Solar Off Grid Load Calculator

Updated

Solar Off Grid Load Calculator for daily watt-hours, battery draw with inverter loss and standby, inverter size for motor starts, battery bank by autonomy days and the panel count.

Quick Setup

Enter nameplate watts and real daily run hours; a fridge compressor runs about 8 h a day.

h/day
days
h/day

Appliance Load List

h
h
W
h
h
W
h
h
W
h
h
W

Known Daily Energy and Peak Watts

W
W

Extra start watts are the biggest motor's starting watts minus its running watts.

Inverter, Battery and Solar SettingsAuto 12 V · LiFePO4 80% DoD · 400 W panels
%
%
× rated
%
%
%
W
Off-Grid Load
1,630 Wh/day
From Appliances
1,510 Wh AC + 120 Wh DC · 67.9 W average draw
1,942 Wh/day Battery Draw
Inverter Loss + Standby312 Wh/day
Amp-Hours per Day at 12 V161.8 Ah
Appliance energy plus inverter loss and standby all day long, the energy your battery supplies daily.
600 W Inverter Size
AC Running at Once230 W
Starting Surge Needed1,130 W
Covers running watts with headroom and the largest single motor start within the inverter’s surge rating.
7.28 kWh Battery Bank
Capacity at 12 V607 Ah
Usable at 80% DoD5.83 kWh
Daily draw times autonomy days, divided by depth of discharge so cloudy days never over-drain it.
800 W Solar Array (2 Panels)
Minimum Array Needed614 W
Charge Controller at 12 V70 A
Battery draw over worst-month sun hours, raised for charging and wiring losses, rounded to whole panels.
Energy Flow Diagram1,942 Wh/day from the battery
Battery draw 1,942 Wh/dayAC appliances 1,510 Wh (77.8%)Inverter loss 168 Wh (8.6%)Standby 144 Wh (7.4%)DC appliances 120 Wh (6.2%)Solar array800 WBattery7.28 kWhInverter600 WLoads1,630 WhDC loads skip the inverter, so they carry no conversion loss
Load Table by ApplianceRefrigerator uses the most (49.1%)
ApplianceTypeWatts × QtyHours/DayEnergy (Wh/day)Share
LED LightsAC20 W × 18 h1609.8%
RefrigeratorAC100 W × 18 h80049.1%
Laptop and TVAC110 W × 15 h55033.7%
Phone Chargers (USB)DC10 W × 34 h1207.4%
Inverter loss at 90%168+10.3%
Inverter standby 6 W × 24 h144+8.8%
Battery draw1,942119.1%
12 V vs 24 V vs 48 V12 V in use (auto)
SystemAh per DayBank SizeInverter Draw at Full LoadCharge Current
12 V (auto)161.8 Ah607 Ah55.6 A66.7 A
24 V80.9 Ah303 Ah27.8 A33.3 A
48 V40.5 Ah152 Ah13.9 A16.7 A
Step-by-Step Load Math9 steps
Appliance energy20 W × 1 × 8 h + 100 W × 1 × 8 h + 110 W × 1 × 5 h + 10 W × 3 × 4 h = 1,630 Wh/day (1,510 AC, 120 DC)
AC energy at the battery1,510 Wh ÷ 0.9 = 1,677.8 Wh/day
Inverter standby1% × 600 W = 6 W × 24 h = 144.0 Wh/day
Daily battery draw1,677.8 + 120.0 + 144.0 = 1,941.8 Wh/day
Peak AC load230 W running + 900 W extra start (Refrigerator) = 1,130 W
Inverter sizemax(230 × 1.25, 1,130 ÷ 2) = 565.0 W → 600 W
Battery bank1,941.8 × 3 ÷ 0.8 = 7,282 Wh ÷ 12 V = 607 Ah
Solar array1,941.8 ÷ 4 h ÷ 0.92 ÷ 0.86 = 613.6 W → 2 × 400 W
Charge controller800 W ÷ 12 V = 66.7 A → 70 A
Biggest Energy User: Refrigerator
Refrigerator takes 49.1% of the appliance load. Cutting its watts or hours shrinks the battery and the array more than any other change on this list.

Solar Off Grid Load Calculator Formulas, Worked Through

A home list of 1,630 Wh per day pulls 1,942 Wh from the battery once inverter loss and standby are counted. Every solar off grid load calculator estimate should size the battery and panels from that larger number, not the appliance total.

