Charge controller size calculator for solar arrays on 12, 24, 36 or 48 V batteries, setting the MPPT or PWM amps, the cold string Voc, string fuses, battery breaker and wire gauge.
Enter the total solar watts and battery voltage. The panel specs below check string voltage, fuses and wiring.
Solar Panel & String Specs
Cold Weather & Battery Cable
Array to Battery Wiring Diagram
Charge Controller Size Chart
| Solar Array | 12 V Battery | 24 V Battery | 48 V Battery |
|---|---|---|---|
| 100 W | 15 A | 10 A | 10 A |
| 200 W | 30 A | 15 A | 10 A |
| 250 W | 30 A | 15 A | 10 A |
| 300 W | 35 A | 20 A | 10 A |
| 400 W | 45 A | 30 A | 15 A |
| 600 W | 70 A | 35 A | 20 A |
| 800 W | 85 A | 45 A | 30 A |
| 1,000 W | 2 × 60 A | 60 A | 30 A |
| 1,200 W | 2 × 70 A | 70 A | 35 A |
| 1,500 W | 2 × 80 A | 80 A | 40 A |
| 2,000 W | 3 × 70 A | 2 × 60 A | 60 A |
| 3,000 W | 4 × 80 A | 2 × 80 A | 80 A |
| 4,000 W | 5 × 85 A | 3 × 70 A | 2 × 60 A |
| 5,000 W | 6 × 100 A | 3 × 100 A | 2 × 70 A |
Max Solar Watts per Controller Rating
| Controller | 12 V Battery | 24 V Battery | 48 V Battery |
|---|---|---|---|
| 10 A | 96 W | 192 W | 384 W |
| 15 A | 144 W | 288 W | 576 W |
| 20 A | 192 W | 384 W | 768 W |
| 30 A | 288 W | 576 W | 1,152 W |
| 35 A | 336 W | 672 W | 1,344 W |
| 40 A | 384 W | 768 W | 1,536 W |
| 45 A | 432 W | 864 W | 1,728 W |
| 50 A | 480 W | 960 W | 1,920 W |
| 60 A | 576 W | 1,152 W | 2,304 W |
| 70 A | 672 W | 1,344 W | 2,688 W |
| 80 A | 768 W | 1,536 W | 3,072 W |
| 85 A | 816 W | 1,632 W | 3,264 W |
| 100 A | 960 W | 1,920 W | 3,840 W |
Step-by-Step Math
Amps, Volts and Margin Behind a Charge Controller Size Calculator Result
By charge controller size calculator math, a 1,200 W array on a 24 V battery needs a 70 A MPPT rated for at least 150 V. The array pushes 50 A into the battery, and a 25% margin lifts that to 62.5 A, which rounds up to 70 A.
Ictrl is the controller amp rating to look for, Parray is the total panel watts and Vbat is the battery bank voltage. The 1.25 factor keeps the controller off its limit on bright, cold days when panels beat their rating.
Dividing by the charging voltage instead, 28.8 V on a 24 V bank, gives 52.1 A and a 60 A controller. Nominal voltage is the safer divisor, so any charge controller size calculator figure based on it carries extra room for the morning bulk charge.
Amps are only half of any charge controller size calculator answer. Three 400 W panels in series with a 37 V open-circuit voltage reach 121.5 V at 14°F (-10°C), so the same 70 A unit must come in a 150 V class, not 100 V.
Controller Amps for 100 W to 5,000 W of Solar
A 400 W array needs a 45 A controller on 12 V, 30 A on 24 V and 15 A on 48 V. Each doubling of battery voltage halves the amps, which is why large arrays move to 48 V banks.
Each cell follows the charge controller size calculator rule of array watts ÷ nominal battery volts × 1.25, rounded up to 10, 15, 20, 30, 35, 40, 45, 50, 60, 70, 80, 85 or 100 A. Arrays above 100 A split evenly across two or more controllers.
