Solar Battery Bank Calculator

Updated

Solar battery bank calculator for off-grid and backup systems, sizing bank kWh, amp-hours, battery count and series-parallel wiring from daily kWh, an appliance list or Ah per day.

Quick Setup

Use your daily or monthly kWh. Battery type sets depth of discharge and efficiency.

days
V
Ah/day
W
hrs/day
W
hrs/day
W
hrs/day
W
hrs/day
Battery Unit & Efficiency12 V 100 Ah, 90% DoD, 90% eff.
V
Ah
%
%
Peak Load & Solar Recharge3,000 W peak, 4.6 sun hours, 80%
W
hrs/day
%
Battery Price$280 per battery

The US 30% homeowner credit for batteries ended for systems installed after 2025.

$ each
Solar Battery Bank Size
24.7 kWh Battery Bank
At least 514 Ah at 48 V to carry 10.0 kWh a day for 2 days
24 Batteries in 4S × 6P
Installed Capacity600 Ah, 28.8 kWh
Delivered After Losses23.3 kWh
Batteries in series set the bank voltage, and parallel strings add amp-hours. Delivered energy counts depth of discharge and losses.
2.33 Days of Backup
Runtime at Peak Load7.8 h
Daily Cycle Depth38.6%
Backup counts usable energy after efficiency losses. Cycle depth shows how much charge one normal day pulls from the full bank.
69.4 A Peak Draw at 48 V
Discharge Rate0.12C
Solar to Recharge Daily Use3.02 kW
Peak amps are peak watts divided by bank volts and efficiency. The array replaces one day of use in average sun.
$6,720 Battery Cost
Cost per Usable kWh$259
Cost per Backup Day$2,881
Batteries only, before racks, cables, fuses and the inverter. Usable kWh counts only the share inside your chosen depth of discharge.
Battery Bank Wiring Diagram4S × 6P at 48 V
+-4 in series × 6 in parallel of 12 V 100 Ah
Solar Battery Size Chart2 days, 90% DoD
Daily UseBank SizeAt 48 V12 V 100 Ah Units
1.00 kWh/day2.47 kWh51 Ah4 batteries
2.00 kWh/day4.94 kWh103 Ah8 batteries
3.00 kWh/day7.41 kWh154 Ah8 batteries
5.00 kWh/day12.3 kWh257 Ah12 batteries
10.0 kWh/day24.7 kWh514 Ah24 batteries
15.0 kWh/day37.0 kWh772 Ah32 batteries
20.0 kWh/day49.4 kWh1,029 Ah44 batteries
30.0 kWh/day74.1 kWh1,543 Ah64 batteries
12 V vs 24 V vs 48 V BankSame 24.7 kWh bank
Bank VoltageAmp-HoursWiringPeak Current
12 V2,058 Ah1S × 21P278 A
24 V1,029 Ah2S × 11P139 A
48 V514 Ah4S × 6P69 A
Step-by-Step Math11 steps
Daily energy10 kWh × 1,000 = 10,000 Wh/day
Backup energy10,000 Wh × 2 days = 20,000 Wh
Bank size20,000 Wh ÷ (0.9 × 0.9) = 24,691 Wh
Amp-hours24,691 Wh ÷ 48 V = 514.4 Ah
Battery wiring4 in series; 514.4 Ah ÷ 100 Ah = 5.14 → 6 in parallel = 24 batteries
Backup check25,920 Wh usable × 0.9 ÷ 10,000 Wh = 2.33 days
Peak runtime25,920 Wh × 0.9 ÷ 3,000 W = 7.8 h
Peak current3,000 W ÷ (48 V × 0.9) = 69.4 A, ÷ 600 Ah = 0.12C
Solar recharge10,000 Wh ÷ (4.6 h × 0.8 × 0.9) = 3.02 kW
Battery cost24 batteries × $280 = $6,720
Solar battery bank size24,691 Wh = 24.7 kWh
6 Parallel Strings
Many parallel strings share current unevenly unless cables are equal. Higher-Ah batteries or a higher bank voltage cut the string count.

Backup for 10 kWh a Day: Solar Battery Bank Calculator Math

A home using 10 kWh a day needs a 24.7 kWh LiFePO4 bank for two days of backup at 90% depth of discharge and 90% efficiency. At 48 V that is 514 Ah, or twenty-four 12 V 100Ah batteries wired 4S × 6P.

Four numbers drive every solar battery bank calculator result: daily energy, backup days, depth of discharge and efficiency. Bank voltage only changes how that energy is split into amp-hours.

Ebank is the bank size in Wh and Eday is daily use in Wh. D is backup days without sun. DoD is the share of the bank you drain, and η is battery plus inverter efficiency, both as decimals.