Daily appliance energy, the first line of any solar off grid load calculator sheet, is each load's running watts times quantity times daily hours, summed.

P is running watts, n the quantity and h the hours per day. Lights at 20 W for 8 h, a 100 W fridge for 8 h, a 110 W laptop and TV for 5 h and three 10 W DC chargers for 4 h give 1,630 Wh, of which 1,510 Wh is AC.

Battery draw adds the inverter's conversion loss on the AC share and its idle draw around the clock. DC loads skip the inverter, so they carry no conversion loss.

Here ηinv is inverter efficiency and Psb its standby watts. At 90% and 6 W, 1,510 / 0.9 + 120 + 144 = 1,941.8 Wh per day, which is 161.8 Ah from a 12 V battery.

For a solar off grid load calculator estimate, a home's load in kW sets the inverter, while its kWh per day sets the battery and panels. The inverter must cover running watts with headroom and the largest motor start within its surge rating.

Prun is the AC load running at once, Pxs the extra starting watts of the largest motor and k the inverter's surge multiple. For 230 W running plus 900 W of fridge start, max(287.5, 1,130 / 2) = 565 W, so a 600 W unit.

D is days of autonomy and DoD the usable fraction of the bank. Three days at 80% gives 1,941.8 × 3 / 0.8 = 7,282 Wh, which is a 7.28 kWh bank or 607 Ah at 12 V.

PSH is worst-month peak sun hours, ηbat battery round-trip efficiency and L the PV system loss. At 4 h, 92% and 14%, the need is 613.6 W, so two 400 W panels make an 800 W array.

An 800 W array on a 12 V bank pushes up to 66.7 A, so the next standard controller is 70 A. The Charge Controller Size Calculator covers controller choice when the array is already fixed.

For an off grid load calculator Excel sheet, each formula becomes one column in this order. The order matters, because the inverter size sets the standby watts that feed back into the battery draw.

Fridge Run Hours Can Double the Battery Bank

Counting a fridge's nameplate watts for 24 hours nearly doubles the battery in a solar off grid load calculator estimate. A 100 W compressor at 24 h puts 2,400 Wh on the list, while the same fridge cycling about 8 h a day uses 800 Wh.

Fridge counted asLoad (Wh/day)Battery draw (Wh/day)3-day LiFePO4 bankArray at 4 sun hours
100 W × 8 h run time1,6301,9427.28 kWh800 W (2 panels)
100 W × 24 h nameplate3,2303,72013.95 kWh1,200 W (3 panels)

The 24-hour reading adds 6.67 kWh of battery and a third panel for energy the fridge never uses. Freezers, well pumps and air conditioners cycle the same way, so their hours mean compressor run time, not time plugged in.

In a solar off grid load calculator list, the starting watts belong to the same fridge row. Its 1,000 W start shapes the inverter, while its 8 run hours shape the battery, and mixing the two inflates both.

Inverter Standby and Surge From Real Datasheets

An inverter idling at 6 W all day costs 144 Wh, which is 7.4% of the 1,942 Wh draw in the solar off grid load calculator example. The Victron Phoenix VE.Direct datasheet lists zero-load draw of 6 W at 500 VA, 6.5 W at 800 VA and 10 W at 1,200 VA.

The same datasheet puts ECO mode at about 1 W. At 1 W idle the daily draw falls to 1,822 Wh and the 3-day bank to 6.83 kWh, saving 0.45 kWh of battery from one setting.

Standby grows with inverter size. A 4,000 W unit idling at 1% burns 40 W, or 960 Wh a day, which is 8.0% of a 12,071 Wh home draw and almost the whole daily load of the weekend cabin below.

Inverter model names give VA, not continuous watts. Victron rates the 500 VA Phoenix at 400 W continuous and 900 W peak, a 2.25× surge, and the 1,200 VA model at 1,000 W and 2,200 W, or 2.2×.

So a 600 W solar off grid load calculator result needs 600 W continuous, which a 600 VA label does not promise. The 800 VA Phoenix clears it at 650 W, while the 500 VA model at 400 W falls short.

Heat trims the rating further. The same 500 VA model drops from 400 W at 25 °C to 350 W at 40 °C, a 12.5% cut that matters in a hot cabinet, a van roof space or a summer above 40 °C.

