Wind load calculator answers in pounds and psf, from plain air pressure on a sign or a panel to ASCE 7-16 wall push, roof uplift, base shear, and the DP rating that a window needs.
Wind load from speed, air density and the area facing the wind, as F = ½ρV² × A × sin θ.
Site, Topography & Enclosure
Wind Load Diagram
Wind Speed to Pressure Chart
| Wind Speed | Dynamic ½ρV² | Exposure B qz | Exposure C qz | Exposure D qz |
|---|---|---|---|---|
| 60 mph | 9.20 psf | 5.64 psf | 7.85 psf | 9.26 psf |
| 70 mph | 12.53 psf | 7.68 psf | 10.69 psf | 12.60 psf |
| 80 mph | 16.36 psf | 10.03 psf | 13.96 psf | 16.46 psf |
| 90 mph | 20.71 psf | 12.69 psf | 17.66 psf | 20.83 psf |
| 100 mph | 25.56 psf | 15.67 psf | 21.81 psf | 25.71 psf |
| 110 mph | 30.93 psf | 18.96 psf | 26.39 psf | 31.11 psf |
| 115 mph | 33.81 psf | 20.72 psf | 28.84 psf | 34.00 psf |
| 130 mph | 43.20 psf | 26.48 psf | 36.85 psf | 43.45 psf |
| 150 mph | 57.52 psf | 35.25 psf | 49.07 psf | 57.85 psf |
| 180 mph | 82.83 psf | 50.76 psf | 70.65 psf | 83.31 psf |
Step-by-Step Wind Load Math
Mph to Pounds of Force in a Wind Load Calculator
A 100 mph wind pushes about 2,556 lb on a 100 sq ft wall it hits squarely. Halve the speed to 50 mph and the push falls to 639 lb, a quarter of the load, because pressure follows the square of the speed.
The figures below are plain air pressure at sea level, with air at 1.225 kg/m³ and no code factors. That is the right wind load calculator scale for a sign face, a solar panel or a fence board, not yet for a house.
| Wind Speed | km/h | Dynamic Pressure | Pascals | Force on 100 sq ft |
|---|---|---|---|---|
| 30 mph | 48 | 2.30 psf | 110 Pa | 230 lb |
| 50 mph | 80 | 6.39 psf | 306 Pa | 639 lb |
| 70 mph | 113 | 12.53 psf | 600 Pa | 1,253 lb |
| 90 mph | 145 | 20.71 psf | 991 Pa | 2,071 lb |
| 100 mph | 161 | 25.56 psf | 1,224 Pa | 2,556 lb |
| 120 mph | 193 | 36.81 psf | 1,763 Pa | 3,681 lb |
| 150 mph | 241 | 57.52 psf | 2,754 Pa | 5,752 lb |
| 180 mph | 290 | 82.83 psf | 3,966 Pa | 8,283 lb |
q is the dynamic pressure in pascals, ρ is air density in kg/m³ and V is wind speed in m/s. One psf equals 47.88 Pa, so 100 mph, or 44.7 m/s, gives 1,224 Pa, which is 25.56 psf.
F is the force, A the surface area and θ the surface angle from horizontal. A wall at 90° takes its full area, and a panel tilted back shows the wind only part of its face, so a wind load calculator answer for a panel at 30° is half the wall value.
| Surface Angle | Force on 100 sq ft at 100 mph |
|---|---|
| 90° (vertical wall) | 2,556 lb |
| 60° | 2,214 lb |
| 45° | 1,808 lb |
| 30° | 1,278 lb |
| 15° | 662 lb |
| 10° | 444 lb |
Roofs are the exception to that sine rule. A low roof barely faces a level wind, yet it still lifts, so a roof wind load calculator estimate has to use ASCE 7 pressure coefficients instead of the angle.
Air density changes any wind load calculator answer at the same speed. On that 100 sq ft wall at 100 mph, a 0 °F day pushes 2,885 lb, a 100 °F day 2,369 lb, and a site at 5,000 ft only 2,203 lb.
How do you calculate wind pressure?
