Steel I-beam size calculator for the lightest W-shape beam on a given span, checked for AISC bending, shear, deflection and bracing, with load capacity, span, beam weight and cost.
Finds the lightest wide-flange beam that passes bending, shear and deflection for your span and loads.
Steel Grade, Bracing and Limits
Point Load at Midspan
Steel Price
I-Beam Section Drawing
Lightest Steel I-Beam by Depth
| Depth | Lightest | Weight | Beam | Used, Governs |
|---|---|---|---|---|
| W6 | None | -- | -- | -- |
| W8 | W8×28 | 28 lb/ft | 560 lb | 91% deflection |
| W10 | W10×19 | 19 lb/ft | 380 lb | 93% deflection |
| W12 | W12×16 | 16 lb/ft | 320 lb | 87% deflection |
| W14 | W14×22 | 22 lb/ft | 440 lb | 45% deflection |
| W16 | W16×26 | 26 lb/ft | 520 lb | 31% bending |
| W18 | W18×35 | 35 lb/ft | 700 lb | 21% bending |
| W21 | W21×44 | 44 lb/ft | 880 lb | 15% bending |
| W24 | W24×55 | 55 lb/ft | 1,100 lb | 11% bending |
| W27 | W27×84 | 84 lb/ft | 1,680 lb | 6% bending |
| W30 | W30×90 | 90 lb/ft | 1,800 lb | 5% bending |
W12×16 Load Capacity Chart
| Span | Max Uniform Load | Governs |
|---|---|---|
| 8.0 ft | 6,253 plf | bending |
| 10.0 ft | 3,996 plf | bending |
| 12.0 ft | 2,770 plf | bending |
| 14.0 ft | 2,031 plf | bending |
| 16.0 ft | 1,486 plf | deflection |
| 18.0 ft | 1,043 plf | deflection |
| 20.0 ft | 761 plf | deflection |
| 24.0 ft | 440 plf | deflection |
| 28.0 ft | 277 plf | deflection |
| 32.0 ft | 186 plf | deflection |
Step-by-Step Steel I-Beam Math
Steel I-Beam Size Calculator Results for a 20 Foot Span
A 20 ft simply supported floor beam carrying 12 ft of floor at 15 psf dead and 40 psf live needs a W12×16 in A992 steel. Deflection decides it: live sag is 0.58 in against an L/360 limit of 0.67 in.
Every steel I-beam size calculator run follows the same order. Floor loads become a line load, the line load becomes moment, shear and sag, and each W-shape from lightest to heaviest is tested until one passes all three.
M is the maximum moment in kip-ft, V is the end shear in kips, w is the line load in kips per foot including the beam's own weight, L is the span in feet and P is a point load at midspan.
Here w is 15 psf × 12 ft = 180 plf dead, plus 16 plf of beam, plus 40 psf × 12 ft = 480 plf live, for 676 plf. The moment is 0.676 × 20² ÷ 8 = 33.8 kip-ft and the shear is 6.76 kips at each end.
Ma and Va are the allowable moment and shear under ASD, Fy is the yield stress in ksi, Zx is the plastic section modulus, d is the depth and tw is the web thickness, all in inches.
A W12×16 has Zx of 20.1 in³, so a braced top flange gives 50 × 20.1 ÷ 1.67 ÷ 12 = 50.1 kip-ft, or 67% used. Its web gives 52.80 kips of shear, only 13% used, as AISC 360-16 Chapters F and G set out.
Δ is the midspan deflection in inches, E is 29,000 ksi for all structural steel and I is the moment of inertia in in⁴. The 480 plf live load alone sags the W12×16 0.58 in, and the full 676 plf sags it 0.81 in against L/240 = 1.00 in.
The live limit needs an I of at least 89.4 in⁴. A W12×14 has 88.6 in⁴ and misses by 0.9%, so the 2 lb/ft heavier W12×16, at 103 in⁴, is the lightest beam that works.
| Tributary Width (ft) | Dead + Live (plf) | Lightest Beam | Capacity Used | Governs |
|---|---|---|---|---|
| 4 | 60 + 160 | W8×10 | 97% | Deflection |
| 8 | 120 + 320 | W12×14 | 67% | Deflection |
| 12 | 180 + 480 | W12×16 | 87% | Deflection |
| 16 | 240 + 640 | W12×19 | 92% | Deflection |
| 20 | 300 + 800 | W12×22 | 95% | Deflection |
| 24 | 360 + 960 | W14×22 | 90% | Deflection |
Tributary width, the first input to any steel I-beam size calculator estimate, is half the joist span on each side of the beam added together.
