Solar battery bank calculator for off-grid and backup systems, sizing bank kWh, amp-hours, battery count and series-parallel wiring from daily kWh, an appliance list or Ah per day.
Use your daily or monthly kWh. Battery type sets depth of discharge and efficiency.
Battery Unit & Efficiency
Peak Load & Solar Recharge
Battery Price
The US 30% homeowner credit for batteries ended for systems installed after 2025.
Battery Bank Wiring Diagram
Solar Battery Size Chart
| Daily Use | Bank Size | At 48 V | 12 V 100 Ah Units |
|---|---|---|---|
| 1.00 kWh/day | 2.47 kWh | 51 Ah | 4 batteries |
| 2.00 kWh/day | 4.94 kWh | 103 Ah | 8 batteries |
| 3.00 kWh/day | 7.41 kWh | 154 Ah | 8 batteries |
| 5.00 kWh/day | 12.3 kWh | 257 Ah | 12 batteries |
| 10.0 kWh/day | 24.7 kWh | 514 Ah | 24 batteries |
| 15.0 kWh/day | 37.0 kWh | 772 Ah | 32 batteries |
| 20.0 kWh/day | 49.4 kWh | 1,029 Ah | 44 batteries |
| 30.0 kWh/day | 74.1 kWh | 1,543 Ah | 64 batteries |
12 V vs 24 V vs 48 V Bank
| Bank Voltage | Amp-Hours | Wiring | Peak Current |
|---|---|---|---|
| 12 V | 2,058 Ah | 1S × 21P | 278 A |
| 24 V | 1,029 Ah | 2S × 11P | 139 A |
| 48 V | 514 Ah | 4S × 6P | 69 A |
Step-by-Step Math
Backup for 10 kWh a Day: Solar Battery Bank Calculator Math
A home using 10 kWh a day needs a 24.7 kWh LiFePO4 bank for two days of backup at 90% depth of discharge and 90% efficiency. At 48 V that is 514 Ah, or twenty-four 12 V 100Ah batteries wired 4S × 6P.
Four numbers drive every solar battery bank calculator result: daily energy, backup days, depth of discharge and efficiency. Bank voltage only changes how that energy is split into amp-hours.
Ebank is the bank size in Wh and Eday is daily use in Wh. D is backup days without sun. DoD is the share of the bank you drain, and η is battery plus inverter efficiency, both as decimals.
CAh is the bank capacity in amp-hours at the bank voltage Vbank. A 24,691 Wh solar battery bank calculator result is 514 Ah at 48 V, 1,029 Ah at 24 V and 2,058 Ah at 12 V.
For the 10 kWh home, 10,000 Wh × 2 days = 20,000 Wh. Then 20,000 ÷ (0.90 × 0.90) = 24,691 Wh, and 24,691 ÷ 48 V = 514.4 Ah. That rounds up to six parallel strings of 100 Ah, so 600 Ah and 28.8 kWh go in.
Rounding up adds margin. The installed 28.8 kWh holds 25.9 kWh above the 90% floor and delivers 23.3 kWh after losses, which is 2.33 days instead of the 2.00 the solar battery bank calculator formula targets.
One normal day pulls 38.6% of the full bank. That daily cycle depth matters for lead-acid life far more than for lithium, since lead-acid wears fastest when it is drained deep every day.
kWh, Amp-Hours and Battery Count by Daily Use
A 5 kWh day needs a 6.17 kWh LiFePO4 bank for one day and 12.3 kWh for two. At 48 V the two-day bank is 257 Ah, or twelve 12 V 100Ah batteries.
This solar battery size chart uses 90% depth of discharge and 90% efficiency, the LiFePO4 case. Battery counts are 12 V 100Ah units wired for a 48 V bank, rounded up to whole strings of four.
| Daily use | Bank for 1 day | Batteries for 1 day | Bank for 2 days | Ah at 48 V, 2 days | Batteries for 2 days |
|---|---|---|---|---|---|
| 1 kWh | 1.23 kWh | 4 | 2.47 kWh | 51 Ah | 4 |
| 2 kWh | 2.47 kWh | 4 | 4.94 kWh | 103 Ah | 8 |
| 3 kWh | 3.70 kWh | 4 | 7.41 kWh | 154 Ah | 8 |
| 5 kWh | 6.17 kWh | 8 | 12.3 kWh | 257 Ah | 12 |
| 10 kWh | 12.3 kWh | 12 | 24.7 kWh | 514 Ah | 24 |
| 15 kWh | 18.5 kWh | 16 | 37.0 kWh | 772 Ah | 32 |
| 20 kWh | 24.7 kWh | 24 | 49.4 kWh | 1,029 Ah | 44 |
| 30 kWh | 37.0 kWh | 32 | 74.1 kWh | 1,543 Ah | 64 |
The small rows show where a 48 V solar battery bank calculator plan stops making sense. Four 12 V batteries are the minimum string, so a 1 kWh day gets 4.8 kWh of batteries whether it needs 1.23 kWh or 2.47 kWh.
