Inverter Size Calculator

Updated

Inverter size calculator for home, RV and off-grid loads, sizing inverter watts and VA from running load and motor surge, plus DC current and batteries for backup hours at 12-48 V.

Quick Setup

Add the watts of everything that runs at once. Startup surge is the peak when motors start.

W
%
hours
W
units
W
units
W
units
W
units
W
Power Factor & Inverter Specs0.8 PF, 120 V, 90%, 19 V low, 2× surge
PF
%
V
× rated
Inverter Battery12 V 200 Ah, 50% DoD
%
V
Ah
Inverter Size You Need
3,000 W Inverter
Sized for 2,200 W running and 3,600 W at startup, plus a 25% margin
6,000 W Surge Capacity
Surge Headroom33.3%
Inverter Load While Running73.3%
Surge capacity is the inverter rating times its surge rating. Headroom is what remains after the startup need with margin.
3,438 VA Rating Needed
Running Current at 120 V22.9 A
Startup Current at 120 V37.5 A
Volt-amps are continuous watts divided by power factor. Inverters sold in VA must meet this figure, not just the watts.
175.4 A Max DC at 19 V
Running DC Current at 24 V101.9 A
Fuse and Cable Current (125%)219.3 A
Max DC amps are rated watts over the lowest battery voltage and efficiency. Fuse and cable carry 125% of that current.
10 × 12 V 200 Ah Batteries
Backup on This Bank4.9 h
One Battery Alone Lasts29 min
Batteries cover the running load for your backup time at your depth of discharge. One battery shows a single unit on its own.
Power Flow Diagram24 V DC to 120 V AC
10 × 12 V 200 Ah2S × 5P at 24 V4.9 h backup3,000 W6,000 W surge90% efficient2,200 W running3,600 W startup120 V AC101.9 A DC22.9 A ACBattery bank → inverter → loads
Inverter Size Chart25% margin, 4 h backup
InverterAt 0.8 PFSafe LoadMax DC at 19 V200 Ah Units, 4 h
500 W625 VA400 W29.2 A2 batteries
1,000 W1,250 VA800 W58.5 A4 batteries
1,500 W1,875 VA1,200 W87.7 A6 batteries
2,000 W2,500 VA1,600 W117.0 A6 batteries
3,000 W3,750 VA2,400 W175.4 A10 batteries
5,000 W6,250 VA4,000 W292.4 A16 batteries
8,000 W10,000 VA6,400 W467.8 A24 batteries
12 V vs 24 V vs 48 VSame 3,000 W inverter
SystemMax at Low VoltageRunningFuse at 125%Batteries
12 V350.9 A at 9.5 V203.7 A438.6 A1S × 9P
24 V175.4 A at 19 V101.9 A219.3 A2S × 5P
48 V87.7 A at 38 V50.9 A109.6 A4S × 3P
Step-by-Step Math10 steps
Continuous need2,200 W × 1.25 = 2,750 W
Startup need3,600 W × 1.25 = 4,500 W, ÷ 2 surge rating = 2,250 W
Inverter sizelarger of 2,750 W and 2,250 W = 2,750 W → 3,000 W standard size
Apparent power2,750 W ÷ 0.8 PF = 3,438 VA
AC current2,200 W ÷ (120 V × 0.8) = 22.9 A
Max DC current3,000 W ÷ (19 V × 0.9) = 175.4 A, × 1.25 = 219.3 A
Running DC current2,200 W ÷ (24 V × 0.9) = 101.9 A
Battery energy2,200 W × 4 h ÷ 0.9 ÷ 0.5 = 19,556 Wh
Battery count2 in series for 24 V; 19,556 Wh ÷ (24 V × 200 Ah) = 4.07 → 5 in parallel = 10 batteries
Inverter size3,000 W inverter, 3,750 VA at 0.8 PF
High DC Current at 24 V
At full rating and low battery the inverter pulls 175.4 A, which needs heavy cable. A 48 V system carries the same power at about 87.7 A.

Inverter Size Calculator Answer: 3,000 W for a 2,200 W Load

A home load of 2,200 W running with a 3,600 W startup peak needs a 3,000 W inverter. With a 25% margin the load calls for 2,750 W continuous, and the motor start calls for 4,500 W, which a 2× surge rating covers from 2,250 W.

