Solar wire size calculator results in AWG or mm² for panel strings, controller, battery, inverter and AC runs, checked against 156% of panel Isc, rooftop heat and the voltage drop.
Pick the wire run, enter its current and voltage, then the one-way length. Heat and conduit settings are below.
Heat, Conduit & Terminals
Wire Run Diagram
Wire Size Comparison
| Wire Size | Safe Current | Volts Lost | Drop | Max Run | Result |
|---|---|---|---|---|---|
| 12 AWG | 25.0 A | 5.46 V | 8.76% | 17.1 ft | Too small for current |
| 10 AWG | 35.0 A | 3.42 V | 5.48% | 27.3 ft | Too small for current |
| 8 AWG | 50.0 A | 2.15 V | 3.44% | 43.6 ft | Too much drop |
| 6 AWG | 65.0 A | 1.36 V | 2.17% | 69.1 ft | Picked |
| 4 AWG | 85.0 A | 0.85 V | 1.36% | 110.1 ft | Also works |
| 3 AWG | 100.0 A | 0.68 V | 1.08% | 138.4 ft | Also works |
| 2 AWG | 115.0 A | 0.54 V | 0.86% | 174.8 ft | Also works |
Solar Wire Size Chart
| Current | 10 ft | 20 ft | 30 ft | 50 ft | 75 ft | 100 ft | 150 ft |
|---|---|---|---|---|---|---|---|
| 5 A | 14 | 14 | 14 | 14 | 12 | 10 | 10 |
| 10 A | 12 | 12 | 12 | 10 | 10 | 8 | 6 |
| 15 A | 10 | 10 | 10 | 10 | 8 | 6 | 4 |
| 20 A | 8 | 8 | 8 | 8 | 6 | 4 | 4 |
| 27.6 A | 8 | 8 | 8 | 6 | 4 | 4 | 2 |
| 30 A | 8 | 8 | 8 | 6 | 4 | 4 | 2 |
| 40 A | 6 | 6 | 6 | 4 | 4 | 2 | 1 |
| 50 A | 4 | 4 | 4 | 4 | 3 | 1 | 1/0 |
| 60 A | 3 | 3 | 3 | 3 | 2 | 1 | 2/0 |
| 80 A | 1 | 1 | 1 | 1 | 1 | 2/0 | 3/0 |
| 100 A | 2/0 | 2/0 | 2/0 | 2/0 | 2/0 | 3/0 | 4/0 |
| 150 A | 250 kcmil | 250 kcmil | 250 kcmil | 250 kcmil | 250 kcmil | 250 kcmil | 350 kcmil |
| 200 A | 400 kcmil | 400 kcmil | 400 kcmil | 400 kcmil | 400 kcmil | 400 kcmil | 500 kcmil |
Step-by-Step Math
Solar Wire Size Calculator Chart by Amps and One-Way Feet
At 12 V and a 3% drop limit, 20 A over 25 ft one-way needs 4 AWG copper, while the same 20 A at 48 V reaches 100 ft on 4 AWG. Battery and DC load circuits in this solar wire size calculator chart assume 104 °F air, 90 °C wire and 75 °C terminals.
| Load current | 12 V, 10 ft | 12 V, 25 ft | 24 V, 25 ft | 24 V, 50 ft | 48 V, 50 ft | 48 V, 100 ft |
|---|---|---|---|---|---|---|
| 5 A | 14 | 10 | 12 | 10 | 12 | 10 |
| 10 A | 10 | 6 | 10 | 6 | 10 | 6 |
| 20 A | 8 | 4 | 6 | 4 | 6 | 4 |
| 30 A | 6 | 2 | 4 | 2 | 4 | 2 |
| 40 A | 4 | 1 | 4 | 1 | 4 | 1 |
| 60 A | 3 | 2/0 | 2 | 2/0 | 2 | 2/0 |
Doubling the system voltage lets the same current run twice as far on the same gauge. In a solar wire size calculator table the 12 V column at 25 ft matches 24 V at 50 ft, row for row, because the percentage drop is identical.
Lengths are one-way, as in any solar wire size calculator, and the return wire doubles the copper in the drop math. Each size also clears 125% of the load current at the 75 °C terminal rating, so 60 A never drops below 3 AWG even on a 10 ft run.
Panel-side circuits carry a larger multiplier, so a load chart under-sizes array wiring; strings belong in the 156% table further down.
Convert a load rated in watts to amps before reading any solar wire size calculator chart, using the Current Calculator for DC or single-phase AC loads.
