:12 or steeper than 7/12 skip this case.
| Building Width | Pitch | Balanced Load | Windward | Leeward | Drift Height |
|---|---|---|---|---|---|
| 30 ft | 6/12 | 21.00 psf | 0 psf | 30.00 psf | None, short roof |
| 40 ft | 6/12 | 21.00 psf | 0 psf | 30.00 psf | None, short roof |
| 60 ft | 4/12 | 21.00 psf | 6.30 psf | 40.22 psf | 1.86 ft |
| 60 ft | 6/12 | 21.00 psf | 6.30 psf | 44.54 psf | 1.86 ft |
| 80 ft | 6/12 | 21.00 psf | 6.30 psf | 48.82 psf | 2.20 ft |
Past 20 ft from eave to ridge, the leeward side carries the balanced load plus a drift surcharge, and the windward side keeps 30% of the balanced load. On the 60 ft wide 6/12 roof the drift adds 23.54 psf over the first 7.02 ft from the ridge.
pd is the drift surcharge in psf, hd the drift height in feet, γ the snow density of 0.13pg + 14 lb per cubic foot capped at 30, and S the roof run for 1 ft of rise.
A steeper 8/12 roof on the same 60 ft building needs no unbalanced snow load calculator check at all. A little more pitch removes a 44.54 psf design case from the rafters, and the Roof Truss Calculator gives the layout to send with those loads.
ASCE 7-22, Eurocode and Other Codes
ASCE 7-22 drops the importance factor, so the flat roof formula becomes 0.7 times Ce times Ct times pg. Risk is built into four separate ground snow load maps, one for each risk category, instead.
That matters when mixing editions in one snow load calculator run. MiTek's ASCE 7-22 comparison gives Chesterfield, Missouri a 20 psf ground load under ASCE 7-16 but 18, 23, 26 and 30 psf by risk category under ASCE 7-22.
| Risk Category | ASCE 7-16 Flat Load | ASCE 7-22 Flat Load | 7-22 Map With 7-16 Is Applied Again |
|---|---|---|---|
| I | 11.20 psf | 12.60 psf | 10.08 psf |
| II | 14.00 psf | 16.10 psf | 16.10 psf |
| III | 15.40 psf | 18.20 psf | 20.02 psf |
| IV | 16.80 psf | 21.00 psf | 25.20 psf |
With an ASCE 7-22 ground load in a snow load calculator, set the importance factor to 1.0, or the risk is counted twice. That error turns a 21.00 psf hospital roof into 25.20 psf, as the last column shows for Ce and Ct of 1.0.
Ground loads also changed basis. STRUCTURE magazine reports that most roofs land at 0.91 to 1.30 times their ASCE 7-16 load, averaging 1.12, with the strength-level snow load factor cut from 1.6 to 1.0.
For a snow load calculator by zip code or address, the source is the ASCE Hazard Tool, which reports the mapped ground snow load for a site. Many mountain areas are case-study zones where the local building department sets the value instead.
A snow load calculator UK or Eurocode check uses EN 1991-1-3, where s is the shape coefficient times Ce, Ct and sk. On pitched roofs up to 30°, the Eurocode shape coefficient is 0.8, dropping to 0 at 60°.
| Eurocode Ground Load sk | Up to 30° | 35° | 45° | 60° and Steeper |
|---|---|---|---|---|
| 0.5 kN/m² | 0.400 kN/m² | 0.333 kN/m² | 0.200 kN/m² | 0 |
| 1.0 kN/m² | 0.800 kN/m² | 0.667 kN/m² | 0.400 kN/m² | 0 |
| 1.5 kN/m² | 1.200 kN/m² | 1.000 kN/m² | 0.600 kN/m² | 0 |
| 2.0 kN/m² | 1.600 kN/m² | 1.333 kN/m² | 0.800 kN/m² | 0 |
Those Eurocode values take Ce and Ct as 1.0, the Belgian national annex setting, and each country's annex sets its own. Canada's NBCC and India's IS 875 Part 4 use their own formulas, so an ASCE snow load calculator result does not transfer to them.
Practical Answers on Snow Weight
The four questions below come up most about roof snow. Each answer works a case not shown in the tables above, in both US and metric units where it helps.
How to calculate a snow load?
For a snow load calculator result, multiply the ground snow load by 0.7 and the exposure, thermal and importance factors, then by the slope factor. Check the result against the low-slope minimum and any rain-on-snow surcharge, and use the larger.
For a 50 psf ground load on an open, fully exposed site with a cold vented 8/12 roof, that is 0.7 x 0.9 x 1.1 x 1.0 x 50, or 34.65 psf. At 33.69°, a cold rough roof keeps a slope factor of 1.0, so the design load stays 34.65 psf.
Over a 40 x 30 ft plan, that snow load calculator case comes to 41,580 lb of snow. The same math in metric starts from 2.394 kPa of ground snow and ends at 1.659 kPa on the roof.
What is 20 psf snow load?
A 20 psf snow load is 20 pounds of snow on every square foot of roof, equal to 0.958 kPa or 97.6 kg/m². It takes 15.4 in of settled snow to reach it, but only 5.1 in of very wet snow.
In snow load calculator terms, fresh powder needs 64.1 in to weigh the same. As a ground snow load, 20 psf gives a 14.00 psf design load on a heated 6/12 roof, or 20 psf on roofs under 15° where the minimum governs.
How much do 12 inches of snow weigh per square foot?
Twelve inches of snow weighs 3.75 psf as fresh powder, 15.61 psf settled and 46.82 psf as very wet snow. A foot of ice weighs 57.25 psf, over 15 times the fresh snow figure.
Code drift checks in a snow load calculator use a set density instead, 0.13 times the ground snow load plus 14, up to 30 lb per cubic foot. On a 30 psf site that is 17.9 psf for each foot of snow depth.
What is snow load capacity?
Snow load capacity is the design snow load the roof framing was built for, set from the ground snow load and site factors. For a heated 40 x 30 ft house on a 30 psf site, it is 21 psf, or 25,200 lb across the plan.
In depth, that capacity holds 16.1 in of settled snow measured straight down, but only 5.4 in of very wet snow. Dead load from the roofing itself is separate, and the Roof Weight Calculator totals it.
Houses built before modern codes may not match today's snow load calculator figures. When the snow on a roof passes about 75% of its design load, plan to clear it with a roof rake from the ground before more snow or rain adds weight.