A 2 kWh day for two days needs 103 Ah at 48 V, just over one string, so it takes eight batteries. At 12 V the same bank is 412 Ah, or five batteries, so small cabins and vans suit a 12 V or 24 V solar battery bank calculator plan.
LiFePO4, Lithium-Ion or Lead-Acid: Bank Size Compared
Lead-acid needs about twice the bank of LiFePO4 for the same backup. Two days at 10 kWh takes 50.0 kWh of lead-acid at 50% depth and 80% efficiency, against 24.7 kWh of LiFePO4.
| Battery type | Depth of discharge | Efficiency | 5 kWh/day, 2 days | 10 kWh/day, 2 days | 20 kWh/day, 2 days |
|---|---|---|---|---|---|
| LiFePO4 | 90% | 90% | 12.3 kWh / 12 | 24.7 kWh / 24 | 49.4 kWh / 44 |
| Lithium-ion | 80% | 90% | 13.9 kWh / 12 | 27.8 kWh / 24 | 55.6 kWh / 48 |
| Lead-acid | 50% | 80% | 25.0 kWh / 24 | 50.0 kWh / 44 | 100.0 kWh / 84 |
Each cell is bank kWh and the count of 12 V 100Ah batteries at 48 V. The 50% lead-acid figure is not a guess. Trojan's Industrial Line User's Guide says renewable systems are typically designed for 20% to 50% depth of discharge, and never past 80%.
In a solar battery bank calculator run for lead-acid, a 10 kWh home grows to 44 batteries in 11 parallel strings. That many strings share current poorly, so 2 V or 6 V cells suit a lead-acid bank better than 12 V blocks.
LiFePO4 at 90% and lithium-ion at 80% land on the same 24 batteries at 10 kWh a day, but the gap opens at 20 kWh, 44 against 48. Any solar battery bank calculator comparison should use the depth the maker rates for daily cycling.
Efficiency Losses That Change the Battery Count
Raising efficiency from 90% to 95% turns the 10 kWh, two-day solar battery bank calculator answer from 24 batteries into 20. That saves $1,120 at $280 a battery, but only if the inverter and battery really lose just 5%.
Ninety percent is the more defensible figure for a lithium bank feeding household loads. Victron's MultiPlus-II datasheet lists a maximum inverter efficiency of 93% at 12 V, 94% at 24 V and 96% at 48 V, before any battery losses.
| Case at 10 kWh/day, 2 days | Bank needed | Ah at 48 V | Batteries | Backup delivered | Battery cost at $280 |
|---|---|---|---|---|---|
| 95% efficiency | 23.4 kWh | 487 Ah | 20 | 2.05 days | $5,600 |
| 90% efficiency | 24.7 kWh | 514 Ah | 24 | 2.33 days | $6,720 |
| 89% efficiency | 25.0 kWh | 520 Ah | 24 | 2.31 days | $6,720 |
| 90% plus 18 W inverter idle draw | 25.8 kWh | 537 Ah | 24 | 2.24 days | $6,720 |
The 89% row matches the round-trip rating in Tesla's Powerwall 3 datasheet for solar to battery to home. Both 90% and 89% land on the same 24 batteries, so the exact loss figure matters less than not overstating it.
Idle draw is the loss most solar battery bank calculator inputs leave out. The same Victron inverter uses 18 W with no load, which is 432 Wh a day. Add it to daily use; on a 10 kWh day it eats the spare margin, cutting backup from 2.33 to 2.24 days.
12 V, 24 V or 48 V for the Same Bank
The same 24.7 kWh bank is 2,058 Ah at 12 V, 1,029 Ah at 24 V and 514 Ah at 48 V. The energy is identical; the current changes, from 278 A at 12 V to 69 A at 48 V for a 3,000 W load.
| Bank voltage | Amp-hours | Wiring of 12 V 100Ah units | Current at 3,000 W | Inverter max efficiency |
|---|---|---|---|---|
| 12 V | 2,058 Ah | 1S × 21P | 278 A | 93% |
| 24 V | 1,029 Ah | 2S × 11P | 139 A | 94% |
| 48 V | 514 Ah | 4S × 6P | 69 A | 96% |
At 12 V, twenty-one batteries sit in parallel and a 3,000 W load pulls 278 A, which needs very heavy cable and fusing. Past about 1,080 W, a 12 V bank pulls more than 100 A, so most home solar battery bank calculator plans move to 48 V.