156% of Isc Comes Before Any Gauge
A 27.6 A array needs wire rated for 43.1 A at 75 °C, not 27.6 A. NEC 690.8 multiplies short-circuit current by 1.25 twice, so 8 AWG (50 A) carries this circuit, and in the solar wire size calculator result the 50 ft voltage drop moves it to 6 AWG.
Isc is the array short-circuit current, the sum of the parallel strings. The first 1.25 covers sunlight brighter than test conditions, the second covers continuous duty, and Amin is checked against the 75 °C column of NEC Table 310.16.
A second test runs in parallel. After heat and bundling corrections, the 90 °C rating must still reach 1.25 × Isc, a check several solar wire size calculator pages skip.
The EC&M Code Q&A on PV conductor ampacity works both checks for an 8 AWG example, using 55 A × 0.58 for conduit on a roof.
The solar wire ampacity chart below inverts the rule: the largest array Isc each copper gauge can serve, including the next-size-up fuse limit. Short runs are assumed, so voltage drop is not yet in play.
| Copper gauge | 104 °F air | 122 °F air | 104 °F, 4 circuits in conduit | 104 °F, conduit on roof |
|---|---|---|---|---|
| 14 AWG | 9.6 A | 9.6 A | 9.6 A | 9.6 A |
| 12 AWG | 12.8 A | 12.8 A | 12.8 A | Skipped |
| 10 AWG | 19.2 A | 19.2 A | 19.2 A | 12.8 A |
| 8 AWG | 32.0 A | 32.0 A | 25.6 A | 19.2 A |
| 6 AWG | 41.6 A | 41.6 A | 32.0 A | 25.6 A |
| 4 AWG | 54.4 A | 51.2 A | 44.8 A | 32.0 A |
| 3 AWG | 64.0 A | 64.0 A | 51.2 A | 38.4 A |
| 2 AWG | 73.6 A | 70.4 A | 57.6 A | 44.8 A |
| 1 AWG | 83.2 A | 80.0 A | 64.0 A | 51.2 A |
| 1/0 AWG | 96.0 A | 96.0 A | 70.4 A | 57.6 A |
| 2/0 AWG | 112.0 A | 112.0 A | 80.0 A | 64.0 A |
| 3/0 AWG | 128.0 A | 128.0 A | 96.0 A | 80.0 A |
| 4/0 AWG | 147.2 A | 144.0 A | 112.0 A | 96.0 A |
In open air up to 104 °F, the 75 °C terminal limit decides everything: maximum Isc equals the 75 °C ampacity divided by 1.5625, so 8 AWG tops out at 32 A. Heat starts to bite only with bundling or a sunny roof.
On a hot roof, 12 AWG never wins. Its corrected 15 A rating permits only a 15 A fuse, the same as 14 AWG, so 10 AWG takes over above 9.6 A. That gap is why roof-mounted home runs jump from 14 to 10 AWG in a solar wire size calculator.
Voltage drop in a solar wire size calculator estimate should use the operating current Imp, not Isc. Two strings of 13.79 A Isc and 12.9 A Imp lose 2.03% over 50 ft of 6 AWG at 62.4 V, against 2.17% when Isc stands in for both.
Rooftop Heat and Bundled Conduit Push the Size Up
Conduit lying within 7/8 in (23 mm) of a sunny roof adds 33 °C under NEC 310.15(B)(2). At 104 °F air the wire sits at 73 °C, keeps half its 90 °C rating, and the 27.6 A array circuit needs 4 AWG for current alone, against 8 AWG in open air.
| Wire location | Combined factor | Size for current | Size over 50 ft | Drop over 50 ft |
|---|---|---|---|---|
| 86 °F air | 1.00 | 8 | 6 | 2.17% |
| 104 °F air | 0.91 | 8 | 6 | 2.17% |
| 122 °F air | 0.82 | 8 | 6 | 2.17% |
| 104 °F, 4 circuits in one conduit | 0.64 | 6 | 6 | 2.17% |
| 95 °F, conduit on roof | 0.58 | 6 | 6 | 2.17% |
| 104 °F, conduit on roof | 0.50 | 4 | 4 | 1.36% |
| 104 °F, 2 circuits on roof | 0.40 | 3 | 3 | 1.08% |
Bundling, the factor most often missed in a solar wire size calculator run, counts current-carrying conductors, two per DC circuit.