Square the wind speed in m/s and multiply by half the air density. At 30 m/s that is 0.5 × 1.225 × 30² = 551 Pa, or 11.5 psf. In US units every wind load calculator formula starts from 0.00256 × V², with V in mph and the answer in psf.
Force is that pressure times the area it lands on, so 20 psf on 100 sq ft is 2,000 lb. A building adds height, terrain, gust and shape factors on top, which the next sections work through.
What is a 20 psf wind load?
A 20 psf wind load is the plain dynamic pressure of an 88.4 mph wind at sea level, inside the 74 to 95 mph range of a Category 1 hurricane. On a 100 sq ft wall it adds up to 2,000 lb, the figure any plain wind load calculator method reaches.
Under ASCE 7-16, the windward wall of a 30 ft house in open terrain reaches 24.3 psf at 115 mph, so 20 psf is a light design wind. It also sits just above the 16 psf floor the code sets for walls and cladding.
Simplified Pressure Undershoots a Corner Window
At 130 mph, plain ½ρV² gives 43.2 psf on every surface. ASCE 7-16 gives a 3 × 5 ft window near a house corner -54.8 psf of suction, 27% more than the plain figure, while the windward wall gets only +31.1 psf.
The house behind these wind load calculator numbers is 60 × 40 ft, 30 ft to mean roof height, enclosed, in open Exposure C terrain at sea level. Every value is strength level, before the 0.6 factor used for allowable stress design.
| Load at 130 mph | Pressure | vs Plain 43.2 psf |
|---|---|---|
| Velocity pressure at roof, qh | 36.12 psf | -16% |
| Windward wall | +31.06 psf | -28% |
| Leeward wall | -21.85 psf | -49% |
| Roof uplift, wind along the ridge | -40.28 psf | -7% |
| 3 × 5 ft window, wall middle | -45.11 psf | +4% |
| 3 × 5 ft window, near a corner | -54.83 psf | +27% |
The plain number misses height, terrain, gusts, the building's shape and the air pushing out from inside. That is fine for a quick sign estimate, but a wind load calculator result for glazing, ties or sheathing needs the code path.
What is a wind load?
Wind load is the push and suction moving air puts on a structure. It acts as inward pressure on the windward wall, outward suction on the leeward and side walls, and uplift that tries to peel the roof off.
The frame takes it as sideways base shear and overturning. The 60 × 40 ft house at 130 mph carries 71,846 lb of base shear and 1,077,692 lb·ft of overturning moment at strength level.
What is a wind load calculator?
Behind any wind load calculator sits one conversion, from wind speed to pressure on a surface and then to force in pounds or newtons. A plain version stops at ½ρV², while a code version applies ASCE 7 or another standard.
The gap is large on a real building. At 130 mph the plain answer is the same 43.2 psf everywhere, while ASCE 7-16 ranges from -21.9 psf on the leeward wall to -54.8 psf on a small corner window.
Why Does Building Height Affect Wind Pressure?
Wind slows near the ground, so height and terrain set how fast the air is at the roof. At 130 mph the 60 × 40 × 30 ft house takes 51,244 lb of base shear in Exposure B, 71,846 lb in C and 85,009 lb in D.
ASCE 7-16 puts urban, suburban and wooded ground with closely spaced obstructions upwind in Exposure B. Exposure D is flat, open ground or water at a shoreline, and Exposure C covers open fields and everything else.
The exposure factor Kz carries both effects into every wind load calculator pressure. Below 15 ft the code holds Kz at its 15 ft value, so a shed and a one-story house on the same open lot share it.
| Height Above Ground | Exposure B Kz | Exposure C Kz | Exposure D Kz |
|---|---|---|---|
| 15 ft or less | 0.575 | 0.849 | 1.030 |
| 20 ft | 0.624 | 0.902 | 1.083 |
| 30 ft | 0.701 | 0.982 | 1.162 |
| 40 ft | 0.761 | 1.044 | 1.222 |
| 60 ft | 0.854 | 1.137 | 1.311 |
| 100 ft | 0.988 | 1.266 | 1.433 |
| 200 ft | 1.205 | 1.464 | 1.616 |
A 100 ft building in Exposure B still sees less pressure than a 30 ft house on a beach, at 0.988 against 1.162. Between two exposures, the more open one is the safe wind load calculator choice.
z is height in ft, zg is the gradient height and α is the terrain exponent. ASCE 7-16 uses α = 7.0 and zg = 1,200 ft for B, 9.5 and 900 ft for C, and 11.5 and 700 ft for D.