For a 20 foot span, every width from 4 to 24 ft ends up deflection-governed, which is why a stiffer, deeper section beats a heavier shallow one.
In metric terms, the same steel I-beam size calculator case is a 6.1 m span with 9.63 kN/m of applied load and 45.8 kN·m of moment against 68.0 kN·m allowed.
The W12×16 weighs 23.8 kg/m. The Beam Deflection Calculator breaks down the sag for other load cases.
Deflection and Depth Decide the Lightest Beam
On typical floor spans, steel I-beam size calculator results are set by sag, not strength, so depth matters more than weight. For the 20 ft case, the lightest passing beam in each depth runs from W8×28 to W24×55, and the W12 is the lightest of all.
| Depth Family | Lightest That Passes | Weight for 20 ft (lb) | Capacity Used | Governs |
|---|---|---|---|---|
| W6 | None | -- | -- | -- |
| W8 | W8×28 | 560 | 91% | Deflection |
| W10 | W10×19 | 380 | 93% | Deflection |
| W12 | W12×16 | 320 | 87% | Deflection |
| W14 | W14×22 | 440 | 45% | Deflection |
| W16 | W16×26 | 520 | 31% | Bending |
| W18 | W18×35 | 700 | 21% | Bending |
| W21 | W21×44 | 880 | 15% | Bending |
| W24 | W24×55 | 1,100 | 11% | Bending |
Headroom is the usual reason to cap depth in a steel I-beam size calculator search, and it has a price. Holding the beam to 8 in deep calls for a W8×28, which is 240 lb heavier than the W12×16 for the same 20 ft and the same loads.
Higher-strength steel does not fix a sag problem, since every grade has the same E. In a steel I-beam size calculator run at A36, the W12×16 still passes, but bending rises to 94% and takes over, while Grade 65 only drops bending to 52%.
The deflection limit moves a steel I-beam size calculator result more than the grade does. IBC Table 1604.3 sets L/360 live and L/240 total for floors, and roofs with no ceiling go down to L/180 and L/120.
| Live / Total Limit | Typical Use | Live Limit at 20 ft | Lightest Beam | Governs |
|---|---|---|---|---|
| L/180 / L/120 | Roof, no ceiling | 1.33 in | W12×14 | Bending |
| L/240 / L/180 | Roof, nonplaster ceiling | 1.00 in | W12×14 | Bending |
| L/360 / L/240 | Floors, ceramic tile | 0.67 in | W12×16 | Deflection |
| L/720 / L/360 | Natural stone tile | 0.33 in | W14×22 | Deflection |
The tile limits come from the TCNA Handbook, which the Ceramic Tile Education Foundation quotes as L/360 for ceramic and porcelain and L/720 for natural stone.
A stone floor over this beam needs a W14×22, 6 lb/ft heavier than the W12×16 that carries ceramic tile.
Span Table From 10 to 32 Feet
At 12 ft of tributary floor and 15/40 psf, the steel I-beam size calculator result goes from a W6×8.5 at 10 ft to a W16×31 at 32 ft. Each row is the first W-shape by weight that passes bending, shear and deflection.
| Span (ft) | Lightest Beam | Actual Depth (in) | Capacity Used | Span ÷ 20 Rule (in) |
|---|---|---|---|---|
| 10 | W6×8.5 | 5.83 | 75% | 6.0 |
| 12 | W8×10 | 7.89 | 63% | 7.2 |
| 14 | W8×10 | 7.89 | 100% | 8.4 |
| 16 | W10×12 | 9.87 | 85% | 9.6 |
| 18 | W12×14 | 11.9 | 74% | 10.8 |
| 20 | W12×16 | 12.0 | 87% | 12.0 |
| 24 | W12×22 | 12.3 | 99% | 14.4 |
| 28 | W16×26 | 15.7 | 82% | 16.8 |
| 32 | W16×31 | 15.9 | 98% | 19.2 |
The span ÷ 20 depth rule lands close up to 20 ft and then overshoots. At 32 ft it asks for a 19 in beam, while a W16×31 passes at 98%, so the rule is a starting depth for a steel I beam span calculator check, not a size.
The 14 ft row is right at the edge: the W8×10 uses 99.5% of its live-load sag allowance. Any extra load, such as a heavier floor finish, moves that span to the next size up in a steel I-beam size calculator check.
Load Capacity Charts for 6, 8 and 12 Inch Beams
A W8×10 at 12 ft carries 1,053 plf of added uniform load, and a W8×31 of the same depth carries 3,761 plf, more than three times as much.
Each steel I-beam size calculator capacity here is the load on top of the beam's own weight, split 27% dead and 73% live, in A992 under ASD with a braced top flange.