Four circuits put eight wires in one conduit, which multiplies the rating by 0.70, and with 104 °F air the combined 0.64 moves the size for current from 8 to 6 AWG.
Insulation rated 75 °C, such as plain THWN, has no ampacity at all at 73 °C in NEC Table 310.15(B)(1). Roof conduit therefore needs 90 °C wire, and the IAEI inspector guidance shows the factor falling to 0.29 at 83 °C.
Lifting the conduit 7/8 in or more removes the adder. Left flat, it moves this circuit from 6 to 4 AWG over 50 ft, so a solar wire size calculator result for rooftop runs should always state the conduit height.
Voltage Drop at 1%, 2% and 3%: Copper Against Lost Watts
Most DC solar wiring is held to 3% or less, the usual target in a solar wire size calculator. Australia caps PV DC drop at 3% under AS/NZS 5033, per Electrotechnik's summary of the limits.
The NEC suggests no more than 3% on a branch circuit and 5% overall, but only in informational notes, so the US limit is a design choice rather than a code rule.
| Drop limit | Copper size | Volts lost | Actual drop | Heat at full current | Loss per year, 5 h/day | Longest run at limit |
|---|---|---|---|---|---|---|
| 1% | 2 | 0.54 V | 0.86% | 14.8 W | 27.0 kWh | 58.3 ft |
| 2% | 4 | 0.85 V | 1.36% | 23.5 W | 42.8 kWh | 73.4 ft |
| 3% | 6 | 1.36 V | 2.17% | 37.4 W | 68.3 kWh | 69.1 ft |
| 5% | 8 | 2.15 V | 3.44% | 59.3 W | 108.2 kWh | 72.7 ft |
Going from 3% to 1% swaps 6 AWG for 2 AWG, which holds 2.53 times the copper (66,360 against 26,240 circular mils), to save 22.6 W at full sun and 41.3 kWh a year. The Electricity Cost Calculator prices that energy.
CM is the minimum area in circular mils, K is 12.9 Ω·cmil/ft for copper or 21.2 for aluminum at 75 °C, L is the one-way length in feet, I is the current, and Vdrop is the allowed loss in volts.
For the 3% row, 62.4 V × 3% allows 1.872 V, and 2 × 12.9 × 50 × 27.6 ÷ 1.872 gives 19,019 cmil. That clears 8 AWG (16,510) and lands on 6 AWG (26,240).
The 0.491 Ω per 1,000 ft for 6 AWG copper comes from NEC Chapter 9, Table 8, as listed in Mike Holt's Table 8 extract.
Three-phase AC replaces the 2 with 1.732 in the same solar wire size calculator formula. Low-voltage DC feels the limit hardest: 20 A over 20 ft at 12 V needs 4 AWG at 3% but 1/0 AWG at 1%, which is why long 12 V runs move to 24 or 48 V.
Metric mm² Cable for Strings, Battery Leads and AC
A 10-panel string of 13.79 A Isc modules at 312 V needs 2.5 mm² over 30 m at 3% in a solar wire size calculator in mm, 4 mm² at 2% and 6 mm² at 1%.
A 12 V battery lead carrying 20 A over just 5 m needs 16 mm², because low voltage leaves almost no room for loss: 3% of 12 V is only 0.36 V.
| Circuit | One-way length | Drop limit | Copper cable | IEC fuse | Actual drop | US gauge for the same run |
|---|---|---|---|---|---|---|
| 10-panel string, 312 V | 30 m | 3% | 2.5 mm² | None | 2.13% | 12 AWG |
| 10-panel string, 312 V | 30 m | 1% | 6 mm² | None | 0.89% | 8 AWG |
| 2 strings in parallel, 62.4 V | 15 m | 3% | 10 mm² | None | 2.66% | 6 AWG |
| 12 V DC load, 20 A | 5 m | 3% | 16 mm² | 25 A | 2.23% | 6 AWG |
| 24 V controller to battery, 40 A | 3 m | 3% | 10 mm² | 50 A | 2.14% | 8 AWG |
| 48 V controller to battery, 60 A | 5 m | 3% | 16 mm² | 80 A | 1.68% | 4 AWG |
| 5 kW inverter, 230 V single-phase | 20 m | 3% | 4 mm² | 32 A | 2.03% | 10 AWG |
| 10 kW inverter, 400 V three-phase | 30 m | 3% | 2.5 mm² | 20 A | 1.61% | 12 AWG |
A is the cross-section in mm², ρ is resistivity, 0.0214 Ω·mm²/m for copper and 0.0352 for aluminium at 75 °C, L is the one-way length in metres, I is the current and ΔV is the allowed drop in volts.