Two numbers set every inverter size calculator answer: the continuous watts with margin, and the startup watts divided by the surge rating. The larger of the two, rounded up to a standard size, is the inverter.

Wrun is everything that runs at the same time and Wstart is that load at the moment the biggest motor starts. M is the margin factor, 1.25 for 25%, and ksurge is how many times its rating the inverter can deliver for a few seconds.

In this inverter size calculator example, the 3,000 W unit runs the 2,200 W load at 73.3% of its rating. Its 6,000 W surge covers the 4,500 W start with 33.3% to spare, so neither limit is tight.

Dropping the margin to zero brings the inverter size calculator result down to 2,500 W. That unit runs at 88% of its rating all evening, which leaves no room for one more appliance or a hot room derating the output.

Surge Rating Decides the Size More Than Watts

A 1,000 W running load with a 3,600 W startup peak needs a 3,000 W inverter at a 1.5× surge rating but only 1,500 W at 3×. The running watts alone would need just 1,250 W, so an inverter size calculator count that skips surge undersizes it.

Inverter surge ratingContinuous needStartup need ÷ surgeInverter size
1.5×1,250 W3,000 W3,000 W
2×1,250 W2,250 W2,500 W
2.5×1,250 W1,800 W2,000 W
3×1,250 W1,500 W1,500 W

The 2× figure is realistic for high-frequency units. Victron's MultiPlus-II datasheet lists 5,500 W of peak power on a model rated 2,400 W continuous, and 9,000 W peak on one rated 4,000 W, both close to 2.3×.

Read the surge rating and its duration on the spec sheet before trusting a result for a well pump, fridge or air conditioner. A soft starter on the largest motor lowers the startup peak and can drop the inverter a size or two.

Watts, VA and Power Factor on the Nameplate

In any inverter size calculator estimate, an inverter sold by VA delivers fewer watts than its label suggests. At a 0.8 power factor, a 3,000 VA unit gives 2,400 W, and the 2,750 W continuous need above calls for 3,438 VA.

VA is the apparent power the inverter must be rated for and PF is the load's power factor, 1.0 for heaters and kettles and lower for motors. The Victron 3,000 VA model above is rated 2,400 W, which is that same 0.8 ratio.

Continuous needVA at PF 1.0VA at PF 0.8VA at PF 0.7
1,013 W1,013 VA1,266 VA1,446 VA
1,875 W1,875 VA2,344 VA2,679 VA
2,750 W2,750 VA3,438 VA3,929 VA
5,000 W5,000 VA6,250 VA7,143 VA

Many quick inverter size calculator guides divide by 0.7. For the 2,750 W case that gives 3,929 VA instead of 3,438 VA, which can push a buyer up a full size.

Use 0.7 only when motors make up most of the load. A resistive load such as a 1,500 W heater runs at a power factor of 1.0, so its VA equals its watts.

AC current follows the same power factor. The 2,200 W load draws 22.9 A at 120 V and the 3,600 W start draws 37.5 A, so the output breaker and wiring see the startup current for those few seconds.

Standard Sizes in an Inverter Size Chart

A 1,000 W running load with no motor start needs a 1,500 W inverter, and a 2,000 W load needs 2,500 W. Each step up the chart is the running load times 1.25, rounded to the next standard size.

Running loadContinuous needStandard inverterVA at PF 0.8Max DC amps at 19 V
300 W375 W400 W469 VA23.4 A
500 W625 W800 W781 VA46.8 A
800 W1,000 W1,000 W1,250 VA58.5 A
1,000 W1,250 W1,500 W1,563 VA87.7 A
1,500 W1,875 W2,000 W2,344 VA117.0 A
2,000 W2,500 W2,500 W3,125 VA146.2 A
3,000 W3,750 W4,000 W4,688 VA233.9 A
4,000 W5,000 W5,000 W6,250 VA292.4 A
5,000 W6,250 W8,000 W7,813 VA467.8 A

The last row shows how the standard sizes jump. A 5,000 W load needs 6,250 W, and with no 7,000 W step in the list the inverter size calculator answer lands on 8,000 W, so two 3,500 W units or a 6,000 W unit with less margin are worth pricing.

What size inverter you need to run a 1,500 watt heater is a common inverter size calculator case. With no motor start, 1,500 W × 1.25 is 1,875 W, so a 2,000 W inverter carries it at 75% of its rating.