A solar battery calculator 12V result still fits a van or boat with a 1 to 2 kWh day. A 12 V 100Ah battery stores 1.2 kWh, and three of them cover a 2 kWh day for one day at 90% depth and 90% efficiency.
The Current Calculator converts any load to amps at your bank voltage, which sets the cable and fuse size before you buy.
Wiring Batteries in Series and Parallel
Series count is bank voltage divided by battery voltage, and parallel strings are amp-hours needed divided by one battery's Ah, rounded up. Four 12 V batteries in series make 48 V; six such strings make 600 Ah.
N is the battery count, Vunit is one battery's nominal voltage and Cunit is its amp-hour rating. The ceiling brackets mean the parallel count always rounds up to a whole string.
LiFePO4 batteries are often labeled 12.8 V, and four in series make 51.2 V, not 48 V. Dividing the 24.7 kWh bank by 51.2 V gives 482 Ah, so five strings of 12.8 V units do the job: 20 batteries instead of 24, holding 25.6 kWh.
That gap is easy to miss in any solar battery bank calculator estimate that divides by the nominal 48 V. Five strings of 12.8 V 100Ah units still deliver 20.7 kWh after losses, or 2.07 days at 10 kWh a day.
| 2 kWh/day backup | Bank needed | 12 V wiring | 24 V wiring | 48 V wiring |
|---|---|---|---|---|
| 1 day | 2.47 kWh | 1S × 3P, 3 batteries | 2S × 2P, 4 batteries | 4S × 1P, 4 batteries |
| 2 days | 4.94 kWh | 1S × 5P, 5 batteries | 2S × 3P, 6 batteries | 4S × 2P, 8 batteries |
| 3 days | 7.41 kWh | 1S × 7P, 7 batteries | 2S × 4P, 8 batteries | 4S × 2P, 8 batteries |
A 2 kWh day shows why battery bank size depends on voltage. Two days at 48 V needs eight batteries because 103 Ah spills into a second string, while 12 V does it with five.
Five or more parallel strings in a solar battery bank calculator layout share current unevenly unless every cable is the same length and gauge. Higher-Ah batteries or a higher bank voltage bring the string count down.
House Backup From an Appliance List
Critical loads usually need a far smaller solar battery bank calculator result than whole-home use. A 250 W freezer for 8 hours, a 15 W router all day, a 60 W fan for 8 hours and a 40 W CPAP for 8 hours add up to 3,160 Wh a day.
That list needs a 3.9 kWh LiFePO4 bank for one day and 7.8 kWh for two, eight 12 V 100Ah batteries at 48 V. Whole-home use of 30 kWh a day needs 37.0 kWh for just one day, close to ten times as much.
| Backup plan | Daily use | 1 day | 2 days | 3 days |
|---|---|---|---|---|
| Critical loads only | 3.16 kWh | 3.90 kWh / 4 | 7.80 kWh / 8 | 11.7 kWh / 12 |
| AC, freezer, PC and fan | 8.68 kWh | 10.7 kWh / 12 | 21.4 kWh / 20 | 32.1 kWh / 28 |
| Whole home | 30 kWh | 37.0 kWh / 32 | 74.1 kWh / 64 | 111.1 kWh / 96 |
The middle row is a 900 W window AC for 6 hours, a 250 W freezer for 8, a 200 W desktop for 4 and a 60 W fan for 8. The AC alone is 5.4 kWh, or 62% of that day, so cooling decides how much battery backup a house needs.
Tesla lists Powerwall 3 at 13.5 kWh of usable AC energy, so the depth and efficiency division is already done. A 30 kWh day needs three units for one day, not the 37.0 kWh from the DC solar battery bank calculator formula.
The Energy Consumption Calculator totals a longer appliance list before any solar battery bank calculator sizing, and the Battery Life Calculator checks how long one load runs.
Cold, Peak Load and Solar Recharge
A solar battery bank calculator result sized for a mild climate can fall short in winter. Trojan's guide says lead-acid at 0°F (-18°C) delivers 50% of rated capacity, so the 50.0 kWh lead-acid bank would need about 100 kWh there.