| Solar array | 12 V battery | 24 V battery | 48 V battery |
|---|---|---|---|
| 100 W | 15 A | 10 A | 10 A |
| 200 W | 30 A | 15 A | 10 A |
| 250 W | 30 A | 15 A | 10 A |
| 300 W | 35 A | 20 A | 10 A |
| 400 W | 45 A | 30 A | 15 A |
| 600 W | 70 A | 35 A | 20 A |
| 800 W | 85 A | 45 A | 30 A |
| 1,000 W | 2 × 60 A | 60 A | 30 A |
| 1,200 W | 2 × 70 A | 70 A | 35 A |
| 1,500 W | 2 × 80 A | 80 A | 40 A |
| 2,000 W | 3 × 70 A | 2 × 60 A | 60 A |
| 3,000 W | 4 × 80 A | 2 × 80 A | 80 A |
| 4,000 W | 5 × 85 A | 3 × 70 A | 2 × 60 A |
| 5,000 W | 6 × 100 A | 3 × 100 A | 2 × 70 A |
A 1000w solar charge controller size on 12 V is two 60 A units, since 1,000 ÷ 12 × 1.25 is 104.2 A. On 24 V a single 60 A unit covers it, and the cable to the battery shrinks with the current.
What size charge controller for a 1200W solar panel array comes down to battery voltage the same way. It takes two 70 A units on 12 V, one 70 A on 24 V and one 35 A on 48 V.
So a charge controller size calculator estimate should start from the battery voltage you plan to keep, since changing the bank later changes the controller and the cable.
The Solar Panel Size Calculator sets the array watts from your daily kWh, and that figure is the starting point for every row above.
Max Solar Watts on a 10 A to 100 A Controller
A 30 A MPPT carries 288 W on 12 V, 576 W on 24 V and 1,152 W on 48 V with a 25% margin. Without the margin the same unit reaches 360, 720 and 1,440 W, which is the ceiling, not a target.
Pmax is the largest array the controller should take, found by turning the charge controller size calculator formula around. Ictrl is the controller rating in amps and Vbat is the nominal battery voltage.
| Controller | 12 V battery | 24 V battery | 48 V battery | Ceiling at 12 V, no margin |
|---|---|---|---|---|
| 10 A | 96 W | 192 W | 384 W | 120 W |
| 20 A | 192 W | 384 W | 768 W | 240 W |
| 30 A | 288 W | 576 W | 1,152 W | 360 W |
| 35 A | 336 W | 672 W | 1,344 W | 420 W |
| 40 A | 384 W | 768 W | 1,536 W | 480 W |
| 45 A | 432 W | 864 W | 1,728 W | 540 W |
| 50 A | 480 W | 960 W | 1,920 W | 600 W |
| 60 A | 576 W | 1,152 W | 2,304 W | 720 W |
| 70 A | 672 W | 1,344 W | 2,688 W | 840 W |
| 80 A | 768 W | 1,536 W | 3,072 W | 960 W |
| 85 A | 816 W | 1,632 W | 3,264 W | 1,020 W |
| 100 A | 960 W | 1,920 W | 3,840 W | 1,200 W |
The wattage of a battery controller is its amp rating times battery voltage. A 60 A unit on 24 V moves 1,440 W into the battery at full output, and a charge controller size calculator result with margin keeps the array at 1,152 W.
Manufacturer Ratings Run Higher Than the 25% Rule
Victron rates its 150/45 MPPT for 1,300 W of panels on a 24 V battery. That is more than the 1,200 W array that the 25% rule sends to a 70 A unit.
The SmartSolar MPPT 150/45 to 150/100 datasheet lists 1,720 W for the 150/60 and 2,000 W for the 150/70 at 24 V, figures any charge controller size calculator result can be checked against.
Those ratings work out to about 28.9 V per amp at 24 V, which is the charging voltage with no margin. The same datasheet says a larger array is allowed, since the controller limits its input power and clips the excess.
| Victron model | Nominal PV power at 24 V | Watts per amp | 25% rule max at 24 V | 25% rule size for that array |
|---|---|---|---|---|
| 150/45 | 1,300 W | 28.9 | 864 W | 70 A |
| 150/60 | 1,720 W | 28.7 | 1,152 W | 100 A |
| 150/70 | 2,000 W | 28.6 | 1,344 W | 2 × 60 A |
So the 25% rule buys headroom the controller does not strictly need. That headroom still helps in a cold spell, when panels beat their nameplate rating for an hour or two.
Treat a charge controller size calculator result as the conservative choice, and the maker's nominal PV power as the most array that model is built to convert.
One limit outside watts-based charge controller size calculator math is the PV short-circuit input. Victron caps the 150/45 to 150/70 at 50 A, or 30 A per MC4, so three strings of 13.79 A panels at 41.4 A fit but four at 55.2 A do not.