Not every unit reaches 2×. The 1,600 VA Phoenix lists 1,450 W continuous and 2,200 W peak, only 1.52×, and a lower multiple pushes the same 1,130 W fridge start onto a bigger inverter.

Inverter surge multipleMinimum for 1,130 W peakNext standard size
2.0×565 W600 W
1.8×628 W750 W
1.5×753 W800 W

Divide the peak watts by the continuous watts on the inverter's own data sheet to get its real surge multiple. The Inverter Size Calculator handles the inverter alone when the running and starting watts are already known.

Peak Sun Hours and Off-Grid Solar Panel Size

Each 400 W panel adds about 1,266 Wh a day at 4 peak sun hours, after 8% battery loss and 14% PV loss. Adding or removing one panel moves any solar off grid load calculator result by that much, so low sun hours raise the count fast.

Worst-month sun hoursMinimum array400 W panelsArraySystem voltageCharge controller
2.5 h982 W31,200 W24 V50 A
3 h818 W31,200 W24 V50 A
3.5 h701 W2800 W12 V70 A
4 h614 W2800 W12 V70 A
5 h491 W2800 W12 V70 A
6 h409 W2800 W12 V70 A

The 14% loss is the default in NREL's PVWatts Version 5 manual. It combines soiling 2%, shading 3%, mismatch 2%, wiring 2%, connections 0.5%, light-induced degradation 1.5%, nameplate 1% and availability 3%.

A popular shortcut takes appliance kWh times 1.25 over sun hours. Here it gives 1,630 × 1.25 / 4 = 509 W, about 17% short of 614 W, because it skips the 312 Wh of inverter loss and standby in a solar off grid load calculator draw.

Below 3.5 sun hours the array passes 1,000 W, so a solar off grid load calculator result steps up to 24 V and the controller falls from 70 A to 50 A. The Peak Sun Hours Calculator finds the worst-month figure for a site.

For panel counts on their own, the Solar Panel Size Calculator starts from daily kWh. Tilt changes winter harvest too, and the Solar Panel Tilt Angle Calculator sets the angle for the worst month.

Days of Autonomy: Lithium vs Lead-Acid Banks

Each extra day of autonomy adds 2.43 kWh of LiFePO4 or 3.88 kWh of lead-acid for a 1,942 Wh daily draw. Three days, the usual solar off grid load calculator target, means 7.28 kWh of lithium or 11.65 kWh of lead-acid.

Days of autonomyLiFePO4 at 80% DoDLiFePO4 at 12 VLead-acid at 50% DoDLead-acid at 12 V
12.43 kWh202 Ah3.88 kWh324 Ah
24.85 kWh405 Ah7.77 kWh647 Ah
37.28 kWh607 Ah11.65 kWh971 Ah
512.14 kWh1,011 Ah19.42 kWh1,618 Ah

The lead-acid column uses 50% depth of discharge, matching the advice in Victron's Energy Unlimited never to leave a lead battery more than half discharged. Its cycle table shows AGM lasting 250 cycles at 80% depth but 800 cycles at 60%.

Lead-acid also loses more in each charge cycle. Victron puts full-cycle efficiency near 75% and partial-charge use near 89%, and at 80% the array need rises from 614 W to 706 W, still two 400 W panels.

For an off grid load calculator India setup on 12 V 200 Ah tubular batteries, 971 Ah means five batteries in parallel. At 24 V the same energy is 485 Ah, or three parallel strings of two 200 Ah batteries.

An on-grid system skips this table, since the grid covers cloudy days. Off-grid, the Solar Battery Bank Calculator works out series and parallel strings for a chosen battery.

Cabin, RV and Home Off-Grid Solar System Sizes

A weekend cabin using 1 kWh a day needs a 4.71 kWh lithium bank and one 400 W panel at 4 sun hours. A family home at 20 kWh needs about 90.5 kWh of battery and twenty panels.