CAh is the bank capacity in amp-hours at the bank voltage Vbank. A 24,691 Wh solar battery bank calculator result is 514 Ah at 48 V, 1,029 Ah at 24 V and 2,058 Ah at 12 V.

For the 10 kWh home, 10,000 Wh × 2 days = 20,000 Wh. Then 20,000 ÷ (0.90 × 0.90) = 24,691 Wh, and 24,691 ÷ 48 V = 514.4 Ah. That rounds up to six parallel strings of 100 Ah, so 600 Ah and 28.8 kWh go in.

Rounding up adds margin. The installed 28.8 kWh holds 25.9 kWh above the 90% floor and delivers 23.3 kWh after losses, which is 2.33 days instead of the 2.00 the solar battery bank calculator formula targets.

One normal day pulls 38.6% of the full bank. That daily cycle depth matters for lead-acid life far more than for lithium, since lead-acid wears fastest when it is drained deep every day.

kWh, Amp-Hours and Battery Count by Daily Use

A 5 kWh day needs a 6.17 kWh LiFePO4 bank for one day and 12.3 kWh for two. At 48 V the two-day bank is 257 Ah, or twelve 12 V 100Ah batteries.

This solar battery size chart uses 90% depth of discharge and 90% efficiency, the LiFePO4 case. Battery counts are 12 V 100Ah units wired for a 48 V bank, rounded up to whole strings of four.

Daily useBank for 1 dayBatteries for 1 dayBank for 2 daysAh at 48 V, 2 daysBatteries for 2 days
1 kWh1.23 kWh42.47 kWh51 Ah4
2 kWh2.47 kWh44.94 kWh103 Ah8
3 kWh3.70 kWh47.41 kWh154 Ah8
5 kWh6.17 kWh812.3 kWh257 Ah12
10 kWh12.3 kWh1224.7 kWh514 Ah24
15 kWh18.5 kWh1637.0 kWh772 Ah32
20 kWh24.7 kWh2449.4 kWh1,029 Ah44
30 kWh37.0 kWh3274.1 kWh1,543 Ah64

The small rows show where a 48 V solar battery bank calculator plan stops making sense. Four 12 V batteries are the minimum string, so a 1 kWh day gets 4.8 kWh of batteries whether it needs 1.23 kWh or 2.47 kWh.

A 2 kWh day for two days needs 103 Ah at 48 V, just over one string, so it takes eight batteries. At 12 V the same bank is 412 Ah, or five batteries, so small cabins and vans suit a 12 V or 24 V solar battery bank calculator plan.

LiFePO4, Lithium-Ion or Lead-Acid: Bank Size Compared

Lead-acid needs about twice the bank of LiFePO4 for the same backup. Two days at 10 kWh takes 50.0 kWh of lead-acid at 50% depth and 80% efficiency, against 24.7 kWh of LiFePO4.

Battery typeDepth of dischargeEfficiency5 kWh/day, 2 days10 kWh/day, 2 days20 kWh/day, 2 days
LiFePO490%90%12.3 kWh / 1224.7 kWh / 2449.4 kWh / 44
Lithium-ion80%90%13.9 kWh / 1227.8 kWh / 2455.6 kWh / 48
Lead-acid50%80%25.0 kWh / 2450.0 kWh / 44100.0 kWh / 84

Each cell is bank kWh and the count of 12 V 100Ah batteries at 48 V. The 50% lead-acid figure is not a guess. Trojan's Industrial Line User's Guide says renewable systems are typically designed for 20% to 50% depth of discharge, and never past 80%.

In a solar battery bank calculator run for lead-acid, a 10 kWh home grows to 44 batteries in 11 parallel strings. That many strings share current poorly, so 2 V or 6 V cells suit a lead-acid bank better than 12 V blocks.

LiFePO4 at 90% and lithium-ion at 80% land on the same 24 batteries at 10 kWh a day, but the gap opens at 20 kWh, 44 against 48. Any solar battery bank calculator comparison should use the depth the maker rates for daily cycling.

Efficiency Losses That Change the Battery Count

Raising efficiency from 90% to 95% turns the 10 kWh, two-day solar battery bank calculator answer from 24 batteries into 20. That saves $1,120 at $280 a battery, but only if the inverter and battery really lose just 5%.

Ninety percent is the more defensible figure for a lithium bank feeding household loads. Victron's MultiPlus-II datasheet lists a maximum inverter efficiency of 93% at 12 V, 94% at 24 V and 96% at 48 V, before any battery losses.