The deflection limits are L/360 live and L/240 total. In each cell, B means bending governs, D means deflection and S means shear, the same three checks any I beam load capacity calculator has to pass.
| Beam | 8 ft | 10 ft | 12 ft | 14 ft | 16 ft | 18 ft | 20 ft | 24 ft |
|---|---|---|---|---|---|---|---|---|
| W6×9 | 1,892 D | 969 D | 561 D | 353 D | 237 D | 166 D | 121 D | 67 D |
| W6×12 | 2,550 D | 1,306 D | 756 D | 476 D | 319 D | 224 D | 163 D | 91 D |
| W6×15 | 3,157 B | 1,719 D | 995 D | 626 D | 420 D | 295 D | 215 D | 121 D |
| W6×20 | 4,627 B | 2,446 D | 1,415 D | 891 D | 597 D | 419 D | 306 D | 173 D |
| W6×25 | 5,869 B | 3,155 D | 1,826 D | 1,150 D | 770 D | 541 D | 394 D | 224 D |
| W8×10 | 2,724 B | 1,740 B | 1,053 D | 663 D | 444 D | 312 D | 227 D | 132 D |
| W8×13 | 3,542 B | 2,262 B | 1,354 D | 853 D | 571 D | 401 D | 292 D | 169 D |
| W8×18 | 5,284 B | 3,375 B | 2,116 D | 1,333 D | 893 D | 627 D | 457 D | 265 D |
| W8×24 | 7,180 B | 4,587 B | 2,827 D | 1,780 D | 1,193 D | 838 D | 611 D | 353 D |
| W8×31 | 9,441 B | 6,031 B | 3,761 D | 2,368 D | 1,586 D | 1,114 D | 812 D | 470 D |
| W8×40 | 12,373 B | 7,904 B | 4,991 D | 3,143 D | 2,106 D | 1,479 D | 1,078 D | 624 D |
| W12×14 | 5,413 B | 3,459 B | 2,398 B | 1,758 B | 1,278 D | 897 D | 654 D | 379 D |
| W12×16 | 6,253 B | 3,996 B | 2,770 B | 2,031 B | 1,486 D | 1,043 D | 761 D | 440 D |
| W12×26 | 11,576 B | 7,399 B | 5,130 B | 3,762 B | 2,874 B | 2,066 D | 1,506 D | 872 D |
| W12×40 | 17,513 S | 11,337 B | 7,861 B | 5,765 B | 4,404 B | 3,110 D | 2,267 D | 1,312 D |
Values are in pounds per linear foot. Doubling the span cuts a deflection-governed capacity by about eight times, so a W8×10 drops from 1,053 plf at 12 ft to 132 plf at 24 ft.
Most 6 inch steel I-beam capacities in an I beam load capacity chart are deflection-governed from 10 ft on. The W6×15 is the odd one out at 8 ft: its flanges are noncompact at 50 ksi, so its bending strength is cut to 94.2% of the plastic moment.
The W12×40 at 8 ft is the only shear-governed cell, as short, deep, heavily loaded beams tend to be.
A steel I-beam size calculator check at a new span or load split changes every number here, so this steel I beam load chart is a guide for a first choice only.
Reach of a 12 Inch I-Beam at Common Loads
A W12×16 spans 23.0 ft at 500 plf and 18.3 ft at 1,000 plf. The heaviest common 12 in size here, the W12×53, reaches 29.3 ft at 1,000 plf, with the same 27/73 dead-live split and L/360 floor limits.
| Beam | 300 plf | 500 plf | 750 plf | 1,000 plf | 1,500 plf | 2,000 plf |
|---|---|---|---|---|---|---|
| W12×14 | 25.9 ft | 21.9 ft | 19.1 ft | 17.4 ft | 15.1 ft | 13.1 ft |
| W12×16 | 27.3 ft | 23.0 ft | 20.1 ft | 18.3 ft | 15.9 ft | 14.1 ft |
| W12×19 | 29.5 ft | 24.9 ft | 21.7 ft | 19.7 ft | 17.2 ft | 15.6 ft |
| W12×26 | 34.2 ft | 28.9 ft | 25.2 ft | 22.9 ft | 20.0 ft | 18.2 ft |
| W12×40 | 38.8 ft | 33.1 ft | 28.9 ft | 26.3 ft | 23.0 ft | 20.9 ft |
| W12×53 | 42.7 ft | 36.7 ft | 32.2 ft | 29.3 ft | 25.6 ft | 23.2 ft |
The load in each column is the applied load before the beam's own weight, so a W12×53 carries 53 plf more than its column heading.