Those four values are all any solar wire size calculator in mm needs for the drop side; the current check comes separately from the ampacity tables.
Many solar wire size calculator formulas online plug in 0.0172, copper at 20 °C, which is only 80% of the 75 °C figure. For the 12 V lead that cold value asks for 9.56 mm² and picks 10 mm², which really loses 0.429 V, or 3.57%, once the wire warms.
Metric current ratings follow IEC 60364-5-52 Table C.52.1 and change with the cable route and insulation. With two loaded conductors in conduit, 4 mm² copper is rated 42 A with XLPE insulation and 31 A with PVC, before heat and grouping.
The cable must also carry its fuse, picked from the IEC range of 25, 32, 40, 50, 63 and 80 A. A 60 A, 48 V controller lead has a 75 A design current, takes an 80 A fuse, and lands on 16 mm² XLPE rated 91 A at 104 °F.
| Cable route | XLPE, 1 circuit | PVC, 1 circuit | XLPE, 4 circuits | PVC, 4 circuits |
|---|---|---|---|---|
| In conduit or trunking | 16 mm² | 25 mm² | 25 mm² | 50 mm² |
| Clipped to a wall or roof | 16 mm² | 25 mm² | 25 mm² | 35 mm² |
| Free air or open tray | 16 mm² | 16 mm² | 25 mm² | 35 mm² |
Insulation and grouping move this 60 A lead further than the route does. Four PVC circuits sharing one conduit push it from 16 to 50 mm², while the same four circuits in XLPE on an open tray need only 25 mm².
Metric PV design takes 1.25 × Isc as the maximum string current, the figure Fronius lists for IEC 60364-7-712 and AS/NZS 5033, rather than the 1.5625 of NEC 690.8. That is why a metric string cable can come out one size smaller than its AWG twin.
The earth conductor follows IEC 60364-5-54: equal to the line up to 16 mm², 16 mm² for 25 and 35 mm² lines, and half the line size above, so a 70 mm² feed takes a 35 mm² earth in a metric solar wire size calculator result.
Battery-to-Inverter Cable From 1,000 to 5,000 W
A 3,000 W inverter on 12 V needs two parallel sets of 4/0 copper. At 9.5 V cutoff and 90% efficiency it draws 350.9 A, and 125% of that is 438.6 A, past the 380 A of 500 kcmil, the largest single conductor in this solar wire size calculator table.
Idc is the battery current, P is the inverter continuous rating in watts, Vmin is the low-voltage cutoff (9.5, 19 or 38 V for 12, 24 or 48 V banks) and η is inverter efficiency as a decimal, 0.90 here.
| Inverter rating | 12 V bank | 24 V bank | 48 V bank |
|---|---|---|---|
| 1,000 W | 1/0 (150 A fuse) | 4 (80 A fuse) | 8 (40 A fuse) |
| 2,000 W | 350 kcmil (300 A fuse) | 1/0 (150 A fuse) | 4 (80 A fuse) |
| 3,000 W | 2 × 4/0 (450 A fuse) | 4/0 (225 A fuse) | 2 (110 A fuse) |
| 5,000 W | 2 × 500 kcmil (800 A fuse) | 500 kcmil (400 A fuse) | 3/0 (200 A fuse) |
Every size in this solar wire size calculator table is for a 6 ft one-way cable, where drop stays near 0.84% even for the 12 V, 3,000 W case, so current decides the gauge. Moving the same inverter to 48 V cuts the cable to 2 AWG on a 110 A fuse.
Parallel sets are allowed only at 1/0 and larger, with the same length, metal, size and lugs on each set, under NEC 310.10(G). The Inverter Size Calculator sets the rating, and the Solar Battery Bank Calculator picks the bank voltage.
Fuse, Ground Wire and EMT Conduit by Gauge
The fuse or breaker paired with a solar wire size calculator result is the next standard size at or above 125% of the circuit current, 156% for array circuits.