Case at 10 kWh/day, 2 daysBank neededAh at 48 VBatteriesBackup deliveredBattery cost at $280
95% efficiency23.4 kWh487 Ah202.05 days$5,600
90% efficiency24.7 kWh514 Ah242.33 days$6,720
89% efficiency25.0 kWh520 Ah242.31 days$6,720
90% plus 18 W inverter idle draw25.8 kWh537 Ah242.24 days$6,720

The 89% row matches the round-trip rating in Tesla's Powerwall 3 datasheet for solar to battery to home. Both 90% and 89% land on the same 24 batteries, so the exact loss figure matters less than not overstating it.

Idle draw is the loss most solar battery bank calculator inputs leave out. The same Victron inverter uses 18 W with no load, which is 432 Wh a day. Add it to daily use; on a 10 kWh day it eats the spare margin, cutting backup from 2.33 to 2.24 days.

12 V, 24 V or 48 V for the Same Bank

The same 24.7 kWh bank is 2,058 Ah at 12 V, 1,029 Ah at 24 V and 514 Ah at 48 V. The energy is identical; the current changes, from 278 A at 12 V to 69 A at 48 V for a 3,000 W load.

Bank voltageAmp-hoursWiring of 12 V 100Ah unitsCurrent at 3,000 WInverter max efficiency
12 V2,058 Ah1S × 21P278 A93%
24 V1,029 Ah2S × 11P139 A94%
48 V514 Ah4S × 6P69 A96%

At 12 V, twenty-one batteries sit in parallel and a 3,000 W load pulls 278 A, which needs very heavy cable and fusing. Past about 1,080 W, a 12 V bank pulls more than 100 A, so most home solar battery bank calculator plans move to 48 V.

A solar battery calculator 12V result still fits a van or boat with a 1 to 2 kWh day. A 12 V 100Ah battery stores 1.2 kWh, and three of them cover a 2 kWh day for one day at 90% depth and 90% efficiency.

The Current Calculator converts any load to amps at your bank voltage, which sets the cable and fuse size before you buy.

Wiring Batteries in Series and Parallel

Series count is bank voltage divided by battery voltage, and parallel strings are amp-hours needed divided by one battery's Ah, rounded up. Four 12 V batteries in series make 48 V; six such strings make 600 Ah.

N is the battery count, Vunit is one battery's nominal voltage and Cunit is its amp-hour rating. The ceiling brackets mean the parallel count always rounds up to a whole string.

LiFePO4 batteries are often labeled 12.8 V, and four in series make 51.2 V, not 48 V. Dividing the 24.7 kWh bank by 51.2 V gives 482 Ah, so five strings of 12.8 V units do the job: 20 batteries instead of 24, holding 25.6 kWh.

That gap is easy to miss in any solar battery bank calculator estimate that divides by the nominal 48 V. Five strings of 12.8 V 100Ah units still deliver 20.7 kWh after losses, or 2.07 days at 10 kWh a day.

2 kWh/day backupBank needed12 V wiring24 V wiring48 V wiring
1 day2.47 kWh1S × 3P, 3 batteries2S × 2P, 4 batteries4S × 1P, 4 batteries
2 days4.94 kWh1S × 5P, 5 batteries2S × 3P, 6 batteries4S × 2P, 8 batteries
3 days7.41 kWh1S × 7P, 7 batteries2S × 4P, 8 batteries4S × 2P, 8 batteries

A 2 kWh day shows why battery bank size depends on voltage. Two days at 48 V needs eight batteries because 103 Ah spills into a second string, while 12 V does it with five.

Five or more parallel strings in a solar battery bank calculator layout share current unevenly unless every cable is the same length and gauge. Higher-Ah batteries or a higher bank voltage bring the string count down.

House Backup From an Appliance List

Critical loads usually need a far smaller solar battery bank calculator result than whole-home use. A 250 W freezer for 8 hours, a 15 W router all day, a 60 W fan for 8 hours and a 40 W CPAP for 8 hours add up to 3,160 Wh a day.

That list needs a 3.9 kWh LiFePO4 bank for one day and 7.8 kWh for two, eight 12 V 100Ah batteries at 48 V. Whole-home use of 30 kWh a day needs 37.0 kWh for just one day, close to ten times as much.

Backup planDaily use1 day2 days3 days
Critical loads only3.16 kWh3.90 kWh / 47.80 kWh / 811.7 kWh / 12
AC, freezer, PC and fan8.68 kWh10.7 kWh / 1221.4 kWh / 2032.1 kWh / 28
Whole home30 kWh37.0 kWh / 3274.1 kWh / 64111.1 kWh / 96

The middle row is a 900 W window AC for 6 hours, a 250 W freezer for 8, a 200 W desktop for 4 and a 60 W fan for 8. The AC alone is 5.4 kWh, or 62% of that day, so cooling decides how much battery backup a house needs.

Tesla lists Powerwall 3 at 13.5 kWh of usable AC energy, so the depth and efficiency division is already done. A 30 kWh day needs three units for one day, not the 37.0 kWh from the DC solar battery bank calculator formula.