Tripling the steel from W12×16 to W12×53 adds only 11 ft of reach at 1,000 plf, because sag grows with the fourth power of the span. Each extra foot of reach costs more steel than the last in steel I-beam size calculator results.
This metal I beam span chart assumes both ends sit on solid bearing and the top flange is braced. Without that bracing, the reach at the heavier loads drops sharply, as the next section works out.
Unbraced Top Flanges and Lateral-Torsional Buckling
In an unbraced steel I-beam size calculator case, a W12×16 over 20 ft keeps only 17.1% of its braced bending strength, 8.57 kip-ft instead of 50.1 kip-ft. Lateral-torsional buckling lets the compression flange twist sideways before the steel yields.
Lp is the longest unbraced length that keeps full plastic strength, ry is the weak-axis radius of gyration and E and Fy are in ksi. Past Lr, AISC F2 switches to the elastic buckling equation.
| Unbraced Length (ft) | Allowable Moment (kip-ft) | Share of Braced Strength | Lightest Beam for the 20 ft Case |
|---|---|---|---|
| 0 (fully braced) | 50.15 | 100% | W12×16 |
| 5 | 44.02 | 87.8% | W12×16 |
| 10 | 26.90 | 53.6% | W10×19 |
| 20 | 8.57 | 17.1% | W10×26 |
The narrow 3.99 in flange of the W12×16 gives it an Lp of only 2.73 ft and an Lr of 8.04 ft. The wider 5.77 in flange of the W10×26 stretches those to 4.80 and 14.94 ft, which is why a shallower beam wins once bracing is lost.
Joists or decking fastened to the top flange brace it at their spacing. A beam that only carries a wall or a post with nothing tied to its top needs the full unbraced span in any steel I-beam size calculator check.
Flange slenderness cuts strength too, even in a fully braced steel I-beam size calculator case, because thin, wide flanges can buckle locally first.
At 50 ksi, ten W-shapes have noncompact flanges, including the W6×8.5, W8×10 and W6×15, which keep 97.6%, 98.8% and 94.2% of their plastic moment under AISC F3.
Moment of Inertia From Flange and Web Sizes
The moment of inertia of an I-beam is the rectangle around it minus the two empty rectangles beside the web. For a W8×10 that gives 29.8 in⁴, against 30.8 in⁴ in the AISC table, because the formula leaves out the fillets.
bf is the flange width, d is the overall depth, tw is the web thickness and tf is the flange thickness, all in inches. The elastic section modulus is then Sx = Ix ÷ (d ÷ 2).
| Beam | d × bf × tf × tw (in) | Ix by Formula (in⁴) | Ix AISC (in⁴) | Fillet Share |
|---|---|---|---|---|
| W8×10 | 7.89 × 3.94 × 0.205 × 0.17 | 29.8 | 30.8 | 3.4% |
| W10×19 | 10.2 × 4.02 × 0.395 × 0.25 | 93.7 | 96.3 | 2.7% |
| W12×16 | 12.0 × 3.99 × 0.265 × 0.22 | 100.5 | 103 | 2.5% |
| W12×26 | 12.2 × 6.49 × 0.38 × 0.23 | 201.0 | 204 | 1.5% |
| W8×31 | 8.0 × 8.0 × 0.435 × 0.285 | 108.3 | 110 | 1.6% |
Hand-calculated values run 1.5 to 3.4% low, a safe-side error for sag, and light sections lose the most. A W12×14 misses the 20 ft case by 0.9%, so a steel I-beam size calculator answer can flip on a 3% gap in I.
The plastic modulus Zx for bending sums each half's area times its centroid distance. The W12×16 works out to 19.6 in³ by flange-and-web rectangles against 20.1 in³ in the table, and the Bending Stress Calculator turns either into a stress.
Weight per Foot, Kilograms per Meter and Cost
An I-beam's weight in kg per meter is its lb/ft figure times 1.488. A W12×16 is 23.8 kg/m, so a 6 m length weighs 142.9 kg, and the second number in every W-shape name is the weight per foot.
| Beam | lb/ft | kg/m | 12 ft Length (lb) | 20 ft Length (lb) | 6 m Length (kg) |
|---|---|---|---|---|---|
| W6×9 | 9 | 13.4 | 108 | 180 | 80.4 |
| W8×10 | 10 | 14.9 | 120 | 200 | 89.3 |
| W8×18 | 18 | 26.8 | 216 | 360 | 160.7 |
| W10×19 | 19 | 28.3 | 228 | 380 | 169.7 |
| W12×16 | 16 | 23.8 | 192 | 320 | 142.9 |
| W12×26 | 26 | 38.7 | 312 | 520 | 232.2 |
| W14×22 | 22 | 32.7 | 264 | 440 | 196.4 |
| W16×26 | 26 | 38.7 | 312 | 520 | 232.2 |
This I beam weight chart in kg, read as a steel I beam sizes chart, makes clear that weight is a poor guide to strength. The W12×16 is lighter than the W10×19 yet carries the 20 ft floor with more margin, 87% used against 93%.