Thin Air at Altitude, Faster Air Over Hills
A site at 5,280 ft carries about 17% less wind pressure than one at sea level, because the air is thinner. ASCE 7-16 added the ground elevation factor Ke for this, and Denver works out near 0.82.
ze is the ground elevation above sea level in ft. ASCE 7-16 also allows Ke = 1.0 at any site, so the cut is optional, and a wind load calculator result at Ke 1.0 always errs on the safe side.
| Ground Elevation | Ke | qh at 130 mph, Exposure C, 30 ft |
|---|---|---|
| Sea level | 1.000 | 36.12 psf |
| 1,000 ft | 0.964 | 34.83 psf |
| 2,500 ft | 0.913 | 32.98 psf |
| 5,000 ft | 0.834 | 30.12 psf |
| 5,280 ft | 0.826 | 29.84 psf |
| 7,500 ft | 0.762 | 27.52 psf |
The Denver figure matches the ASCE 7-16 change summary from the ASCE Northeast Texas Branch, which reports an 18% drop in design pressure there. The pressures in the table are for 130 mph, Exposure C and a 30 ft roof.
How do topographic effects influence wind load calculations?
Wind speeds up as it climbs a ridge, an escarpment or an isolated hill, and the topographic factor Kzt multiplies the velocity pressure one for one.
A Kzt of 1.2 turns 36.12 psf into 43.35 psf, adding a full 20% to every wind load calculator pressure on the house.
ASCE 7-16 applies Kzt only to hills that stand well above the terrain around them, at sites in the upper half of the slope or near the crest. Flat ground and gentle rolling land stay at 1.0, and so do valleys.
A 60 × 40 ft House From 100 to 170 mph
At 115 mph this enclosed 30 ft house in Exposure C sees +24.3 psf on the windward wall, -31.5 psf of roof uplift and 56,223 lb of wind base shear, with the wind on its 60 ft face.
| Basic Wind Speed | qh | Windward Wall | Leeward Wall | Side Walls | Roof Uplift | Base Shear | Base Shear at 0.6W |
|---|---|---|---|---|---|---|---|
| 100 mph | 21.37 psf | +18.38 psf | -12.93 psf | -16.56 psf | -23.83 psf | 42,513 lb | 25,508 lb |
| 115 mph | 28.27 psf | +24.31 psf | -17.10 psf | -21.91 psf | -31.52 psf | 56,223 lb | 33,734 lb |
| 130 mph | 36.12 psf | +31.06 psf | -21.85 psf | -27.99 psf | -40.28 psf | 71,846 lb | 43,108 lb |
| 150 mph | 48.09 psf | +41.36 psf | -29.10 psf | -37.27 psf | -53.62 psf | 95,653 lb | 57,392 lb |
| 170 mph | 61.77 psf | +53.12 psf | -37.37 psf | -47.87 psf | -68.87 psf | 122,861 lb | 73,717 lb |
These building wind load calculator values follow the ASCE 7-16 directional method with Kd 0.85, Kzt 1.0 and sea level. Wall pressures include the inside air pushing the worst way, which is why leeward and side walls show suction.
Roof uplift uses the low-slope coefficient, which ASCE 7 applies at every pitch when wind blows along the ridge. That case sets the largest uplift near the windward edge, the load hurricane ties and roof-to-wall straps hold down.
Uplift works against the dead load the rafters were sized for on the Rafter Span Calculator. At 130 mph the -40.28 psf of uplift is four times a typical 10 psf shingle roof, so the connectors carry the difference.
An open garage door in a storm can make an enclosed house partially enclosed. At 130 mph that raises roof uplift from -40.28 psf to -53.64 psf and the windward wall from +31.06 to +44.43 psf.
Light winds hit a code floor in any wind load calculator for buildings. ASCE 7-16 sets it at 16 psf on the wall area plus 8 psf on the roof area seen from the wind.