MPPT or PWM: Power Kept From the Same Panels
A PWM controller wastes most of a high-voltage string. Three 31 V Vmp panels in series on a 24 V bank keep only 31% of their 1,200 W, about 372 W, because PWM drags the panels down to the 28.8 V charging voltage.
kPWM is the share of array power a PWM controller keeps, Vcharge is the battery charging voltage and Vmp,string is the panel max-power voltage times the panels in series. An MPPT converts the full string power, minus about 2% loss.
| Battery and string | String Vmp | Charging voltage | Power kept by PWM |
|---|---|---|---|
| 12 V, one 18 V panel | 18 V | 14.4 V | 80.0% |
| 12 V, one 31 V panel | 31 V | 14.4 V | 46.5% |
| 24 V, one 31 V panel | 31 V | 28.8 V | 92.9% |
| 24 V, two 31 V panels | 62 V | 28.8 V | 46.5% |
| 24 V, three 31 V panels | 93 V | 28.8 V | 31.0% |
PWM only makes sense when string Vmp sits just above the charging voltage, as with a single 31 V panel on 24 V. A PWM is also sized on short-circuit current, so one string of 13.79 A panels needs 13.79 × 1.25 = 17.2 A, a 20 A PWM.
MPPT wins for any home or van roof built from 400 W class panels, which is why an MPPT solar charge controller calculator is the usual starting point.
Victron lists a 98% maximum efficiency for its MPPT units, so almost all of the extra string power from a high-voltage string reaches the battery.
Voc in Cold Weather and Panels per String
A 37 V panel with a -0.27%/°C coefficient reaches 40.5 V at 14°F (-10°C) and 43.5 V at -40°F (-40°C). Three in series stay under 150 V even at -40°F, while four exceed it everywhere.
Voc,cold is the open-circuit voltage at the record low, β is the datasheet Voc coefficient in %/°C and Tmin is the lowest expected temperature in °C.
The IAEI Magazine PV math guide uses this same NEC 690.7 method and recommends the record low for a conservative design, the input every charge controller size calculator voltage check depends on.
| Record low | Factor | One panel | 2 in series | 3 in series | 4 in series | Max on 100 V | Max on 150 V |
|---|---|---|---|---|---|---|---|
| 32°F (0°C) | 1.0675 | 39.5 V | 79.0 V | 118.5 V | 158.0 V | 2 | 3 |
| 14°F (-10°C) | 1.0945 | 40.5 V | 81.0 V | 121.5 V | 162.0 V | 2 | 3 |
| -4°F (-20°C) | 1.1215 | 41.5 V | 83.0 V | 124.5 V | 166.0 V | 2 | 3 |
| -22°F (-30°C) | 1.1485 | 42.5 V | 85.0 V | 127.5 V | 170.0 V | 2 | 3 |
| -40°F (-40°C) | 1.1755 | 43.5 V | 87.0 V | 130.5 V | 174.0 V | 2 | 3 |
Victron's datasheet adds a second limit that most charge controller size calculator charts miss. Its 150 V models treat 150 V as the absolute cold maximum but start and run only below 145 V, so keep a cold string 5 V under the class.
Strings also need a floor. The same datasheet says PV voltage must exceed battery voltage plus 5 V to start, so a 24 V bank charging at 28.8 V needs 33.8 V, two 31 V panels in series, and a 48 V bank needs three.
Fuses, Breaker and Cable Between Controller and Battery
A 70 A controller needs a 90 A breaker and 3 AWG (26.7 mm²) copper to the battery. The breaker is 125% of the rating, 87.5 A rounded up, and the cable must carry it, a step many charge controller size calculator charts skip.
| Controller | Breaker at 125% | Cable by ampacity | 12 V, 25 ft run, 3% drop |
|---|---|---|---|
| 20 A | 25 A | 10 AWG (5.26 mm²) | 4 AWG (21.2 mm²) |
| 30 A | 40 A | 8 AWG (8.37 mm²) | 3 AWG (26.7 mm²) |
| 40 A | 50 A | 8 AWG (8.37 mm²) | 2 AWG (33.6 mm²) |
| 50 A | 70 A | 4 AWG (21.2 mm²) | 1 AWG (42.4 mm²) |
| 60 A | 80 A | 4 AWG (21.2 mm²) | 1/0 AWG (53.5 mm²) |
| 70 A | 90 A | 3 AWG (26.7 mm²) | 1/0 AWG (53.5 mm²) |
| 80 A | 100 A | 3 AWG (26.7 mm²) | 2/0 AWG (67.4 mm²) |
| 100 A | 125 A | 1 AWG (42.4 mm²) | 3/0 AWG (85.0 mm²) |
The last column assumes the controller charges at its rating ÷ 1.25 over a 25 ft (7.6 m) one-way run, with copper resistance from NEC Chapter 9 Table 8.