The ground wire then follows NEC Table 250.122 by that fuse rating, and conduit is sized at 40% fill of EMT.
| Circuit current | 125% of current | Copper wire | Fuse or breaker | Ground wire | EMT conduit |
|---|---|---|---|---|---|
| 16 A | 20.0 A | 12 | 20 A | 12 | 1/2 in |
| 30 A | 37.5 A | 8 | 40 A | 10 | 1/2 in |
| 40 A | 50.0 A | 8 | 50 A | 10 | 1/2 in |
| 60 A | 75.0 A | 4 | 80 A | 8 | 3/4 in |
| 80 A | 100.0 A | 3 | 100 A | 8 | 1 in |
| 120 A | 150.0 A | 1/0 | 150 A | 6 | 1-1/4 in |
| 160 A | 200.0 A | 3/0 | 200 A | 6 | 1-1/4 in |
| 200 A | 250.0 A | 250 kcmil | 250 A | 4 | 2 in |
Each row assumes a short 48 V DC run with one circuit, so current sets the size. Conduit area uses THWN-2 dimensions from NEC Chapter 9; PV wire has thicker insulation, so measure its outside diameter before trusting a conduit size.
Conduit fill counts every wire in the pipe, including the ground. Two 6 AWG conductors and an 8 AWG ground take 0.138 in², inside the 0.213 in² that 40% of 3/4 in EMT allows.
A ground wire grows when voltage drop forces a larger main wire, per NEC 250.122(B). The default 27.6 A array circuit uses 6 AWG, 1.59 times the 8 AWG current needs, so its ground moves from 10 to 8 AWG.
Longer runs push it further: at 150 ft the same array circuit takes 2 AWG for drop, and its ground grows in step to 4 AWG instead of the 10 AWG the fuse table lists.
For combined strings, a solar wire size calculator result also needs string fuses, required at three or more parallel strings and sized at 1.56 × module Isc.
A 13.79 A module gives 21.5 A, so each string takes a 25 A fuse, as long as the module datasheet allows a series fuse that large.
Wire Type, Gauge and Run Length Cases
Answers below use the same NEC tables, 104 °F (40 °C) design air and 75 °C terminals as the solar wire size calculator charts above, with copper unless the question is about aluminum or a metric market.
What gauge wire for solar panels?
A string of 13.79 A panels needs 12 AWG, since 1.5625 × 13.79 A is 21.5 A and 12 AWG carries 25 A. In roof conduit the 33 °C adder pushes it to 10 AWG, which is why 10 AWG PV wire is the usual solar wire size calculator answer for one string.
What size cable from solar panel to inverter?
A 10-panel string at 312 V runs 100 ft on 12 AWG with 1.64% drop, and 200 ft on 10 AWG at 2.05%. High string voltage keeps drop low, so ampacity and roof heat usually decide this cable in a solar wire size calculator, not length.
Combining three such strings before the inverter raises the home run to 6 AWG over 100 ft and adds a 25 A fuse on each string. Above 8 AWG, land the panel leads in a combiner box and run the heavier cable from there.
Stäubli lists its MC4 couplers for cross-sections up to 10 mm² in the MC4 cable coupler datasheet, which is the 8 AWG ceiling for any lead plugged straight into a panel.
What size wire from charge controller to battery?
A 40 A controller on 24 V needs 8 AWG over 10 ft with a 50 A fuse, and drops 2.59%. At 12 V, a 30 A unit needs 6 AWG and a 60 A unit needs 3 AWG over the same 10 ft, both set by voltage drop.
Size this run in a solar wire size calculator from the controller output rating, not the panel watts, since that is the most it can push. The Charge Controller Size Calculator sets that rating from the array and battery voltage.
What wire size is used for solar panels in India?
Rooftop strings in India mostly use 4 mm² or 6 mm² DC solar cable, and a solar wire size calculator run for India explains why.
A 10-panel string at 312 V needs only 2.5 mm² over 30 m at 3% in open air, but conduit lying on a sunny roof halves the rating and forces 4 mm², and 6 mm² holds it under 1%.
The AC side follows the inverter: a 5 kW single-phase inverter at 230 V takes 4 mm² over 20 m on a 32 A breaker, at 2.03% drop. Larger three-phase systems shift to 400 V, where a 10 kW inverter needs only 2.5 mm² over 30 m on 20 A.
Can I use regular copper wire for solar?
House wiring such as NM cable is held to 60 °C ampacity and is not sunlight or wet-rated, so it cannot be exposed on an array. In conduit, 90 °C wet-rated THWN-2, RHW-2 or XHHW-2 is accepted, per the San Luis Obispo County PV inspection checklist.
The heat check in a solar wire size calculator rules out lower ratings on roofs too. With 104 °F air plus the 33 °C rooftop adder, both 60 °C and 75 °C insulation have no ampacity left, while 90 °C wire keeps half its rating.
What is the difference between PV Wire and USE-2?