Below about 82 mph the calculated base shear on this house drops under that floor of 28,800 lb, from 1,500 sq ft of wall and the 600 sq ft profile of a 6:12 gable.
Studs take the windward push as bending between floors. The Bending Stress Calculator checks a stud against that pressure times its spacing.
DP Ratings That Windows and Garage Doors Need
A 3 × 5 ft window on this house needs DP 30 at 130 mph in the middle of a wall and DP 35 within 3.6 ft of a corner. The numbers assume a 36 ft least building width and a roof pitch over 10°.
| Opening | Area | 115 mph | 130 mph | 150 mph | 170 mph |
|---|---|---|---|---|---|
| 3 × 5 ft window, wall middle | 15 sq ft | DP 25 | DP 30 | DP 40 | DP 50 |
| 3 × 5 ft window, near corner | 15 sq ft | DP 30 | DP 35 | DP 45 | DP 60 |
| 3 × 6 ft 8 in door, wall middle | 20 sq ft | DP 25 | DP 30 | DP 40 | DP 50 |
| 6 × 6 ft 8 in slider, wall middle | 40 sq ft | DP 20 | DP 30 | DP 35 | DP 45 |
| 16 × 7 ft garage door, wall middle | 112 sq ft | DP 20 | DP 25 | DP 35 | DP 45 |
| 16 × 7 ft garage door, near corner | 112 sq ft | DP 25 | DP 30 | DP 35 | DP 45 |
Each rating is the larger of inward pressure and suction at 0.6W, rounded up to the next 5 psf, with DP 15 as the lowest. A window rated DP 30 is built for 30 psf at allowable stress.
Bigger openings get lower ratings in any wind load calculator at the same speed. ASCE 7 averages gusts over the whole effective wind area, so a 112 sq ft garage door needs DP 25 at 130 mph while a 15 sq ft window needs DP 30.
The corner strip width a is 10% of the least building width or 0.4 times the roof height, whichever is less, but never under 4% of the least width or 3 ft. On a 36 ft wide house that is 3.6 ft from each corner.
DASMA garage door wind load guidance works from these same ASCE 7 wall pressures, so a wind load calculator for windows and doors uses one method for both.
A roof slope of 10° or less trims every wall coefficient by 10%, which can drop a door or window one DP step on a low-slope house.
In a wind-borne debris region, where the ASCE 7-16 basic wind speed is 140 mph or more, or 130 mph within one mile of the coast, glazing also needs impact resistance or shutters on top of the DP rating.
What safety factors are included in ASCE 7 wind load calculations?
ASCE 7-16 builds its margin into the wind map itself, using a return period of about 700 years for Risk Category II. Strength design then applies a 1.0 load factor on W, and allowable stress design takes 0.6W.
That 0.6 is why a window facing 45.11 psf of strength-level suction needs only DP 30, since 0.6 × 45.11 is 27.07 psf.
Material design adds its own resistance factors on top, such as those in the NDS for wood and AISC for steel. Every wind load calculator result labeled ASD already carries that 0.6.
Basic Wind Speed Comes From a Map, Not a Forecast
The speed for a US building is read from the ASCE 7 map for its risk category. Most houses use the Risk Category II map, and its speeds are 3-second gusts at 33 ft in Exposure C.
A wind load calculator by zip code needs that mapped speed first. The ATC Hazards by Location site and the ASCE Hazard Tool both return the ASCE 7-16 basic wind speed for an address.
Maps change between editions. In St. Augustine, Florida, the speed went from 140 mph in ASCE 7-10 to 150 mph in ASCE 7-16, which raises every wind load calculator pressure there by (150 ÷ 140)², or 15%.
| Basic Wind Speed | Exposure B qh | Exposure C qh | Exposure D qh | Plain ½ρV² |
|---|---|---|---|---|
| 100 mph | 15.24 psf | 21.37 psf | 25.29 psf | 25.56 psf |
| 115 mph | 20.16 psf | 28.27 psf | 33.45 psf | 33.81 psf |
| 130 mph | 25.76 psf | 36.12 psf | 42.74 psf | 43.20 psf |
| 150 mph | 34.30 psf | 48.09 psf | 56.90 psf | 57.52 psf |
| 180 mph | 49.39 psf | 69.25 psf | 81.94 psf | 82.83 psf |
The wind load calculator ASCE 7-16 velocity pressures in the table are at 30 ft with Kd 0.85, Kzt 1.0 and sea level. Exposure D at 30 ft lands within about 1% of the plain air pressure, while Exposure B comes in 40% lower.