A solar inverter size calculator for a grid-tied array works from array kW and a DC-to-AC ratio instead. The Solar Panel Size Calculator sizes that inverter from the panels.

The Electrical Power Calculator converts amps and volts from an appliance label into watts before they go into a load total.

DC Current and Fuse Size at Low Battery Voltage

A 3,000 W inverter on a 24 V bank draws 138.9 A at nominal voltage and 90% efficiency, but 175.4 A when the battery sags to 19 V. Size the cable and fuse for the low-voltage figure, not the nominal one that most inverter size calculator pages print.

The San Luis Obispo County PV inspection checklist spells out the rule behind NEC 690.8: input current is the rated AC output divided by the lowest battery voltage and by the inverter efficiency at that power, with cables at 125% of that current.

IDC is the battery current at full output, Vmin is the lowest battery voltage the inverter runs on and η is its efficiency. Victron's MultiPlus-II datasheet lists minimum DC inputs of 9.5 V, 19 V and 38 V for its 12, 24 and 48 V models.

SystemFull rating at nominal VAt lowest input VFuse and cable at 125%Batteries for 4 h
12 V277.8 A350.9 A at 9.5 V438.6 A1S × 9P
24 V138.9 A175.4 A at 19 V219.3 A2S × 5P
48 V69.4 A87.7 A at 38 V109.6 A4S × 3P

Every row is the same 3,000 W inverter. Even the 24 V row passes 150 A at low battery, which is past the point where heavy cable becomes a main cost.

At 12 V the fuse current passes 400 A, so an inverter size calculator result above about 2,000 W is a strong case for 24 V or 48 V.

An inverter size calculator 12v case for a car or van is small but still sharp on current. A 300 W unit draws 27.8 A at 12 V and 35.1 A at 9.5 V, and a 2,000 W unit for the 1,500 W heater draws 233.9 A at 9.5 V.

The Current Calculator converts any of these loads to amps at another voltage, which helps when checking cable ratings.

Hours of Backup and the Battery Bank

In an inverter size calculator with battery sizing, four hours of the 2,200 W load needs 19,556 Wh of lead-acid at 50% depth of discharge and 90% inverter efficiency. At 24 V that is ten 12 V 200Ah batteries in 2S × 5P, giving 4.9 hours.

Ebat is the battery energy in Wh, t is backup hours, η is inverter efficiency and DoD is the share of the battery you drain. Divide by bank voltage times one battery's Ah for the parallel count, rounding up.

One 200Ah battery on its own would carry the 2,200 W load for only 29 minutes, so backup hours belong in every inverter size calculator estimate that includes batteries.

Five parallel strings share current unevenly. At 48 V the same energy becomes 4S × 3P, twelve batteries in three strings, and the DC current halves.

The Solar Battery Bank Calculator sizes the same bank for whole days of backup, and the UPS Runtime Calculator checks minutes on a smaller unit.

Appliance List for a Home Inverter at 230 V

Three 60 W ceiling fans, four 45 W tubelights, a 250 W freezer and a 200 W desktop add up to 810 W running. With a 1,200 W startup peak for the freezer, the inverter comes out at 1,200 W, or 1,266 VA at a 0.8 power factor.

That VA figure decides the purchase for an inverter size calculator India estimate, since home inverters there are sold by VA. A 1,100 VA unit falls short of 1,266 VA, so the next VA rating up is the right buy.

At 230 V the 810 W load draws only 4.4 A on the AC side. On a 24 V bank of four 12 V 200Ah lead-acid batteries it runs 5.3 hours. A 12 V bank reaches 4 hours with three batteries, but at 75 A of DC current instead of 37.5 A.

The Energy Consumption Calculator adds hours of use to a list like this one, which gives the daily kWh behind an electricity load calculator in kW for home use.

Air Conditioners on 5 kVA and 7.5 kVA Inverters

A 5 kVA inverter runs one 1.5-ton AC with a 25% margin and two with none. A 7.5 kVA inverter runs two with margin and three without, taking a 1.5-ton unit with an EER of 11 as drawing 1,636 W.