Both are rated 90 °C wet or dry and resist sunlight, but PV Wire (UL 4703) has thicker insulation and passes a 720-hour weathering test against 300 hours for USE-2 (UL 854), per Renewable Energy World.
USE-2 carries a 600 V rating, while PV Wire comes in 600 V, 1,000 V and 2,000 V versions. Many reels are dual-listed as PV, USE-2 and RHW-2, which lets one cable run exposed on the array and continue inside conduit.
Should I use 600V or 2000V PV wire?
Choose a rating above the cold-weather open-circuit voltage of the string, not its nameplate Voc, since a cold morning lifts Voc well above the label.
One- and two-family dwellings in the US are held to 600 V DC by NEC 690.7, so 600 V wire works there, while commercial strings at 1,000 to 1,500 V need 1,000 or 2,000 V wire.
Voltage rating does not change ampacity or voltage drop in a solar wire size calculator, which depend only on conductor size, metal and temperature, so a 2,000 V reel of 10 AWG sizes exactly like a 600 V reel.
What is voltage rise in a solar system?
Voltage rise is the extra voltage at a grid inverter from pushing current back through cable resistance.
A 5 kW inverter at 230 V raises its terminals 4.66 V, or 2.03%, through 20 m of 4 mm² cable, the smallest size that carries its 32 A breaker and passes a 3% drop check.
That rise equals the drop in a solar wire size calculator result for the same cable and current, only reversed in direction.
Australia and New Zealand cap total rise at 2% from the point of supply to the inverter under AS/NZS 4777.1, a limit restated by NT WorkSafe.
That 4 mm² run alone breaks the limit, so holding it to 1% means 10 mm² at 1.86 V, which leaves 2.74 V of the 4.6 V budget for the consumer mains.
Can I use smaller wire for short cable runs?
Only down to the ampacity floor, which no solar wire size calculator result goes below, however short the run.
A 30 A, 12 V circuit over 3 ft would pass the drop limit on 12 AWG, but 125% of 30 A is 37.5 A, so 8 AWG is the smallest legal size.
Stretch the same circuit to 15 ft and voltage drop takes over, needing 4 AWG to stay under 3%, two sizes above the short-run answer.
What about temperature derating for wire ampacity in Canadian climates?
Cold air raises ampacity, with a factor of 1.15 for 90 °C wire at 10 °C, but sizing uses the hottest expected temperature. At 86 °F or 104 °F the 27.6 A array circuit stays at 6 AWG, because the 75 °C terminal limit governs before heat does.
Canadian installations follow CSA C22.1, whose tables and rules differ from the NEC, so treat any solar wire size calculator figure built on NEC tables as a cross-check there. A roof conduit adder still applies in summer sun.
What happens if I use wire that's too small?
On the 27.6 A array circuit over 50 ft at 62.4 V, 10 AWG loses 3.42 V (5.48%) and turns 94.5 W into heat, against 37.4 W on 6 AWG.
Its 35 A terminal rating is also below the 43.1 A the code requires, so it fails a solar wire size calculator check twice.
Undersized PV wire runs hot, can trip or overheat at the fuse, and starves an MPPT controller of input voltage. An inspector can fail it on ampacity alone, before any lost energy is counted.
Is copper or aluminum better for reducing voltage drop?
Copper drops less at any given gauge. Aluminum has about 1.64 times the resistance, so 6 AWG aluminum loses 3.57% on the default array circuit against 2.17% for copper, and aluminum must go up to 4 AWG to land at 2.25%.
Aluminum cannot replace copper at the same gauge: 6 AWG aluminum carries 50 A at 75 °C against 65 A for copper. It pays off on long AC feeders, where a 7.6 kW, 240 V inverter at 100 ft takes 6 AWG aluminum instead of 8 AWG copper.
Aluminum needs lugs marked AL or AL/CU, and the smallest aluminum size in the NEC ampacity table is 12 AWG, so panel leads and small battery leads stay copper.
How do battery bank cables differ from solar panel wiring?
Battery cables carry far more current at low voltage and size from a 1.25 multiplier in a solar wire size calculator, while panel wiring uses 1.5625 on short-circuit current.
A 40 A panel circuit at 48 V needs 6 AWG over 10 ft, while a 40 A battery circuit on the same run needs only 8 AWG with a 50 A fuse.
Battery-to-inverter current is also set at the low-voltage cutoff, not the nominal voltage, which raises it about 26%. The Solar Panel Size Calculator sets the array current that feeds the panel side.