What is the difference between basic wind speed and design wind speed?
Basic wind speed is the 3-second gust from the ASCE 7 map for the risk category, at 33 ft in Exposure C. ASCE 7-16 maps are strength-level, so that speed goes straight into the velocity pressure.
Older codes used an allowable-stress design speed, the basic speed times √0.6. A 130 mph ASCE 7-16 speed matches about 101 mph in that older sense, and mixing the two in a wind load calculator misstates pressure by 67%.
Outside the US, Air Density Barely Moves the Answer
A 40 m/s wind, or 144 km/h, makes 980 Pa at 1.225 kg/m³. Eurocode's recommended 1.25 kg/m³ gives 1,000 Pa, and the 0.6V² form in AS/NZS 1170.2 and IS 875 gives 960 Pa, all within about 4%.
| Wind Speed | km/h | ρ = 1.225 kg/m³ | Eurocode, ρ = 1.25 | 0.6V² (AS/NZS, IS 875) |
|---|---|---|---|---|
| 20 m/s | 72 | 245 Pa | 250 Pa | 240 Pa |
| 30 m/s | 108 | 551 Pa | 562 Pa | 540 Pa |
| 40 m/s | 144 | 980 Pa | 1,000 Pa | 960 Pa |
| 50 m/s | 180 | 1,531 Pa | 1,562 Pa | 1,500 Pa |
| 60 m/s | 216 | 2,205 Pa | 2,250 Pa | 2,160 Pa |
The real gap between a US and an AS1170 or Eurocode wind load calculator sits in the speed each code starts from. ASCE 7-16 uses 3-second gusts at strength level, while Eurocode and Canada's NBCC start from 10-minute or hourly mean speeds.
A Eurocode wind load calculator, or a UK, Australian or Canadian one, therefore needs that code's own speed map, terrain factors and shape coefficients. A US answer for the same storm will not match it.
In a metric wind load calculator for ASCE 7 work, the constant 0.00256 becomes 0.613 with V in m/s and the result in Pa. A 1 kPa dynamic pressure needs 40.4 m/s, about 145 km/h, at sea-level density.
One Result Checked by Hand
At 100 mph the 30 ft house in Exposure C has a velocity pressure of 21.37 psf at roof height and a net wall load of 23.62 psf. Three equations get there, and any wind load calculator Excel sheet or app uses the same ones.
qz is velocity pressure in psf, V is the basic wind speed in mph, Kz is the exposure factor, Kzt the topographic factor, Kd the directionality factor of 0.85 for buildings, and Ke the elevation factor.
With Kz = 0.982, Kzt = 1.0, Kd = 0.85 and Ke = 1.0, the velocity pressure is 0.00256 × 0.982 × 0.85 × 100² = 21.37 psf. Every wall and roof pressure on the house grows from that one number.
p is the design pressure, G is the 0.85 gust factor for rigid buildings, Cp is the outside pressure coefficient and GCpi is the internal pressure coefficient, ±0.18 enclosed and ±0.55 partially enclosed.
The windward wall uses Cp = 0.80, so p = 21.37 × (0.68 + 0.18) = +18.38 psf. The leeward wall of a house 40 ft deep and 60 ft wide uses Cp = -0.50, so p = 21.37 × (-0.425 - 0.18) = -12.93 psf.
Internal pressure cancels across the house, so the net wall load is 21.37 × 0.85 × 1.30 = 23.62 psf. Over the 60 by 30 ft face that is 42,513 lb at strength level, or 25,508 lb at 0.6W.
A hand check like this catches a wrong exposure, Kd or speed map in a wind load calculator run before it spreads into every member. The Beam Load Calculator then takes a stud or header with that pressure as a uniform load.