On 12 V that run forces cable two to four sizes larger than ampacity alone, so mount the controller close to the battery.
Vdrop is the loss in volts, L is the one-way run in feet, I is the charging current and R is ohms per 1,000 ft. In the 1,200 W, 24 V charge controller size calculator example, 3 AWG over 10 ft at 50 A loses 0.25 V, or 1.02%.
String fuses are needed once three or more strings run in parallel. Each fuse is panel Isc × 1.56, so 13.79 A panels need 21.5 A, a 25 A fuse, no larger than the panel's series fuse rating.
The Current Calculator converts these charging currents to amps at another battery voltage, which helps when comparing cable runs.
Specific Wattages and Ratings Answered
The answers below keep the 25% margin and nominal battery voltage from the sections above, and they name the panel or battery whenever the charge controller size calculator answer changes with it.
How to size a MPPT?
Divide array watts by battery volts, multiply by 1.25 and round up to a standard amp rating. Then check that the string's cold Voc stays under the controller's voltage class and above battery voltage plus 5 V.
As a charge controller size calculator example, 800 W on 24 V works out to 800 ÷ 24 × 1.25 = 41.7 A, so a 45 A MPPT. Two 37 V panels per string reach 81 V at 14°F, so a 100 V class unit works for strings of two.
What size charge controller for 300W solar panel?
A 300W solar panel needs a 35 A MPPT on 12 V, 20 A on 24 V or 10 A on 48 V. On 12 V, 300 ÷ 12 is 25 A, and the 25% margin lifts it to 31.3 A, just past a 30 A unit.
A PWM sized for the same panel only needs to cover its short-circuit current with margin, but it keeps far less power unless the panel's Vmp is close to 14.4 V, a gap no charge controller size calculator amp figure reveals.
How many watts can a 30 amp MPPT charge controller handle?
A 30 amp MPPT handles 288 W on 12 V, 576 W on 24 V and 1,152 W on 48 V with margin. A 50 A unit takes 480, 960 and 1,920 W, a 60 A unit 576, 1,152 and 2,304 W, and a 100 A unit 960, 1,920 and 3,840 W.
In panels, a 30 A controller fits two 100 W panels on 12 V, five on 24 V and eleven on 48 V by the charge controller size calculator rule. A single 400 W panel already needs more than 30 A on 12 V.
How many watts can a 40 amp PWM charge controller handle?
A 40 amp PWM is limited by panel current, not watts. At 40 ÷ 1.25 = 32 A it takes two strings of 13.79 A Isc panels, and with 31 V panels on 12 V it keeps only 46.5% of their power.
Two 400 W panels on that PWM deliver about 372 W of their 800 W. A 40 A MPPT on the same 12 V battery would take 384 W of array with margin and convert almost all of it.
Which is better, 200W or 300W?
A 300W panel makes 50% more energy but needs a larger controller on 12 V, 35 A instead of 30 A. On 24 V it needs 20 A against 15 A for 200 W, so the controller cost gap shrinks.
Price the controller at your battery voltage before buying panels, since a charge controller size calculator result moves in steps of 5 to 15 A and one extra panel can cross a step.
What is a solar charge controller calculator?
Behind the name sit two checks, controller amps from array watts and battery voltage, and string voltage at the record low.
A solar charge controller size calculator estimate that skips the voltage check can get the amps right and still destroy the controller's input stage on the first frosty morning.
How do I size an MPPT or PWM charge controller?
Size an MPPT on array watts ÷ battery volts × 1.25, and a PWM on parallel strings × panel Isc × 1.25. One 400 W string on 24 V gives a 30 A MPPT or a 20 A PWM, but the PWM keeps 93% only because one 31 V panel sits near 28.8 V.
How is a charge controller rated?
A charge controller is rated by output amps to the battery and maximum PV input voltage. A 150/70 unit takes up to 150 V of cold string Voc and delivers 70 A, which is 840 W into 12 V or 1,680 W into 24 V.
Those two numbers are what a charge controller size calculator result must match on the label, along with the PV short-circuit limit printed beside them.
The Battery Charge Time Calculator turns that charging current into hours to full, and the Solar Battery Bank Calculator sizes the bank it charges.