Steel is sold by weight, so the lightest passing size from a steel I-beam size calculator is also the cheapest stock. Cutting and delivery add to the steel price, and the beam weight also sets what lifting gear the job needs.
Point Loads, Bearing Walls and Cantilevers
A post carrying 4,000 lb dead and 6,000 lb live at the middle of the 20 ft beam moves the steel I-beam size calculator answer from W12×16 to W12×26. Bending now governs at 91%, with 84.3 kip-ft required against 92.8 kip-ft allowed.
| Case | Loads | Lightest Beam | Capacity Used | Governs |
|---|---|---|---|---|
| 20 ft floor beam | 180 plf dead, 480 plf live | W12×16 | 87% | Deflection |
| Same, plus a midspan post | 4,000 lb dead, 6,000 lb live | W12×26 | 91% | Bending |
| 20 ft under a bearing wall | 1,000 plf dead, 800 plf live | W14×26 | 93% | Deflection |
| 6 ft cantilever | 180 plf dead, 480 plf live | W6×8.5 | 86% | Bending |
A point load at midspan makes twice the moment of the same weight spread evenly, PL/4 against WL/8, where W is the total spread load. Reactions and moments for posts away from midspan come from the Beam Load Calculator.
In a steel I-beam size calculator cantilever case, the support carries wL²/2, four times the simple-span moment, and its sag limit uses twice the cantilever length under IBC Table 1604.3. The 6 ft arm is held to 144 in ÷ 360 = 0.40 in of live sag.
Each end of the 20 ft floor beam pushes 6.76 kips into its post. Web bearing, web crippling and the connection are separate checks, and the footing under the post goes through the Bearing Pressure Calculator.
W-Shape Sizing, Measuring and Pricing
These steel I-beam size calculator answers use A992 steel, ASD, L/360 live and L/240 total limits and a braced top flange unless a case says otherwise. W-shape dimensions and properties are the AISC shapes table values.
What is a steel I-beam size calculator?
It is a search through the wide-flange table for the lightest beam that passes bending, shear and deflection at one span and load. For a 20 ft floor beam carrying 12 ft of floor at 15/40 psf, the search stops at W12×16.
What are steel I beam calculations?
They are four steps: turn the loads into a line load, get the moment and shear, compare them with the section's strength, and check sag. The 20 ft example gives 33.8 kip-ft against 50.1, 6.76 kips against 52.80, and 0.58 in against 0.67.
Load capacity in a steel I-beam size calculator result works the sizing math in reverse. It raises the uniform load until the first check fails, which for a W12×16 over 20 ft is 761 plf on top of its own weight.
How do you calculate a minimum beam size?
Work out the required plastic modulus and the required moment of inertia, then take the lightest beam that meets both. At 33.8 kip-ft, Zx must reach 33.8 × 12 × 1.67 ÷ 50 = 13.5 in³, and the L/360 limit needs Ix of 89.4 in⁴.
The shortcut S = M ÷ Fy gives 8.1 in³ and points to a W10×12, which leaves out the 1.67 safety factor and sag. That beam sags 1.11 in under live load, 66% over the limit, so the W12×16 stays the steel I-beam size calculator minimum.
How to measure I beam calculator?
Measure the overall depth, the flange width, the flange thickness and the web thickness, then match them to the W-shape table before a steel I-beam size calculator check of an existing beam.
Flange thickness separates look-alikes: a W8×10 has a 0.205 in flange and a W8×13 a 0.255 in flange, both about 4 in wide.
Nominal depth is only a family name. A W8×24 measures 7.93 in deep and a W8×31 measures 8.00 in, while a W12×26 shows its weight in a 6.49 in flange against 4.03 in on a W12×22.
What is the price of a 12 ft I-beam?
Price is weight times the local rate per pound. At $1.25 per lb, a 12 ft W8×10 at 120 lb is $150, a W12×16 at 192 lb is $240 and a W12×26 at 312 lb is $390, before cutting and delivery.
A 20 foot I-beam scales the same way: the W12×16 from the 20 ft example weighs 320 lb and costs $400 at that rate. Mill and service-center prices change with the steel market, so a current quote per pound sets the real figure.