UseLoad (Wh/day)Running / extra startInverterBattery draw3-day bankArrayController
Camping kit, all DC540DC onlyNone540 Wh2.03 kWh, 169 Ah at 12 V200 W (2 × 100 W)20 A
Weekend cabin1,000250 W / 900 W600 W1,255 Wh4.71 kWh, 392 Ah at 12 V400 W (1 panel)40 A
RV or van2,300600 W / 900 W750 W2,702 Wh10.13 kWh, 422 Ah at 24 V1,200 W (3 panels)50 A
Small cabin, full time5,0001,500 W / 1,500 W2,000 W6,036 Wh22.63 kWh, 943 Ah at 24 V2,000 W (5 panels)100 A
Efficient home10,0003,000 W / 2,500 W4,000 W12,071 Wh45.27 kWh, 943 Ah at 48 V4,000 W (10 panels)100 A
Family home20,0005,000 W / 3,500 W8,000 W24,142 Wh90.53 kWh, 1,886 Ah at 48 V8,000 W (20 panels)200 A

Every row runs the same solar off grid load calculator math at 4 worst-month sun hours, three days of LiFePO4 at 80% depth, 90% inverter efficiency, 1% standby and 400 W panels, 100 W on the camping kit. The RV row carries 300 Wh of DC loads.

The camping kit runs a 45 W 12 V cooler for 10 h, 10 W of lights for 5 h and two 10 W phone chargers for 2 h. With no AC loads there is no inverter loss or standby, so every listed watt-hour comes straight from the battery.

Standby is why the home rows grow faster than their loads. The 20 kWh home burns 1,920 Wh of inverter idle draw a day, nearly twice the whole weekend cabin load, which any solar off grid load calculator total has to carry.

Appliance Draw, Surge and Season in Off-Grid Loads

In a solar off grid load calculator estimate, the appliance list sets daily energy, motors set the inverter and the season sets the panels. Each answer below keeps those roles apart, using the same 1,630 Wh example load.

What appliances use the most energy off-grid?

Heating and cooling use the most, followed by fridges and freezers that run every day. A 1,500 W space heater on for 4 h uses 6,000 Wh, about 3.7 times the whole 1,630 Wh example list, and 6,667 Wh at the battery.

Kettles and water heaters draw as much power but for minutes, so 1,500 W for 15 minutes is only 375 Wh. In the example solar off grid load calculator list the fridge alone takes 49.1% of the appliance energy, ahead of the laptop and TV at 33.7%.

Should I include surge loads in daily kWh?

Leave surge out of daily kWh and use it only for inverter size in a solar off grid load calculator estimate. A fridge's 900 W of extra starting power lasts seconds, so even 40 starts of 3 seconds each add 30 Wh, under 2% of 1,630 Wh.

The same 900 W still matters for the inverter. It lifts the peak from 230 W to 1,130 W, which moves the inverter from a 300 W unit to a 600 W unit at a 2× surge rating.

Should I size for summer or winter load?

Size the panels for whichever season needs more of them, which is usually winter. With winter hours of 10 h for lights, 7 h for the fridge and 6 h for laptop and TV, the load is 1,680 Wh and the battery draw 1,997 Wh.

At 4 winter sun hours that draw needs 631 W of array, while the 1,942 Wh summer draw at 6 sun hours needs only 409 W. The bank follows the larger draw as well, so three days becomes 7.49 kWh instead of 7.28 kWh.

Summer governs instead where air conditioning, fans or irrigation pumps run long hours. Running separate summer and winter hours through the solar off grid load calculator math reveals which season sets the array before panels are bought.

How do I measure the actual power draw of my appliances?

A plug-in energy meter left on an appliance for 24 to 48 hours gives its real daily Wh for a solar off grid load calculator list, cycling and standby included. A reading of 1.6 kWh over 48 hours is 800 Wh a day, with no run-hour guess needed.

Hard-wired loads such as well pumps need a clamp meter on one conductor. Amps times volts gives apparent power, so a 4.2 A reading on a 230 V pump is 966 VA, at or above its real watts and therefore a safe figure.

Nameplate watts are a maximum. They suit inverter sizing but overstate the daily energy of most motor loads, as the fridge table above shows.

Should I choose a 12V, 24V, or 48V off-grid system?

Choose 12 V up to about 1,000 W of inverter or array, 24 V up to 2,000 W and 48 V above, the usual solar off grid load calculator split. A 10 kWh-a-day home with a 4,000 W inverter pulls 370 A at 12 V but 93 A at 48 V.

The same 45.3 kWh bank is 3,772 Ah at 12 V or 943 Ah at 48 V, and charge current drops from 333 A to 83 A. Lower current means thinner cable and less voltage drop, which the Solar Wire Size Calculator checks run by run.