The Energy Consumption Calculator totals a longer appliance list before any solar battery bank calculator sizing, and the Battery Life Calculator checks how long one load runs.

Cold, Peak Load and Solar Recharge

A solar battery bank calculator result sized for a mild climate can fall short in winter. Trojan's guide says lead-acid at 0°F (-18°C) delivers 50% of rated capacity, so the 50.0 kWh lead-acid bank would need about 100 kWh there.

Lithium banks hold capacity better in cold, but LiFePO4 datasheets typically allow charging only above 32°F (0°C). In an unheated garage or shed, plan heated or insulated storage before adding batteries.

Peak load sets the current, not the energy. A 3,000 W load on the 48 V bank draws 69.4 A, which is 0.12C on 600 Ah and well inside lithium limits. Above 1C, check each battery's continuous discharge rating or add strings.

Steady loadRuntime on 23.3 kWh deliveredPeak sun hoursSolar to refill 10 kWh a day
500 W46.7 h2.8 h (London)4.96 kW
1,000 W23.3 h4.0 h (New Delhi)3.47 kW
3,000 W7.8 h4.6 h (US average)3.02 kW
5,000 W4.7 h5.1 h (Riyadh)2.72 kW

Recharge is the step most battery sizing skips. The array must refill one day of use in average sun, or each cloudy spell leaves the bank lower than the last.

At 4.6 sun hours, 80% array efficiency and 90% battery efficiency, a 10 kWh day needs 3.02 kW of panels to pair with any solar battery bank calculator result.

The Solar Panel Size Calculator turns that kW into a panel count and roof area, and the Battery Charge Time Calculator shows the hours a given charge current needs.

Price per Usable kWh

Twenty-four 12 V 100Ah batteries at $280 each cost $6,720, or $259 per usable kWh and $2,881 per day of backup. Racks, cables, fuses, a battery monitor and the inverter come on top of that.

Cost per usable kWh is the fair way to compare chemistries in a solar battery bank calculator estimate. For the 10 kWh, two-day goal, lead-acid needs 44 batteries against 24, so each must cost no more than about 55% as much to break even.

Any currency works the same way. A rupee or euro price per battery gives a rupee or euro total, so a solar battery bank calculator India estimate needs only a local price per battery and New Delhi's 4.0 sun hours for the recharge check.

US buyers lost the 30% federal credit for home batteries installed after 2025. A solar battery repayment or savings estimate should now start from the full battery price, less any utility or state rebate.

Answers on Battery kWh and Sizing

Each answer below uses the same solar battery bank calculator defaults of 90% depth and 90% efficiency for LiFePO4, unless it names another battery.

How do you size a solar battery bank?

Multiply daily Wh by backup days, divide by depth of discharge times efficiency, then divide by bank voltage for amp-hours. A cabin using 2 kWh a day for three days needs 7,407 Wh, which is 309 Ah at 24 V.

Next, divide bank voltage by battery voltage for the series count, and amp-hours by one battery's Ah for the parallel count, rounding up. At 24 V that cabin takes 2S × 4P, eight 12 V 100Ah batteries holding 9.6 kWh.

What is a solar battery bank calculator?

The term covers the bank-sizing formula above plus the rounding to whole batteries and strings. Any solar battery bank calculator estimate rests on four inputs: daily Wh, backup days, depth of discharge and efficiency.

The same math fits a spreadsheet. With daily Wh in A2, days in B2, DoD in C2 and efficiency in D2, the formula =A2*B2/(C2*D2) gives bank Wh, and =ROUNDUP(E2/F2/G2,0) gives parallel strings from bank Wh, volts and battery Ah.

How many kWh are in a solar battery?

A battery's kWh is volts times amp-hours divided by 1,000. A 12 V 100Ah battery holds 1.2 kWh, a 12.8 V 100Ah LiFePO4 holds 1.28 kWh and a 48 V 100Ah server-rack battery holds 4.8 kWh.

BatteryRated energyUsable at 90% depthUsable at 50% depth
12 V 100Ah1.20 kWh1.08 kWh0.60 kWh
12.8 V 100Ah LiFePO41.28 kWh1.15 kWh0.64 kWh
12 V 200Ah2.40 kWh2.16 kWh1.20 kWh
24 V 100Ah2.40 kWh2.16 kWh1.20 kWh
48 V 100Ah4.80 kWh4.32 kWh2.40 kWh
51.2 V 100Ah LiFePO45.12 kWh4.61 kWh2.56 kWh

Packaged home batteries quote usable energy directly. Powerwall 3 is 13.5 kWh usable per unit, and Tesla's datasheet allows up to seven units with Expansions for 94.5 kWh in one system.