InverterWatts at PF 0.8Safe load at 25% margin1.5-ton ACs with margin1.5-ton ACs at full rating
3 kVA2,400 W1,920 W11
5 kVA4,000 W3,200 W12
7.5 kVA6,000 W4,800 W23
10 kVA8,000 W6,400 W34

One ton of cooling is 12,000 BTU/h, so a 1.5-ton unit at EER 11 draws 18,000 ÷ 11 = 1,636 W. The EER on your own unit's label replaces the 11 in any inverter size calculator count, and a higher rating fits more units on the same inverter.

Non-inverter ACs add a compressor start on top of that draw. Treat the start as the startup peak, staggered so only one compressor starts at a time, before trusting any inverter size calculator count of ACs.

Common Inverter and Battery Sizing Answers

A 25% margin, a 0.8 power factor, a 2× surge rating, 90% efficiency and lead-acid at 50% depth sit behind every inverter size calculator answer below, unless one names another battery.

How do you calculate inverter size?

Add the watts of everything that runs at once, multiply by 1.25 and round up to a standard size. Then check the startup peak times 1.25 against the surge rating, and take whichever result is larger.

For a 1,500 W kettle and a 150 W fridge running together, 1,650 W × 1.25 is 2,063 W, so a 2,500 W inverter. If the fridge start lifts the peak to 2,100 W, 2,625 W ÷ 2 is 1,313 W, so the running load still decides.

What is a good inverter size?

A good inverter size runs your load at about 80% of its rating or less and covers the biggest motor start. For fans, lights, a freezer and a computer that is about 1,200 W; for a 2,200 W evening load with a pump, 3,000 W.

What size inverter for 200Ah battery?

A single 12 V 200Ah lead-acid battery suits an 800 W inverter for two hours of backup or 400 W for four. At 50% depth and 90% efficiency it delivers 1,080 Wh, so two hours means a 540 W load.

A 12 V 100Ah battery delivers 540 Wh the same way, which matches a 400 W inverter for two hours or 300 W for four. A bigger inverter on the same battery only shortens the backup.

How many 200Ah batteries for 3kW inverter?

A 3 kW inverter on 24 V needs ten 12 V 200Ah lead-acid batteries for four hours at its 2,400 W safe load, or six LiFePO4 batteries at 90% depth. Two hours takes six lead-acid batteries.

Inverter and bankSafe load2 h lead-acid2 h LiFePO44 h lead-acid4 h LiFePO48 h lead-acid8 h LiFePO4
1.5 kVA, 24 V960 W224284
3 kW, 24 V2,400 W641061810
5 kVA, 48 V3,200 W841282416
5,000 W, 48 V4,000 W8816123220

Counts are 12 V 200Ah units, two per string at 24 V and four per string at 48 V. A 5,000 watt inverter needs 16 lead-acid batteries for four hours, so LiFePO4 at 12 often wins on space and weight.

Which battery is best, 150Ah or 200Ah?

A 200Ah battery gives 33% more backup than a 150Ah on the same load. At 300 W a 12 V lead-acid 150Ah lasts 2.7 hours and a 200Ah lasts 3.6 hours, so choose by the hours you need.

How much load can a 1.5 kVA inverter carry?

A 1.5 kVA inverter carries about 1,200 W at a 0.8 power factor and 960 W with a 25% margin. That covers four ceiling fans, six tubelights, a 250 W freezer and a 200 W desktop, exactly 960 W running.

How many hours will a 200Ah battery last?

A 12 V 200Ah lead-acid battery lasts 5.4 hours at 200 W, 2.2 hours at 500 W and 1.1 hours at 1,000 W, using 50% depth and 90% inverter efficiency. LiFePO4 at 90% depth nearly doubles each figure.

LoadLead-acid at 50%LiFePO4 at 90%
100 W10.8 h19.4 h
300 W3.6 h6.5 h
500 W2.2 h3.9 h
800 W1.4 h2.4 h
1,000 W1.1 h1.9 h

The Battery Life Calculator runs the same check for other capacities, voltages and depths of discharge before you buy.

What is a power inverter calculator?

The term means inverter sizing math that weighs continuous watts, startup surge, VA at the load's power factor and DC current at low battery voltage. A sound inverter size calculator estimate passes all four limits, not just the running watts.

Do I need a bigger inverter?

You need a bigger inverter when the running load passes 80% of its rating or the motor start passes its surge rating. A 2,200 W load on a 2,500 W unit runs at 88%, so the next 3,000 W size is the safer choice in any inverter size calculator check.