Lithium banks hold capacity better in cold, but LiFePO4 datasheets typically allow charging only above 32°F (0°C). In an unheated garage or shed, plan heated or insulated storage before adding batteries.
Peak load sets the current, not the energy. A 3,000 W load on the 48 V bank draws 69.4 A, which is 0.12C on 600 Ah and well inside lithium limits. Above 1C, check each battery's continuous discharge rating or add strings.
| Steady load | Runtime on 23.3 kWh delivered | Peak sun hours | Solar to refill 10 kWh a day |
|---|---|---|---|
| 500 W | 46.7 h | 2.8 h (London) | 4.96 kW |
| 1,000 W | 23.3 h | 4.0 h (New Delhi) | 3.47 kW |
| 3,000 W | 7.8 h | 4.6 h (US average) | 3.02 kW |
| 5,000 W | 4.7 h | 5.1 h (Riyadh) | 2.72 kW |
Recharge is the step most battery sizing skips. The array must refill one day of use in average sun, or each cloudy spell leaves the bank lower than the last.
At 4.6 sun hours, 80% array efficiency and 90% battery efficiency, a 10 kWh day needs 3.02 kW of panels to pair with any solar battery bank calculator result.
The Solar Panel Size Calculator turns that kW into a panel count and roof area, and the Battery Charge Time Calculator shows the hours a given charge current needs.
Price per Usable kWh
Twenty-four 12 V 100Ah batteries at $280 each cost $6,720, or $259 per usable kWh and $2,881 per day of backup. Racks, cables, fuses, a battery monitor and the inverter come on top of that.
Cost per usable kWh is the fair way to compare chemistries in a solar battery bank calculator estimate. For the 10 kWh, two-day goal, lead-acid needs 44 batteries against 24, so each must cost no more than about 55% as much to break even.
Any currency works the same way. A rupee or euro price per battery gives a rupee or euro total, so a solar battery bank calculator India estimate needs only a local price per battery and New Delhi's 4.0 sun hours for the recharge check.
US buyers lost the 30% federal credit for home batteries installed after 2025. A solar battery repayment or savings estimate should now start from the full battery price, less any utility or state rebate.
Answers on Battery kWh and Sizing
Each answer below uses the same solar battery bank calculator defaults of 90% depth and 90% efficiency for LiFePO4, unless it names another battery.
How do you size a solar battery bank?
Multiply daily Wh by backup days, divide by depth of discharge times efficiency, then divide by bank voltage for amp-hours. A cabin using 2 kWh a day for three days needs 7,407 Wh, which is 309 Ah at 24 V.
Next, divide bank voltage by battery voltage for the series count, and amp-hours by one battery's Ah for the parallel count, rounding up. At 24 V that cabin takes 2S × 4P, eight 12 V 100Ah batteries holding 9.6 kWh.
What is a solar battery bank calculator?
The term covers the bank-sizing formula above plus the rounding to whole batteries and strings. Any solar battery bank calculator estimate rests on four inputs: daily Wh, backup days, depth of discharge and efficiency.
The same math fits a spreadsheet. With daily Wh in A2, days in B2, DoD in C2 and efficiency in D2, the formula =A2*B2/(C2*D2) gives bank Wh, and =ROUNDUP(E2/F2/G2,0) gives parallel strings from bank Wh, volts and battery Ah.
How many kWh are in a solar battery?
A battery's kWh is volts times amp-hours divided by 1,000. A 12 V 100Ah battery holds 1.2 kWh, a 12.8 V 100Ah LiFePO4 holds 1.28 kWh and a 48 V 100Ah server-rack battery holds 4.8 kWh.
| Battery | Rated energy | Usable at 90% depth | Usable at 50% depth |
|---|---|---|---|
| 12 V 100Ah | 1.20 kWh | 1.08 kWh | 0.60 kWh |
| 12.8 V 100Ah LiFePO4 | 1.28 kWh | 1.15 kWh | 0.64 kWh |
| 12 V 200Ah | 2.40 kWh | 2.16 kWh | 1.20 kWh |
| 24 V 100Ah | 2.40 kWh | 2.16 kWh | 1.20 kWh |
| 48 V 100Ah | 4.80 kWh | 4.32 kWh | 2.40 kWh |
| 51.2 V 100Ah LiFePO4 | 5.12 kWh | 4.61 kWh | 2.56 kWh |
Packaged home batteries quote usable energy directly. Powerwall 3 is 13.5 kWh usable per unit, and Tesla's datasheet allows up to seven units with Expansions for 94.5 kWh in one system.